R4795A
INSTALLATION
Replacing RA890E,F,G with R4795A
1.Disconnect all wires from terminal 1, and splice with solderless connector. (If RA890 has no terminal 1 wiring, disregard this step.)
2.Remove line voltage controller wire from terminal 6 and connect to terminal 1.
3.Move burner motor connection from terminal 3 to ter- minal 6 on subbase.
4.Remove jumper from T and T and install air switch. If low voltage control was wired to RA890
5.If R482D Relay was used with RA890E, remove it. The R482D is redundant when R4795D is used.
6.Check for proper operation through at least two cycles.
Fig. 4—Replacing RA890E,F,G with R4795A on gas or oil burner.
REPLACING RA890 WITH R4795 ON GAS OR OIL BURNER
R4795C Replacement
In most cases, the R4795A can directly replace the R4795C. For standing pilot applications where the pilot flame was detected during the off cycle, install a relay as shown in Fig. 5.
Flame Detector Wiring
See Fig. 6.
Alarm Contacts
Models with alarm contacts have three male
If a line voltage alarm is used with the R4795, mount the entire control in a suitable enclosure.
|
|
|
|
|
|
|
| Fig. | |
BEFORE | standing pilot application, install relay 1R to | ||||||||
CONTROLLER HIGH LIMIT |
| prevent detection of pilot flame during burner | |||||||
MAIN GAS | |||||||||
|
|
|
|
|
|
| off cycle. | ||
|
|
|
|
|
|
| VALVE OR | ||
|
|
|
|
|
|
| |||
|
|
|
|
|
|
| 2ND STAGE |
| |
|
|
|
|
|
|
| OIL VALVE |
|
|
| 6 |
| 5 |
|
|
|
|
|
|
|
|
|
|
| IGNITION |
|
|
|
|
|
|
|
|
| T |
| TRANSFORMER |
|
|
|
|
| MIAN FUEL |
|
|
|
| 4 |
| BURNER |
| 5 |
| |||
|
|
|
|
|
| 8 | VALVES |
| |||
|
|
|
| BURNER |
| MOTOR | 2K3 |
| |||
|
|
|
|
|
|
|
| ||||
|
| T |
| MOTOR |
|
|
|
|
|
|
|
|
|
| 3 |
|
|
|
| 4 |
|
| |
|
|
|
|
|
|
|
|
|
|
| |
FLAME |
|
|
| PILOT OR |
|
|
| 7 | 2K2 |
|
|
| F |
| OIL VALVE |
|
|
|
|
|
|
| |
DETECTOR |
|
|
| L1 |
|
|
|
|
|
| |
|
|
|
|
|
|
| 3 |
|
| ||
|
|
|
| 1 | (HOT) |
|
|
| 1R |
| |
|
|
|
| AIR FLOW |
|
|
| ||||
|
|
|
|
|
|
| 1K4 |
| |||
|
| G |
|
| 120V | 6 |
|
| |||
|
|
|
| SWITCH |
|
| |||||
|
|
| 2 | L2 |
|
|
|
| |||
|
|
|
|
|
|
|
|
|
| ||
|
| RA890 WITH Q270 |
|
|
| 1R1 |
| 3K2 |
|
| |
|
|
|
|
| F |
|
|
| |||
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
| TO FLAME |
| FLAME |
|
| |
AFTER |
|
|
|
|
| DETECTOR |
| AMPLIFIER |
|
| |
|
|
|
|
|
|
| G |
|
|
| |
| CONTROLLER | HIGH LIMIT |
|
|
|
|
|
| |||
|
| (FLAME ROD |
|
|
|
| |||||
|
|
|
| MAIN GAS |
|
| 1 | CONTROLLER |
| ||
|
|
|
|
| OR UV |
|
| ||||
|
|
|
| VALVE OR |
|
|
|
|
| ||
|
|
|
| 2ND STAGE |
| DETECTOR) |
|
|
|
| |
|
|
|
| OIL VALVE |
|
|
|
| 3 |
|
|
| 6 | 8 |
| 5 |
|
|
|
| 2 |
|
|
|
|
|
|
|
|
| LIMIT(S) | 2 | |||
|
|
|
| IGNITION |
|
|
|
|
|
|
|
AIR FLOW |
|
|
| TRANSFORMER |
|
|
| R4795A |
|
| |
T | 7 |
| 4 |
|
|
|
|
| |||
SWITCH |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| BURNER |
|
|
|
|
|
|
|
| T | 6 |
| MOTOR |
|
|
|
|
|
|
|
|
| 3 |
|
|
|
|
| 1 |
| ||
|
|
|
|
|
|
|
|
|
| ||
|
| SODERLESS | PILOT OR |
|
|
|
| L2 | L1 |
| |
|
|
|
|
|
| (HOT) |
| ||||
FLAME |
|
|
|
|
|
|
| ||||
F | CONNECTION | OIL VALVE |
|
|
|
|
|
| |||
|
|
|
|
|
|
| |||||
DETECTOR |
|
|
|
| L1 | 1 | POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD | ||||
|
|
|
|
| |||||||
|
|
|
|
|
| PROTECTION AS REQUIRED. |
|
| |||
|
|
|
|
| (HOT) |
|
|
| |||
|
|
|
| 1 |
|
|
|
|
|
| |
| G |
|
| 120V | 2 | REFER TO SPECIFICATIONS SECTION FOR RECOMMENDED LIMITS. | |||||
|
|
|
|
| |||||||
|
| RA4795 WITH Q270 | 2 | L2 | 3 | LOW VOLTAGE CIRCUIT OMITTED. |
| M8685 | |||
|
|
|
|
|
|
|
|
| |||
|
|
|
|
| M8684 |
|
|
|
|
|
|
6 |