| Installation and User Manual | |
|
|
|
|
|
Table |
|
|
| |
|
|
|
|
|
| Display | Factory setting | Options | |
|
|
|
|
|
| Language | English | French, Spanish, German, Italian | |
|
|
|
|
|
| Date / time format | International format | US format | |
|
|
|
| |
|
|
|
|
|
| Date / time change | GMT (Greenwich Mean Time) | ||
|
|
|
|
|
| Audible alarm | Quick beeps | Slow beeps | |
|
|
|
|
|
Table
Display | Factory setting | Options | Comments |
|
|
|
|
Output voltage | 208 Volts AC | 200/208/220/230/240/250 |
|
|
|
|
|
Frequency converter | Disabled | Enabled | Bypass AC source disabled |
|
|
|
|
Output frequency | Auto ranging | 50/60 Hz | User selectable under |
|
|
| frequency converter mode |
|
|
|
|
Eco mode | Disabled | Enabled | See glossary |
|
|
|
|
Hot standby | Disabled | Enabled | Full redundancy (see Figure |
|
|
|
|
Operating mode | IT Network | Industrial | (*) See Section 4.1 |
|
|
|
|
Bypass | When bypass OK (**) | When bypass NOK (**) | (*) |
Transfer |
|
|
|
|
|
|
|
Interrupt time | 10 ms | 10 to 200 ms | Interrupt time calibration during |
|
| (by steps of 10 ms) | during load transfer on |
|
|
| Bypass AC source |
|
|
| out of tolerances |
|
|
|
|
Overload level | 102% | 50/70% |
|
(*) : - Select "IT Network" for computer loads.
-Select "Industrial" when bypass NOK in case of absolute need for service continuity (with potential 10 ms interrupt).
(**) UPS will switch to Bypass AC Source if it is within the set tolerances.
Figure 3-3: Configuration used to provide full redundancy (2N) to critical loads.
BYPASS AC
Protective Device
NORMAL AC
Utility
AC Source
Full redundancy configuration offers better protection to critical load, whereas the first UPS acts as the Bypass AC Source for the second UPS.
Protective Device NORMAL AC
LOAD
Operation | 3 — 3 |