Thermostat Output Table
Table 5 depicts the 51M37 thermostat output states for var- ious input conditions. The following notes described terms used in the table.
NOTES:
SX = output is activated with 24VAC.
SBBP: outdoor temperature is below balance point
SABP: outdoor temperature is above balance point
SIn all cases, the state of the B terminal is opposite that of the O terminal
SData are tabulated for AUTO fan setting. If the fan set- ting is ON, the G output is activated in all cases
SUpstage timers:
30 minutes (when upstaging from small to large demand)
15 minutes (HEAT MODE ONLY − when upstaging from large to very large demand)
SThe temperature ranges expressed in the following definitions of Y LARGE" de-
mands are for guidance only; actual temperatures may vary:
With a small HEAT demand, temperature is: below setpoint
With a large HEAT demand, temperature is: less than setpoint
OR
With a very large heat demand, temperature is:
below setpoint
OR 15−minute 2nd upstage timer HAS expired.
Emergency heat demand (only if emergency heat is enabled): temperature is below setpoint
With a small COOL demand, temperature is: above setpoint +0.5F but below setpoint +1.5F AND
With a large COOL demand, temperature is: above setpoint +1.5F
OR
Table 5
THERMOSTAT OUTPUTS
Demand Condition | W1 | E | Y1 | Y2 | G | O |
|
|
|
|
|
|
|
Cooling Demands
SMALL |
|
|
|
| X |
| X | X |
|
|
|
|
|
|
|
|
|
LARGE |
|
|
|
| X | X | X | X |
|
|
|
|
|
|
|
|
|
No Demand |
|
|
|
|
|
|
| X |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
| Heating Demands |
|
|
|
| |||
|
|
|
|
| ||||
|
|
|
|
| ||||
w/Electric Backup (no outdoor sensor) |
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
SMALL |
|
|
|
| X |
| X |
|
|
|
|
|
|
|
|
|
|
LARGE |
|
|
|
| X | X | X |
|
|
|
|
|
|
|
|
|
|
Very LARGE |
| X |
|
| X | X | X |
|
|
|
|
|
|
|
|
|
|
Emergency |
|
| X |
|
|
| X |
|
|
|
|
|
|
|
|
|
|
No Demand |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
w/Gas Backup (dual fuel; no outdoor sensor)
SMALL |
|
| X |
|
| X |
|
|
|
|
|
|
|
|
|
LARGE |
|
| X |
| X | X |
|
|
|
|
|
|
|
|
|
Very LARGE | X |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Emergency |
| X |
|
|
|
|
|
|
|
|
|
|
|
|
|
No Demand |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
w/Electric Backup (outdoor sensor attached) |
|
|
| ||||
|
|
|
|
|
|
| |
SMALL (Above Balance Point) |
|
| X |
|
| X |
|
|
|
|
|
|
|
|
|
LARGE (ABP) |
|
| X |
| X | X |
|
|
|
|
|
|
|
|
|
Very LARGE (ABP) |
|
| X |
| X | X |
|
|
|
|
|
|
|
|
|
SMALL (Below Balance Point) |
|
| X |
|
| X |
|
|
|
|
|
|
|
|
|
LARGE (BBP) |
|
| X |
| X | X |
|
|
|
|
|
|
|
|
|
Very LARGE (BBP) | X |
| X |
| X | X |
|
|
|
|
|
|
|
|
|
Emergency |
| X |
|
|
| X |
|
|
|
|
|
|
|
|
|
No Demand |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
w/Gas Backup (dual fuel; outdoor sensor attached)
SMALL (ABP) |
|
| X |
| X |
|
|
|
|
|
|
|
|
LARGE (ABP) |
|
| X | X | X |
|
|
|
|
|
|
|
|
Very LARGE (ABP) | X |
|
|
|
|
|
|
|
|
|
|
|
|
SMALL (BBP) | X |
|
|
|
|
|
|
|
|
|
|
|
|
LARGE (BBP) | X |
|
|
|
|
|
|
|
|
|
|
|
|
Very LARGE (BBP) | X |
|
|
|
|
|
|
|
|
|
|
|
|
Emergency |
| X |
|
|
|
|
|
|
|
|
|
|
|
No Demand |
|
|
|
|
|
|
|
|
|
|
|
|
|
Page 10
505050M 5/1/05