Lennox International Inc 51M37 operation manual 75 75 OFF, 5 30 FAN, HEAT − Using the Heat Mode

Models: 51M37

1 54
Download 54 pages 14.47 Kb
Page 3
Image 3
HEAT − Using the Heat Mode

HEAT − Using the Heat Mode

Normal Heat Mode

In normal heat mode, both the heat pump and the backup heat source are used to provide heat. If the thermostat de- tects that the heat pump is not able to provide enough heat (as may be the case in very cold weather), then the backup heat source is activated.

Emergency Heat Mode

In emergency heat mode, only the backup heat source provides heat

heat source is activated only when there is a heat demand.

Enabling Normal Heat Mode

Use the HEAT button to select normal heat mode, emer- gency heat mode, or to disable heat modes as desired. If the thermostat is in OFF or COOL mode, pressing the Heat button enables Heat mode. This is indicated by HEAT in the SYSTEM box as shown in figure 4.

 

 

Normal Heat Mode Enabled

 

 

 

Heat

Cool

MO

 

 

 

 

AM

5:30 FAN

Prog

Day/Time

PM

 

HOLD AUTO

 

 

 

 

 

 

SYSTEM

 

 

ROOM

SETPOINT

 

 

66° 70° HEAT

Fan

Hold

 

 

 

Settings Enter

Figure 4

Enabling Emergency Heat Mode

If the thermostat is in heat mode, pressing the Heat button enables EMG. HEAT mode (see figure 5). If the thermostat is in normal heat mode when the HEAT button is pressed, then emergency heat mode is enabled.

Emergency Heat Mode Enabled

ROOM

SYSTEM

62°

SETPOINT

75° EMG.

 

HEAT

Figure 5

Disabling Heat Mode

If the thermostat is in emergency heat mode when the HEAT button is pressed, then heat modes are disabled. This is indicated by OFF in the SYSTEM box as shown in figure 6.

Heat Mode Disabled

ROOM

SYSTEM

°SETPOINT

75 75° OFF

Figure 6

Heating Demand

The thermostat must be in either normal or emergency heat mode in order to properly control the heating equip- ment. In either heat mode, when the actual temperature is lower than the temperature setpoint (as shown in figure 7), the thermostat detects a heating demand and activates the heating equipment to satisfy the demand. Heating opera- tion is indicated by a flame icon in the SYSTEM box.

Heating Demand

ROOM

SYSTEM

SETPOINT

72°

75°

 

HEAT

Figure 7

When the actual temperature rises above the temperature setpoint, the flame icon will disappear. This indicates that the heating demand has been satisfied and that the heat- ing equipment has been turned off.

Heat pump operation is locked out for 5 minutes after a de- mand has been satisfied. If another heat pump demand occurs during this 5−minute interval, the flame icon will flash; however, the heat pump will not run until the 5−min- ute delay has elapsed.

NOTE − The heat pump is activated for at least 4 minutes if no buttons are pressed during the demand interval. The backup heat source is activated for at least 3 minutes if no buttons are pressed during the demand interval.

If your system supports 3−stage heating (as does the 51M37 thermostat), you may notice various heating levels being delivered during a demand.

If a small heat pump heating demand is present, "Lo" is dis- played in the SYSTEM box; if a large heat pump heating demand is present, "Hi" is displayed (see figure 8).

Large Heat Demand

ROOM

 

 

 

SYSTEM

 

65

°

SETPOINT COOL

 

75

°

OFF

Hi

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HEAT

 

Figure 8

Page 3

51M37 SERIES 5/2

Page 3
Image 3
Lennox International Inc 51M37 operation manual 75 75 OFF, 5 30 FAN, HEAT − Using the Heat Mode