2.10 Connection of CLA Module
1. Connect the battery power cable and battery detection cable (provided with the CLA module)
between the power module and the CLA module.
2. Connect the DC Input of the CLA to high power battery cabinet.
DC Input Cable cross-section (not provided):maximum 4 AWG solid or stranded wire.
3. Connect the AC input cable of the CLA module to the utility AC input:
AC input cable cross-section (not provided):maximum 16 AWG solid or stranded wires.
Figure 2-18: Rear view of CLA module cable battery and AC input connections.
4240
EX 5/7/11 RT System
Installation2 — 20 86-86000-00 A01
To High
Power Battery
Cabinet
Utility AC Source
42
40

Connection Diagram

(inside CLA Module)

- +

DC INPUT
240Vdc
N L
(L2) (L1)
AC INPUT
156-280Vac