Connect Sensors
Only connect sensors supported by the appliance to which the NetBotz 155 is connected. See the installation and quick configuration manual included with your appliance.
Connect APC and third-party sensors to the four ports labeled Sensors on the NetBotz 155.
•Third-party dry contact sensors require the NetBotz Dry Contact Cable (NBES0304). To connect a sensor to the cable, follow the instructions provided with the sensor and the instructions provided with the cable.
•Standard third-party 0-5 V sensors require the NetBotz 0-5 V Sensor Cable (NBES0305). To connect a sensor to the cable, follow the instructions provided with the sensor and the instructions provided with the cable.
•If a sensor cable is not long enough, use an RJ-45 coupling (provided with some sensors) and standard CAT-5 cabling to extend the cable up to 15 m (50 ft) for a Temperature/Humidity Sensor (AP9335TH) or a Temperature Sensor (AP9335T) and up to 30.5 m (100 ft) for all other supported sensors.
Configure and Monitor Sensors
Once your system is installed and receiving power, configure sensors and begin monitoring your system using the software interface for the appliance.
See your appliance installation and quick configuration manual for system installation details and for instructions on accessing the software interface of the appliance.
12 | NetBotz Room Sensor Pod 155 Installation Manual |