1.1 System Electrical Characteristics

Table 3:Power Module Ratings

Part Number 86055 86075 86115
Apparent Power, kVA 5 7 10@ 200/208/250 VAC Output
11@ 220/230/240 VAC Output
Active Power, kW 4 4.9 8@ 200/208/250 VAC Output
7.3@ 220/230/240 VAC Output
Input Current, A 25/24/23/ 35/34/32 50/48/50/48/46/40
22/21/20 31/30/28
Input Voltage, VAC 200/208/220/ 200/208/220/ 200/208/220/230/240/250
230/240/250 230/240/250
Output Current, A 25/24/23/ 35/34/32 50/48/50/48/46/40
22/21/20 31/30/28
Output Voltage, VAC 200/208/220/ 200/208/220/ 200/208/220/230/240/250
230/240/250 230/240/250
CAUTION Power Module is factory configured at 208Vac,60 Hz input and output.
Input and Output of the UPS must always be the same.

Table 4:Battery Module Ratings

Part Number 86079 86119
Battery Type 12VDC/7Ah 12VDC/9Ah
Battery Output Voltage 240VDC 240VDC

1.2 Standard Configurations

The EX 5/7/11 RT systems can be set up in tower and rack configurations.

1.2.1 Tower Configuration

Figure 1-1: Tower Configurations with Power Module, Battery Module, and optional Transformer Module.

EX 5/7/11 RT System
Introduction1 — 4 86-86000-00 A01
www.mgeups.comwww.mgeups.com
E X B R T
E X 1 1 R T
OFFON
BATTERY MODULE
(EXB 5/7/11 RT)
POWER MODULE
(EX 5/7/11 RT)
www.mgeups.comwww.mgeups.com
OFFON
BATTERY MODULE
POWER
MODULE
EX 11 RT EXB RT
EX RT Transformer
EX RT Transformer
www.mgeups.c
om
Standard Configuration Configuration with Transformer