White Rodgers 50A55-843 Timing Specifications, Electrical Ratings @ 77F 25C, Humidity Range

Page 2

SPECIFICATIONS

ELECTRICAL RATINGS [@ 77°F (25°C)]:

Input Voltage: 25 VAC 50/60 Hz

Max. Input Current @ 25 VAC: 0.45 amp

Relay Load Ratings:

Valve Relay: 1.5 amp @ 25 VAC 50/60 Hz 0.6 pf

Ignitor Relay: 6.0 amp @ 120 VAC 50/60 Hz (resistive)

Inducer Relay: 2.2 FLA–3.5 LRA @ 120 VAC

Circulator Relay: 14.5 FLA–25.0 LRA @ 120 VAC

Flame Current Requirements:

Minimum current to insure flame detection: 1 µa DC*

Maximum current for non-detection: 0.1 µa DC*

Maximum allowable leakage resistance: 100 M ohms

*Measured with a DC microammeter in the flame probe lead

OPERATING TEMPERATURE RANGE: -40° to 175°F (-40° to 80°C)

HUMIDITY RANGE:

5% to 93% relative humidity (non-condensing)

MOUNTING:

Surface mount multipoise

 

Timing Specs: (@ 60 Hz**)

 

 

maximum

Flame Establishing Time:

0.8 sec

Flame Failure Response Time:

2.0 sec

**At 50 Hz, all timing specifications should be increased by 20%

Gases Approved: Natural, Manufactured, Mixed, Liquified Petroleum, and LP Gas Air Mixtures are all approved for use.

TIMING SPECIFICATIONS

(All times are in seconds, unless noted otherwise)

 

50A55-843

 

 

PRE-PURGE

30

 

 

INITIAL IGNITOR WARM-UP

17

(1st 64 attempts)

 

 

 

MINIMUM IGNITOR WARM-

5

UP

 

 

 

MAXIMUM IGNITOR WARM-

21

UP

 

 

 

IGNITION ACTIVATION

1

PERIOD

 

 

 

TRIAL FOR IGNITION

4

PERIOD

 

 

 

RETRIES

2 times

 

 

VALVE SEQUENCE PERIOD

12

 

 

INTERPURGE

60

 

 

POST-PURGE

15

 

 

LOCKOUT TIME

300

 

 

HEAT DELAY-TO-FAN-ON*

30, 45

 

 

HEAT DELAY-TO-FAN-OFF*

60/90/

120/180

 

 

 

COOL DELAY-TO-FAN-ON

5

 

 

COOL DELAY-TO-FAN-OFF*

45, 90

 

 

AUTO RESET

60 minutes

 

 

HUMIDIFIER

YES

 

 

ELECTRONIC AIR CLEANER

YES

 

 

*These times will vary depending on option switch position. The control is factory-set at 30 seconds heat delay- to-fan-on, 180 seconds heat delay-to- fan-off and 45 seconds cool delay-to- fan-off. See OPERATION section for further information.

2

Image 2
Contents Contents Installation InstructionsPrecautions DescriptionElectrical Ratings @ 77F 25C SpecificationsTiming Specifications Humidity RangeInstallation Mounting and WiringTypical System Wiring Diagram Twinning Applications Only Flame Sensor ProbeTypical System Wiring Table ConnectionCool Mode Operation Option SwitchesHeat Mode Manual FAN on ModeSystem Lockout Features System Lockout Diagnostic FeaturesDiagnostic Features Twinning InterfaceMounting Hole Template For Mounting Hole Locations