SBD TANK TYPE HEATERS
SERVICE HANDBOOK
STEP 2
HIGH LIMIT, LEFT TERMINAL TEST
Ground
24VAC
FM Transformer
STEP 2. HIGH LIMIT, LEFT TERMINAL TEST. Test for 24 VAC between the left high limit terminal and ground.
IF | THEN | |
The meter does not read 24 VAC: | • | Check wiring between transformer and |
|
| high limit. |
The meter reads 24 VAC: | • | Go to Step 3. |
Note: The high limit (Energy Cut Off) opens if the tank water temperature exceeds 205 degrees. The control is resettable (manually) when the tank water temperature drops below 185 degrees.
Technical Training Department | 20 |
Ashland City, TN ©2003 |