User Manual

Chapter 3 – Installation Procedure

Network Power Switch

4 Chapter 4 - Specifications

4.1General Specifications

Manual and Automatic Transfers

Sense and transfer time – less than 6 milliseconds

Break-Before make switching

Selectable preferred source

Selectable auto/manual retransfer

In-phase transfer window – adjustable from 5 ± 1°

Convection cooling

Hot swappable electronic static switching module

Live mimic on Hot swappable unit for indicating load supply status & alarms

Make before break manual bypass switch to transfer load from static switch to direct source 1 or source 2

4.2Electrical Specifications

 

ELECTRICAL

 

UNITS

DESCRIPTION

 

CHARACTERISTICS

 

 

 

 

 

 

 

 

 

 

 

Nominal Input Voltage

 

Volts

110, 115 or 120 volts singe phase, 3W+G, 50 Hz. Solidly grounded

 

 

 

 

power sources

 

Nominal Output current

 

Amps

25

 

 

 

 

 

 

Frequency

 

Hz

50 / 60

 

 

 

 

 

 

Source unhealthy status

 

-

Guaranteed Transfer to alternate source within –15 % of Vnominal

 

 

 

 

 

 

Load Power factor range

 

-

0.5 to unity leading or lagging

 

 

 

 

 

 

Load Crest factor

 

-

upto 3.5

 

 

 

 

 

 

In-Phase transfer window

 

-

Adjustable from 5 ± 1º

 

 

 

 

 

 

Source voltage distortion

 

%

up to 10% THD

 

 

 

 

 

 

Overload capability

 

%

125% of continuous current for 2 hrs, 1000% for two cycles minimum.

 

 

 

 

 

 

Over current Protection

 

-

By semi conductor fuse

 

 

 

 

 

 

Short circuit withstand

 

Amps

upto 20,000 symmetrical amps, protected by internal fusing.

 

capability

 

 

 

 

 

 

 

 

 

 

 

Redundant Control Power

 

-

taken from available source 1 and source 2

 

supplies

 

 

 

 

 

 

 

 

 

 

 

Integral Maintenance Bypass

 

-

Make before break operation

 

 

 

 

 

 

Alarm contacts

 

-

Eight Isolated Normally Open alarm & static switch Status contacts.

 

 

 

 

 

 

Unsynchronised transfer

 

 

6 milllisec for synchronized transfer and 16 millisec for unsynchronized

 

 

 

transfer.

 

 

 

 

 

 

 

 

 

Page4-1

Page 23
Image 23