State Industries SBD85 500, SBD71 120 AIR for Combustion Cubic Feet of AIR PER 1,000 BTU, Minimum

Page 6

SBD TANK TYPE HEATERS

SERVICE HANDBOOK

AIR FOR COMBUSTION

10 CUBIC FEET OF AIR PER 1,000 BTU

1,000 +

BTU

10CU.

FT.

COMB.

AIR

(Minimum)

2.5CU.

FT.

EXCESS

AIR

Stoichiometric or theoretical complete combustion requires 10 cubic feet of air per 1000 BTUH input of the gas input. The National Fuel Gas Code also recommends an additional 2.5 cu.ft. of "excess" air. This 12.5 cu.ft minimum supply air per 1000 BTUH input applies to natural and propane gas models.

The National Fuel Gas Code also specifies minimum make-up air opening sizes for various building installations. (Ref: NFPA 54, ANSI Z223.1, sec 5.3)

Technical Training Department

5

Ashland City, TN ©2003

Image 6
Contents SandBlaster SBD Tank Type Heaters Service Handbook SBD Handbook Model Breakdown SBD 85 500 P E a CGA D Clearance to Combustibles Table InstallationClearances from Combustibles ModelExterior Clearance AIR for Combustion Cubic Feet of AIR PER 1,000 BTU MinimumMAKE-UP AIR Direct CommunicationSquare Inch Per 4,000 Btuh Vertical Ducts Horizontal DuctsInsufficient MAKE-UP AIR BackdraftContaminated AIR AIR for CombustionGAS Pressure Requirements Natural Gas Propane GasSBD GAS Valve Venting Atmospheric, Single, and Multiple HeatersNine Rules for Good Vents Nine Rules for Good Vents Power Vent Kits for Sidewall Venting SBD Sequence of Operation Sequence of OperationSBD Electrical Sequence SBD Electrical Sequence of Operation 115/60/12ATroubleshooting SBD Water Heaters Test the TransformerThen High LIMIT, Left Terminal Test Ground 24 VAC FM TransformerAfter Push in Reset 24 VAC is now present Reasons For Resetting Condition Cause SolutionTest High Limit Right Terminal Inspect the Damper Check the PC BoardService Switch Motor Lead PC Board Motor TestThermostat Test Adapter Service Motor Plug Switch Lead Heater Harness Effikal DamperTest for 24VAC Between Black Common and Brown Harness ChartNormal Operation Heater Harness Function Damper HarnessTest for 24VAC Between Black and Orange Test for 24VAC Between Black and YellowTroubleshooting the Effikal Damper Test Between Black Common and Brown on the Damper BoardA1 is CORRECT, Check Service Switch Position Service SwitchAdjust END Switch to CAM Contact Wire Harness Test IID Module Test Power To Module May Be Interrupted To Reset Pilot Spark TestPilot Valve OHM Test SBD 120 400 GAS ValvePilot Valve Test SBD 500 only Pilot GAS Manifold Pressure TAP Blue White REDMain Burner Test Flame Rectification Flame RectificationPilot is lit Sparking has stopped Main GAS Valve Check Main GAS Valve Coil Check Main GAS Valve Coil Check SBD 500 onlyGeneral Service Chart General Questions and Answers SBD Models 120 Thru 500A Series 110/111SBD Models 120 Thru 500A Series Series Parts Description Pilot Burner, LP 193314-3 CGA Manifold 76244 76244-2 195121-1 98185-2 Name Specifications State Part Numbers Component Part InformationSBD Service Checklist Water Piping Comments Author Terry MulderCommercial
Related manuals
Manual 56 pages 24.82 Kb