Emerson 200, 400KVA Bypass Supplies, System Control Philosophy, Normal operation, Mains failure

Models: U /400/S/12P U/300/S/6P 160 200 U/300/S/12P 400KVA U /400/S/6P

1 79
Download 79 pages 37.39 Kb
Page 12
Image 12
1.2.2 Bypass Supplies

2

Chapter 1 General Description

1.2.2 Bypass Supplies

The circuit block annotated “Static switch” in Figure 1-2 contains an electronically controlled switching circuit, which enables the critical load to be connected either to the inverter output or to a bypass power source through the static bypass line. During normal system operation, the load is connected to the inverter, and the inverter-side of the static switch is closed. But in the event of a UPS overload or inverter failure, it is automatically transferred to the static bypass line.

Bypass

 

 

 

 

mains supply

Maintenance bypass switch Q3

UPS

 

 

Bypass switch Q2

 

 

 

Input mains

Rectifier

Inverter

Static switch

 

 

 

 

 

supply

DC bus

 

 

 

 

 

 

 

 

Input switch Q1

 

Output switch Q5

UPS output

 

 

 

 

 

C.B.

 

 

 

Battery

Battery circuit breaker

Figure 1-2 UPS power switches configuration

To provide a clean (no-break) load transfer between the inverter output and static bypass line, the static switch activates connecting the load to the bypass supplies. To achieve this, the inverter output and bypass supply must be fully synchronized during normal operating conditions. This is achieved through the inverter control electronics, which make the inverter frequency track that of the static bypass supply provided that the bypass remains within an acceptable frequency window.

A manually controlled, maintenance bypass supply is also incorporated into the UPS design. Its purpose is to enable the critical load to be powered from the mains (bypass) supply while the UPS is shut down for routine maintenance.

Note: The load equipment is not protected from normal supply aberrations when operating on bypass side or in the maintenance bypass mode.

1.2.3 System Control Philosophy

Normal operation

During normal operation, that is, when the UPS input supply is present and within specification, both the rectifier and inverter sections are active and the static switch is turned on to connect the inverter output to the critical load busbars. The battery circuit breaker (BCB) is also closed and the battery is therefore permanently float charged at the DC busbar voltage level.

(“1+N” parallel UPS system) Note: As the unit outputs are connected in parallel, the system checks that the inverter control circuits are perfectly synchronized with one another and with the bypass mains in terms of both frequency and phase and that they have the same output voltages. Current supplied to the load is automatically divided among UPSs. A warning message appears while synchronization is in progress.

A module's static switch cannot close until these conditions are satisfied.

Mains failure

If the power mains has a failure or is out of tolerance the rectifier will go off automatically, while the inverter will continue to operate on power from the battery for a period of time which depends on the load and the capacity of the battery. If the mains supply has not returned within this time, the inverter will go off automatically and an alarm message will appear on the operator control and display panel of the UPS.

Critical load will not be interrupted in the event of a drop or return of the AC power mains.

HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

Page 12
Image 12
Emerson 200, U/300/S/12P, U /400/S/12P, 400KVA Bypass Supplies, System Control Philosophy, Normal operation, Mains failure