New Buck Corporation 42ZCBB dimensions Ventilation Air From Inside Building

Page 17
VENTILATION AIR

VENTILATION AIR

VENTILATION AIR FROM INSIDE BUILDING

This fresh air would come from an adjoining unconfined space. When venting to an adjoining space, you must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see Options 1 and 2, Figure 6). You can also remove door into adjoining room (see Option 3, Figure 6).

NOTE: Each opening shall have a minimum free area of 1 square inch per 1000 BTU’s per hour of the total input ratings of all gas utilization equipment in the confined space, but not less than 100 square inches.

Figure 6

Ventilation Air From Inside Building

15

Image 17
Contents UNIVERSAL BOX Page TABLE OF CONTENTS Page SAFETY INFORMATION WARNINGS TOP FRONT PANELS 42 ZCBB FRONTCANOPY SCREEN DOORSCHOOSING THE LOCATION FOR YOUR FIREBOX INSTALLATION20181/2-15/16 GAS LINE38361/8-5/8 35-5/8 8 1/16FIREBOX CLEARANCES INSTALLING THE FIREBOXCLEARANCES FINISHING YOUR FIREBOXMANTEL PROFILES FOR VENTLESS FIREBOX ENCLOSURE CLEARANCES INSTALLATION INSTRUCTIONSTOP VIEW 42ZCBBCLEARANCES ASSEMBLY INSTRUCTIONSREAR VIEW DETERMINING FRESH-AIRFLOW FOR HEATER LOCATION PRODUCING ADEQUATE VENTILATIONPage VENTILATION AIR FROM INSIDE BUILDING VENTILATION AIRVENTILATION AIR FROM OUTDOORS THERMOSTAT OPTIONAL BLOWER INSTALLATIONTHERMOSTAT WIRES BLACK WHITE WIRING DIAGRAM MA ZCBB714R E V . D A T E D IS C R IP T IO NOPTIONAL PARTS REPLACEMENT PARTS