Operating Instructions for Master-Bilt Alarm/Light Module (19-14009)

1598003200

 

 

 

14.

PARAMETER LIST

 

 

 

Ot

Thermostat probe calibration: (-12.012.0°C/ -2121°F) allows to adjust possible offset of the

 

 

thermostat probe.

 

 

 

CF

T measurement unit: °C = Celsius; °F = Fahrenheit. When the measurement unit is changed the

 

 

Set Point and the values of some parameters have to be modified.

rES

Resolution (for °C): (in = 1°C; dE = 0.1 °C) allows decimal point display.

Ut

Display update: The time delay of the T readout (0÷255s)

onF

Off function enabling: n = off function disabled; y = off function enabled;

ALU

High T° alarm setting: (ALL 150°C or 302°F);

 

 

when this T° is reached and after the ALd delay time the HA alarm is enabled.

ALL

Low T° alarm setting:

(- 50°C or -58°F ALU)

 

 

when this T° is reached and after the ALd delay time, the LA alarm is enabled,.

AFH

T° alarm differential: (0,1÷25,5°C; 1÷45°F) differential for T° alarm Set Point and fan regulation Set

 

 

Point, always a positive value

ALd

T° alarm delay: (0÷255 min) time interval between the detection of an alarm condition and the

 

 

corresponding alarm signaling.

dAO

Delay of T° alarm at start-up: (0min÷23h 50min) time interval between the detection of the T°

 

 

alarm condition after the instrument power on and the alarm signaling.

EdA

Alarm delay at the end of defrost: (0255 min) Time interval between the detection of the T° alarm

 

 

condition at the end of defrost and the alarm signaling.

dot

Delay of T° alarm after closing the door: (0255 min) Time delay to signal the T° alarm

 

 

condition after closing the door.

LHt

Light timer: (0-255 min) The time the light will stay on after pressing the light switch on the

 

 

keyboard.

 

 

 

doA

Open door alarm delay:(0÷255 min) delay between the detection of the open door condition and its

 

 

alarm signaling: the flashing message “dA” is displayed.

oA1

First relay configuration: (14-15): ALr = alarm; LHt = light; onF = on/off relay

oA2

Second relay configuration: (14-16): ALr = alarm; LHt = light; onF = on/off relay

AOP

Alarm relay polarity: cL = closing contacts; oP = opening contacts.

i1P

Digital input 1 polarity (1-2): CL : the digital input is activated by closing the contact;

OP

the digital input is activated by opening the contact

i1L

Door switch to turn light ON(1-2):(y / no) To turn the light ON automatically when the door is

 

 

open. The light will turn off based on LHt . Keyboard switch must be turned ON first.

i1F

Digital input 1 operating mode(1-2): EAL = external alarm; dor = door switch; dFr = A defrost is

 

 

running; LHt = keep light ON (signal from occupancy sensor) override LHt.;

i2P

Digital input 2 polarity (1-3): CL : the digital input is activated by closing the contact;

OP

the digital input is activated by opening the contact

i2F

Digital input 2 operating mode: configure the digital input function:

EAL

= External alarm;

 

 

 

PAn

=Panic alarm;

 

 

 

dFr = A defrost is running;

 

 

 

LHt = Keep light ON (signal from occupancy sensor) override LHt.

did

Time interval/delay for digital input alarm:(0255 min.) If I2F=EAL or PAn (external alarms), “did”

 

 

parameter defines the time delay between the detection and the successive signaling of the alarm.

tbA

Alarm relay & Buzzer disabling: (y ; no)

Pbc

Type of probe (PTC, NTC)

dP1

Probe 1 T

 

 

 

rEL

Software release for internal use.

Ptb

Parameter table code: read only.

 

 

 

 

 

 

 

15.

PARTS LIST

 

 

 

 

 

 

 

 

 

 

 

 

 

M/B Part Number

 

Description

 

 

 

 

19-14009

 

WI therm, alarm, panic light, contl. #XWA11V-4N1F0

 

 

 

 

19-14012

 

PROBE, 18NB-NTC-1.5M, (5')

 

 

 

 

19-14013

 

PROBE, 18NB-NTC-1.5M, (50')

 

 

 

 

19-14014

 

PROBE, 18NB-NTC-1.5M, (75')

 

For more information, please contact our Technical Service Dept.

@ 1-800-684-8988

7

Image 7
Contents General Description Please Read Before Using this ManualSafety Precautions General WarningsAlarms Setting Light Management ProgrammingUSE of the Programming HOT KEY Installation and Mounting 7.1 Mounting of XWA11V PR10000Alarm Signals Electrical ConnectionsConnections Alarm RecoveryTechnical Data Silencing BuzzerParameter MAP Parameter List Parts ListEAL

19-14009 specifications

The Master Bilt 19-14009 is a versatile and efficient commercial refrigeration unit designed to meet the demands of various business environments, including restaurants, convenience stores, and catering operations. As a well-regarded model in the Master Bilt lineup, it stands out for its robust build quality, impressive cooling performance, and user-friendly features.

One of the primary characteristics of the Master Bilt 19-14009 is its spacious interior, which offers ample storage capacity for a wide range of food items. With adjustable shelving, users can easily configure the interior space to accommodate different products, making it suitable for everything from beverages to perishable goods. This flexibility enhances operational efficiency and allows businesses to optimize their inventory space.

The refrigeration system is another highlight of the Master Bilt 19-14009. It is equipped with a powerful compressor that ensures rapid cooling and consistent temperature control, vital for preserving the freshness of products. The unit often features a digital thermostat, allowing for precise temperature adjustments and easy monitoring. This technology ensures that food items are stored at optimal temperatures, reducing the risk of spoilage and waste.

Energy efficiency is a key consideration in the design of the Master Bilt 19-14009. This model typically includes improved insulation and an environmentally friendly refrigerant, which not only helps in reducing energy consumption but also supports sustainability efforts in the foodservice industry. Businesses benefit from lower operational costs while contributing to a greener environment.

In terms of durability, the Master Bilt 19-14009 is built to withstand the rigors of daily use in a commercial setting. The exterior is often crafted from high-quality stainless steel, providing resistance to corrosion and easy cleaning. This robust construction enhances the longevity of the unit, ensuring that it remains a reliable asset for years to come.

The Master Bilt 19-14009 also emphasizes user convenience with features such as easy-access doors, bright interior lighting, and an intuitive control panel. These elements collectively enhance the overall user experience, making it simple for staff to organize and retrieve items efficiently.

In summary, the Master Bilt 19-14009 is a dependable refrigeration solution that combines practicality, durability, and energy efficiency. With its ample storage space, advanced cooling technology, and user-friendly design, it is an excellent choice for businesses looking to maintain the integrity of their perishable goods while ensuring operational efficiency.