Omega CN3440 manual Logic Input Connections Figs .20, Programming Guide

Page 17

4 ELECTRICAL INSTALLATION…

4.10Logic Input Connections – Figs. 4.20 and 4.21

Each logic input can be programmed to perform one of a number of functions – see Section

3.10of the Programming Guide.

 

 

 

 

 

 

 

 

 

 

 

 

 

Auto/

Local/Remote

Dual Set Point

Alarm

 

 

 

 

 

 

 

 

 

 

 

 

 

Manual

 

Set Point

 

Selection

Acknowledgement

 

 

 

 

 

 

 

 

 

 

 

 

 

Selection

 

Selection

 

 

 

 

 

* Alarm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fixed Dual

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Acknowledge

 

 

 

 

 

 

 

 

 

 

 

 

 

Automatic

 

 

 

Local

 

Set Point 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Logic switching

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Manual

 

 

Remote

 

Fixed Dual

* Leading 'edge-triggered'

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

or Dual

 

Set Point 1

(minimum duration 200ms)

30

31

32

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Automatic

Local

Fixed Dual Set Point 2

 

 

 

 

Manual

Remote (Dual) Fixed Dual Set Point 1

Alarm Ack.

30

Logic Input 1

Note. Only one function may be

performed by each input at any one time.

31

Logic Input 2

 

32Common

Fig. 4.20 Standard Logic Input Functions

 

 

 

 

Hold

* Profile

* Skip

 

 

 

 

(Soak)

Reset

Segment

 

 

5V

 

 

 

 

 

Logic switching

 

 

 

 

0V

 

* Leading 'edge-triggered'

 

 

 

 

Start

 

 

 

 

Profile

(minimum duration 200ms)

 

30

31

32

 

 

 

 

 

 

 

P–Strt

P–rSEt

P–SKIP

 

 

 

 

Hold/ (Soak)

 

 

 

 

 

Start Profile

Profile Reset Skip Current Segment

30

Logic Input 1

Note. Only one function may be

31

Logic Input 2

performed by each input at any one time.

 

 

 

 

32Common

Fig. 4.21 Additional Logic Input Functions for Profile Selection

15

Image 17
Contents CN3440 Series WARRANTY/DISCLAIMER Contents Operation Programming Modbus RTU IntroductionChecking the Code Number Fig PreparationNEMA4X Mechanical InstallationEC Directive 89/336/EEC Siting Figs .1Mounting Figs .3 Overall DimensionsAccess to Terminals Fig Electrical InstallationSetting Input Selector Links .2A Setting Isolated Output Link .2BTHC & RTD Ring Thomas & Betts CableGlands N. American 0.5in FigTerminal Block Identification Connections Summary FigTerminal Number AC Supply Thermocouple THC Inputs Fig Input Connections2 3-lead Resistance Thermometer RTD Inputs Fig 3 2-lead Resistance Thermometer RTD Inputs Fig+ Tx Motorized Valve Connections Figs .18 Output ConnectionsRelay Connections Fig Programming Guide Logic Input Connections Figs .2022 Power Supply Selection and AC Connections Power Supply Selection and AC Connections FigPower Supply Connection/Terminal Number Page …NOTES Omega.com Temperature