TWINNING INTERFACE | DIAGNOSTIC FEATURES |
If the control has six screw terminals, one of which is designated TWIN, the control is equipped with a single wire twinning interface. If twinning is used, either control will process a call for heat, cool or fan as described above. However, after the
acommon transformer ground (TR). To enable twinning, do the following.
1.Power supplied to both furnaces must be from the same phase of the incoming 120 VAC power.
2.Connect the TWIN screw terminals on the
SYSTEM LOCKOUT AND
DIAGNOSTIC FEATURES
SYSTEM LOCKOUT FEATURES
When system lockout occurs, the gas valve is
(System lockout will never override the precautionary fea- tures.)
To reset the control after system lockout, do one of the following:
1.Interrupt the call for heat or cool at the thermostat for at least one second but less than 20 seconds (if flame is sensed with the gas valve
2.Interrupt the 24 VAC power at the control for at least one second. You may also need to reset the flame rollout sensor switch.
3.After one hour in lockout, the control will automatically reset itself.
The
If the sensed failure is in the system (external to the control), the LED will flash in the following
1 flash, then pause | System lockout |
2 flashes, then pause | Pressure switch stuck closed |
3 flashes, then pause | Pressure switch stuck open |
4 flashes, then pause | Open limit switch |
5 flashes, then pause | Open rollout switch |
6 flashes, then pause | 115 Volt AC power reversed/Im- |
| proper ground |
7 flashes, then pause | Low flame sense signal |
Continuous flashing | Flame has been sensed when |
(no pause) | no flame should be present (no |
| call for heat) |
The LED will also flash once at