Lennox International Inc 51M37 operation manual HEAT − Using the Heat Mode, Normal Heat Mode

Models: 51M37

1 54
Download 54 pages 14.47 Kb
Page 39
Image 39
Manual background

HEAT − Using the Heat Mode

Normal Heat Mode

In normal heat mode, both the heat pump and the backup heat source are used to provide heat. If the thermostat de- tects that the heat pump is not able to provide enough heat (as may be the case in very cold weather), then the backup heat source is activated.

Emergency Heat Mode

In emergency heat mode, only the backup heat source provides heat

heat source is activated only when there is a heat demand.

Enabling Normal Heat Mode

Use the HEAT button to select normal heat mode, emer- gency heat mode, or to disable heat modes as desired. If the thermostat is in off or cool mode, pressing the HEAT button enables heat mode. This is indicated by HEAT in the lower right corner (see figure 4).

 

Normal Heat Mode Enabled

 

 

 

Heat

Cool

 

 

5:30

Prog

Auto

 

 

 

 

 

 

82

Copy Day/Time

 

 

 

 

 

70

70

Fan

Hold

(DOOR

 

 

 

 

 

 

OPEN)

 

 

Settings Enter

 

 

 

 

(Outside)

 

Figure 4

Enabling Emergency Heat Mode

If the thermostat is in heat mode, pressing the HEAT button enables emergency heat mode (see figure 5). If the ther- mostat is in normal heat mode when the HEAT button is pressed, then emergency heat mode is enabled.

Emergency Heat Mode Enabled

ROOM

 

62°

HEAT SETPOINT EMG.

75° HEAT

Figure 5

Disabling Heat Mode

If the thermostat is in emergency heat mode when the HEAT button is pressed, then heat modes are disabled. This is indicated by OFF near the right side of the display as shown in figure 6.

Heat Mode Disabled

ROOM

 

OFF

 

75°

75°

 

 

 

HEAT SETPOINT

 

 

 

 

Figure 6

 

 

 

Heating Demand

The thermostat must be in either normal or emergency heat mode in order to properly control the heating equip- ment. In either heat mode, when the actual temperature is lower than the temperature setpoint (as shown in figure 7), the thermostat detects a heating demand and activates the heating equipment to satisfy the demand. Heating opera- tion is indicated by a flame icon in bottom right−hand corner of the display.

Heating Demand

ROOM

 

72°

HEAT SETPOINT

75° HEAT

Figure 7

When the actual temperature rises above the temperature setpoint, the flame icon will disappear. This indicates that the heating demand has been satisfied and that the heat- ing equipment has been turned off.

Heat pump operation is locked out for 5 minutes after a de- mand has been satisfied. If another heat pump demand occurs during this 5−minute interval, the flame icon will flash; however, the heat pump will not run until the 5−min- ute delay has elapsed.

NOTE − The heat pump is activated for at least 4 minutes if no buttons are pressed during the demand interval. The backup heat source is activated for at least 3 minutes if no buttons are pressed during the demand interval.

If your system supports 3−stage heating (as does the 51M42 thermostat), you may notice various heating levels being delivered during a demand.

If a small heat pump heating demand is present, "Lo" is dis- played in the SYSTEM box; if a large heat pump heating demand is present, "Hi" is displayed (see figure 8).

Large Heat Heating Demand

ROOM

 

 

65

°

75°

Hi

 

 

HEAT SETPOINT

 

 

 

 

HEAT

 

 

 

Lo

Figure 8

Page 3

51M42 SERIES 5/2

Page 39
Image 39
Lennox International Inc 51M37 operation manual HEAT − Using the Heat Mode, Normal Heat Mode