64

Appendix 1 Transportation Restraints Removing Procedures

Appendix 1 Transportation Restraints Removing Procedures

1.160kVA&200kVA UPS Transportation Restraints Removing Procedures

Transformer transportation restraints removing procedures for UPS with 6-pulse rectifier

1.Open the front door of the cabinet, remove the lower switch baffle plate and the installation hole cover, as shown in Figure 1. Retain the screws.

Installation hole安装孔cover盖板

Screw

A

A amplified view

Figure 1 Removing the installation hole cover

2. Remove the back panel of the cabinet to reveal the output transformer, as shown in Figure 2. Retain the screws.

M10boltM12bolt

 

 

固定件

Output

 

Transportation

 

restraint

变压

 

transformer

 

 

 

 

A放大

 

A

A amplified view

 

 

Figure 2 Removing the output transformer transportation restraints

3.There is a transportation restraint respectively in the front and at the back at the bottom of the output transformer. The one at the back is shown in Figure 2. Remove the fixing bolts of the one at the back, including two M10 bolts in the middle and two M12 bolts at sides; then, remove the fixing bolts, including two M10 bolts in the middle and two M12 bolts at sides, of the transportation restraint in the front through the installation hole revealed in step 1.

4.Remove the two transportation restraints, and install the four M12 bots removed in step 3 in their original positions.

HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

Page 74
Image 74
Emerson 400KVA, 200 Appendix 1 Transportation Restraints Removing Procedures, 螺Screw钉 Amplified view, M10螺bolt栓 M12螺bolt栓