MGE UPS Systems EX 5RT, EX 11RT, EX 7RT user manual Display Factory setting Options Comments

Models: EX 7RT EX 11RT EX 5RT

1 72
Download 72 pages 54.19 Kb
Page 47
Image 47

 

 

 

Installation and User Manual

 

 

 

 

 

Table 3-1: Local Settings.

 

 

 

 

 

 

 

 

 

Display

Factory setting

Options

 

 

 

 

 

 

Language

English

French, Spanish, German, Italian

 

 

 

 

 

 

Date / time format

International format

US format

 

 

(DD-MM-YYYY/HH:MM)

(MM-DD-YYYY/HH:MM AM/PM)

 

 

 

 

 

 

Date / time change

GMT (Greenwich Mean Time)

MM-DD-YYYY/HH:MM adjustable

 

 

 

 

 

 

Audible alarm

Quick beeps

Slow beeps

 

 

 

 

 

Table 3-2: Output features.

Display

Factory setting

Options

Comments

 

 

 

 

Output voltage

208 Volts AC

200/208/220/230/240/250

 

 

 

 

 

Frequency converter

Disabled

Enabled

Bypass AC source disabled

 

 

 

 

Output frequency

Auto ranging

50/60 Hz

User selectable under

 

 

 

frequency converter mode

 

 

 

 

Eco mode

Disabled

Enabled

See glossary

 

 

 

 

Hot standby

Disabled

Enabled

Full redundancy (see Figure 3-3)

 

 

 

 

Operating mode

IT Network

Industrial

(*) See Section 4.1

 

 

 

 

Bypass

When bypass OK (**)

When bypass NOK (**)

(*)

Transfer

 

 

 

 

 

 

 

Interrupt time

10 ms

10 to 200 ms

Interrupt time calibration during

 

 

(by steps of 10 ms)

during load transfer on

 

 

 

Bypass AC source

 

 

 

out of tolerances

 

 

 

 

Overload level

102%

50/70%

 

(*) : - Select "IT Network" for computer loads.

-Select "Industrial" when bypass NOK in case of absolute need for service continuity (with potential 10 ms interrupt).

(**) UPS will switch to Bypass AC Source if it is within the set tolerances.

Figure 3-3: Configuration used to provide full redundancy (2N) to critical loads.

BYPASS AC

Protective Device

NORMAL AC

Utility

AC Source

Full redundancy configuration offers better protection to critical load, whereas the first UPS acts as the Bypass AC Source for the second UPS.

Protective Device NORMAL AC

LOAD

86-86000-00 A01

Operation

3 — 3

Page 47
Image 47
MGE UPS Systems EX 5RT, EX 11RT, EX 7RT user manual Display Factory setting Options Comments