Chapter 3 – Installation Procedure

Network Power Switch

3.3.3Cable connections

Following are the set of external power cables, which are connected to the Network Power Switch equipment –

Input source 1 – Line

Input source 2 – Line

Input source 1 – Neutral

Input source 2 – Neutral

Output – Line

Output – Neutral

Earthing

These cables are connected to the terminals on rear side of the equipment as shown in fig 3.2

External Cable

O/p Line

Neutral - 2

Neutral - 1

I/p Line - 2

I/p Line - 1

Common

S2 Healthy

S1 Healthy

Input Fuse 2

Input Fuse 1

Snap-on

Connector

External Cables Potential

Earthing

Free Contacts

 

Fig 3.2 – External Power Cables

3.3.4Safety earth

The safety earth busbar is provided on the rear side of equipment .The safety earth cable must be connected to this busbar.

WARNING

FAILURE TO FOLLOW ADEQUATE EARTHING PROCEDURES CAN RESULT IN ELECTRIC

SHOCK HAZARD TO PERSONNEL, OR THE RISK OF FIRE, SHOULD AN EARTH FAULT OCCUR.

3.3.5Protective devices

The input to Network Power Switch should be given through a 32 amp, 2pole ELCB for safe operation.

3.3.6Cabling Procedure

The external power cables should be connected to the terminals as shown in fig 3.2. Proper termination labels are provided near each connector for ease of cabling.