34

Chapter 4 Operator Control And Display Panel

Help information

Select the current record window

Select the previous menu item

Select the next menu item

Q3

Q2

Q1

Q5

 

 

 

 

?

F1

F2

F3

F4

HELP

 

Figure 4-7

Help screen

 

Operation of the HELP key:

1.Only at the primary screen can you use the HELP key to display the help screen.

2.The HELP key is invalid at the start screen.

3.At the default screen, help screen, or when the LCD backlight is off, the primary screen will return if you press the HELP key.

4.3Prompt Window

A prompt window is displayed during the operation of the system to alert you to certain conditions and/or to require your confirmation of a command. The prompts are provided in Table 4-7.

 

Table 4-7 Prompts and meanings

 

 

 

No.

Prompt

Meaning

1

Transfer with interrupt, confirm or

Inverter and Bypass supplies are not synchronized and any load transfer

cancel

between the supplies will cause a brief load interruption

 

 

 

 

2

The load is too high to be

The total load must be less than the capacity of one unit to allow a parallel

transferred with interrupt

system to perform an interrupted transfer from bypass to inverter

 

 

 

 

3

This operation leads to output

No alternative supply is available and any Inverter Off operation will cause the

shutdown, confirm or cancel

load to be de-energised

 

 

 

 

4

This operation leads to inverter

Turning off this inverter will lead to the overload of remaining inverter(s) in a

overload, confirm or cancel

parallel system

 

 

 

 

5

Turn on more UPS to carry current

The number of paralleled inverters already turned on is insufficient to carry the

load

existing load

 

 

 

 

 

Battery will be depleted, confirm or

Battery capacity test discharges the battery 100%. This prompt apears to

6

require your confirmation. Cancelling the test will ends the test and transfers the

cancel

 

UPS to Normal mode

 

 

 

 

 

7

System selftest finished, everything

No action required

is ok

 

 

 

 

 

8

System selftest finished, please

Check the current record window

check the current warnings

 

 

 

 

 

9

Enter control password

Required for battery or UPS test (default: 12345)

 

Battery selftest condition is low,

Battery test condition is not met. Please check whether the battery is in boost

10

please check battery state and

charge state and the load level meet the battery test conditions. To initiate the

 

loadlevel

battery test, the load must range between 20% and 80%

 

 

 

 

Freshening charge condition is low,

This prompt appears when you select the freshening charge command while

11

please check battery settings and

the freshening charge condition is not met (such as no battery, charger failure)

 

state

 

 

 

 

 

HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

Page 44
Image 44
Emerson U/300/S/6P, U/300/S/12P, U /400/S/12P, U /400/S/6P, 400KVA, 200, 160 user manual Prompt Window