Lennox International Inc 51M37 operation manual Thermostat Output Table, 35F to 105F, 5% to 90% RH

Models: 51M37

1 54
Download 54 pages 14.47 Kb
Page 26
Image 26
Manual background

Maintenance Reminder

Settings of Off, 6 or 12 (months of chronological time) are available. When programmed time has elapsed, a mainte- nance indicator

Service Reminder

The SERVICE indicator is displayed only under the follow- ing conditions:

Sif the thermostat Y1 terminal has been activated with 24VAC for at least 5 minutes, AND the L terminal is shorted to the R terminal;

OR

Sif the thermostat Y1 terminal has been activated with 24VAC for at least 5 minutes, AND the L terminal is shorted to the C terminal.

Power Loss/Recovery

Thermostat memory is retained for a minimum of 24 hours during a power loss (includes retention of program infor- mation, HOLD status, programmed temperature setpoint, heat/cool and fan mode settings, filter reminder status, maintenance reminder status, and equipment protection timers). After 24 hours of power loss, programmed settings will be lost and replaced with default settings.

Manual background IMPORTANT

Power must be applied for at least six consecutive hours prior to a power loss in order for memory to be retained for the specified time.

LCD Backlight

Activated for 30 seconds when any button is pressed.

NOTE − During an electrical storm or similar disturbance, the backlight may activate for a few seconds. This is nor- mal and will no longer occur after the electrical disturbance has passed.

Thermostat Operating Conditions

35°F to 105°F, 5% to 90% RH

Thermostat Storage Conditions

−40°F to 185°F, 5% to 95% RH

Thermostat Output Table

Table 5 depicts the 51M34 thermostat output states for var- ious input conditions.

Table 5

Thermostat Outputs

Condition

W1

Y1

G

 

 

 

 

Gas Heat, Auto Fan

HEAT Demand

X

 

 

 

 

 

 

COOL Demand

 

X

X

 

 

 

 

No Demand

 

 

 

 

 

 

 

Gas Heat, Continuous Fan

 

 

 

 

 

 

HEAT Demand

X

 

X

 

 

 

 

COOL Demand

 

X

X

 

 

 

 

No Demand

 

 

X

 

 

 

 

Electric Heat, Auto Fan

 

 

 

 

 

 

HEAT Demand

X

 

X

 

 

 

 

COOL Demand

 

X

X

 

 

 

 

No Demand

 

 

 

 

 

 

 

Electric Heat, Continuous Fan

 

 

 

 

HEAT Demand

X

 

X

 

 

 

 

COOL Demand

 

X

X

 

 

 

 

No Demand

 

 

X

 

 

 

 

NOTE − X = output is activated with 24VAC.

Page 8

505048M 5/1/05

Page 26
Image 26
Lennox International Inc 51M37 operation manual Thermostat Output Table, 35F to 105F, 5% to 90% RH