User Manual | Chapter 3 – Installation Procedure |
Network Power Switch
4 Chapter 4 - Specifications
4.1General Specifications
•Manual and Automatic Transfers
•Sense and transfer time – less than 6 milliseconds
•
•Selectable preferred source
•Selectable auto/manual retransfer
•
•Convection cooling
•Hot swappable electronic static switching module
•Live mimic on Hot swappable unit for indicating load supply status & alarms
•Make before break manual bypass switch to transfer load from static switch to direct source 1 or source 2
4.2Electrical Specifications
| ELECTRICAL |
| UNITS | DESCRIPTION |
| CHARACTERISTICS |
| ||
|
|
|
| |
|
|
|
|
|
| Nominal Input Voltage |
| Volts | 110, 115 or 120 volts singe phase, 3W+G, 50 Hz. Solidly grounded |
|
|
|
| power sources |
| Nominal Output current |
| Amps | 25 |
|
|
|
|
|
| Frequency |
| Hz | 50 / 60 |
|
|
|
|
|
| Source unhealthy status |
| - | Guaranteed Transfer to alternate source within |
|
|
|
|
|
| Load Power factor range |
| - | 0.5 to unity leading or lagging |
|
|
|
|
|
| Load Crest factor |
| - | upto 3.5 |
|
|
|
|
|
|
| - | Adjustable from 5 ± 1º | |
|
|
|
|
|
| Source voltage distortion |
| % | up to 10% THD |
|
|
|
|
|
| Overload capability |
| % | 125% of continuous current for 2 hrs, 1000% for two cycles minimum. |
|
|
|
|
|
| Over current Protection |
| - | By semi conductor fuse |
|
|
|
|
|
| Short circuit withstand |
| Amps | upto 20,000 symmetrical amps, protected by internal fusing. |
| capability |
| ||
|
|
|
| |
|
|
|
|
|
| Redundant Control Power |
| - | taken from available source 1 and source 2 |
| supplies |
| ||
|
|
|
| |
|
|
|
|
|
| Integral Maintenance Bypass |
| - | Make before break operation |
|
|
|
|
|
| Alarm contacts |
| - | Eight Isolated Normally Open alarm & static switch Status contacts. |
|
|
|
|
|
| Unsynchronised transfer |
|
| 6 milllisec for synchronized transfer and 16 millisec for unsynchronized |
|
|
| transfer. | |
|
|
|
| |
|
|
|
|
|