F120 ROOM AIR CLEANING SYSTEM
SPECIFICATIONS
IMPORTANT
The specifications given in this publication do not include normal manufacturing tolerances. Therefore, this unit may not exactly match the listed specifica- tions. This product is tested and calibrated under closely controlled conditions, and some minor differ- ences in performance can be expected if those con- ditions are changed.
Model:
F120 consists of:
recirculating air supply openings, four recirculating air return openings and an optional exhaust opening;
Air Flow Capacity:
Color:
Blower Housing: Unpainted galvanized steel.
Return and Supply Grilles:
Electrical Ratings:
|
| 120 Vac, 60 Hz | 240 Vac, 60 Hz | ||
|
| Fan Speeda | Fan Speeda | ||
|
| II (high) | I (low) | II (high) | I (low) |
Current | (A) | 7.0 | 5.5 | 3.5 | 2.8 |
Power | (W) | 800 | 695 | 800 | 695 |
aOff is “O”.
|
| Efficiency |
|
| Air Vol cfm | |
|
| Particulates at 0.3 | VOC/Odors | Gas, VOC, Odor | Air Vol cfm | |
Model | Voltage | micron (DOP Test) | (First Pass Average) | Control Module (2) | (cu m/hr) | (cu m/hr)a |
F120A 1023 | 120 Vac 60 Hz | 95% | 85% | CPZ | 900 (1530) | 1050 (1780) |
|
|
|
|
|
|
|
F120A 1031 | 120 Vac 60 Hz | 99.97% | — | — | 900 (1530 | 1000 (1700) |
|
|
|
|
|
|
|
F120A 1015 | 120 Vac 60 Hz | b | b | b | — | — |
|
|
|
|
|
|
|
aWith exhaust option installed.
bPurchase filters separately.
Filters:
HEPA: High efficiency particulate air (HEPA) filter is 99.97 per- cent efficient for 0.3 micron particulates when measured with Military Standard 282 DOP test.
DOP:
CPZ: Sorbent modules contain 11 pounds of sorbent. Adsorbs higher molecular weight hydrocarbons and oxidizes acid gases and lower molecular weight hydrocarbons.
Ambient Temperature Rating:
Shipping and Storage:
Operating: Ambient temperatures ≥90°F (32°C). Can tolerate 104°F (40°C) for brief periods.
Sound Output Rating at 3.3 ft (1m):
High Speed: 52 dBA (below ASHRAE noise criteria (NC) curve specifications for NC45 over speech recognition fre- quency range of 500 to 2000 Hz).
Low Speed: 45 dBA (below ASHRAE noise criteria (NC) curve for NC35 over speech recognition frequency range of 500 to 2000 Hz).
Installation Weight:
Blower Module: 63 lb (28.6 kg).
Supply Module: (4 required): 8 lb (3.6 kg).
Return Module without filter (2 required): 24 lb (10.9 kg).
95% DOP Filter/CPZ Module (2 required): 21 lb (9.5 kg).
99.97% HEPA Filter (2 required): 10 lb (4.5 kg).
Shipping Weight:
F120 with 95% DOP Filter and CPZ Module: 207 lb (94 kg).
F120 with 99.97% HEPA Filter: 182 lb (83 kg).
F120A1015: 152 lb (69 kg).
F120A1007: 70 lb (32 kg).
Dimensions:
See Fig. 1.
2 |