Therma-Stor Products Group Rx Free-Standing Dehumidification owner manual Refrigerant Charging

Page 5

FOR HVAC INSTALLER ONLY

3.Defective compressor overload (Sec. 5.6A).

4.Defective compressor (Sec. 5.6).

5.Defrost thermostat open (Sec. 5.8).

6.Defective relay (Sec. 5.10).

7.Pump Safety switch open (Sec. 5.9)

Blower runs with AUTO FAN, but compressor cycles on & off.

1.Low ambient temperature and/or humidity causing unit to cycle through defrost mode.

2.Defective compressor overload (Sec. 5.6A).

3.Defective compressor (Sec. 5.6).

4.Defrost thermostat defective (Sec. 5.8).

Blower does not run with fan switch in either position. Compressor runs briefly but cycles on & off.

1.Loose connection in blower circuit (see Fig. 2).

2.Obstruction prevents impeller rotation.

3.Defective blower (Sec. 5.5).

4.Blower switch defective.

Evaporator coil frosted continuously, low dehumidifying capacity.

1.Defrost thermostat loose or defective (Sec. 5.8).

2.Low refrigerant charge.

3.Dirty air filter or air flow restricted (Sec. 4.1B).

5.4 Refrigerant Charging

If the refrigerant charge is lost due to service or a leak, a new charge must be accurately weighed in. If any of the old charge is left in the system, it must be removed before weighing in the new charge. Follow EPA recovery regulations. Refer to the unit nameplate for the correct charge weight and refrigerant type.

5.5 Blower Replacement

The centrifugal blower has a PSC motor and internal thermal overload protection. If defective, the complete assembly must be replaced.

1. Unplug the power cord.

2.Remove the unit top.

3.If optional HEPA, 95% efficient or carbon filters are attached to the unit back, the filter(s) and their frame must be removed.

4.Remove the back cover (4 screws).

5.Remove the cabinet (6 screws).

6.Disconnect the blower leads: black from the black wire at wire nut, and white from the run capacitor.

7.Remove the foam pieces at the blower outlet at the bottom back to access the blower screws.

8.Remove the 4 screws holding the blower outlet flange and remove the blower.

9.Reassembling with the new blower is the above procedure reversed.

5.6 Compressor/Capacitor Replacement

Caution-electric shock hazard: Electrical power must be present to perform some tests; these test should be performed by a qualified service person.

This compressor run capacitor is accessed by following steps 1 through 4 in section 5.5 on blower replacement; the compressor is accessed by following steps 1 through 5. This compressor is equipped with a two terminal external overload, run capacitor, but no start capacitor or relay (see Fig. 2).

Perform the following tests if the blower runs but the compressor does not with the AUTO FAN and the humidity control ON.

1.Unplug the unit, follow steps 1 through 5 of section 5.5 to access the compressor. Remove the electrical connection cover on the compressor top.

2.Plug in the unit and turn the humidity control to ON. If the compressor tries to start but cycles on the over load, go to step 4. If the compressor remains silent, check for 110 volts from compressor terminal R to overload terminal 3 using an AC voltmeter. If voltage is resent, go to step 3. If there is no voltage, either the pump safety switch, defrost thermostat, low pressure control, or relay are open or there is a loose connection in the continuity; see the appropriate section if a defect is suspected.

3.Check continuity between overload terminals 1 and 3: if there is none, the overload may be tripped. Wait 10 minutes and try again. If there is still no continuity, it is defective and must be replaced.

4.Unplug the unit, then replace the run capacitor with one of the same microfarad rating and equal or greater voltage rating. If such a capacitor is unavailable, a hard start kit sized for this compressor may be used. If the compressor does not start and run correctly, the compressor is defective and must be replaced.

5

Santa Fe Rx Installer’s & Owner’s Manual

Image 5
Contents Hvac Installer Please Leave Manual for Homeowner Table of Contents Operation Safety PrecautionsMaintenance Service For Hvac Installer onlyRefrigerant Charging Blower ReplacementCompressor/Capacitor Replacement 6B Replacing a Compressor-Nonburn Out 6A Replacing a Burned out CompressorHumidity Control Defrost ThermostatSanta FE Rx Wiring Diagram QTY Description Santa FE Rx Filter Frame Assembly How to prepare the Santa Fe Rx for operation Santa FE Rx SET UP InstructionsSanta FE Rx Laminate TOP KIT Santa Fe Rx Dehumidifier Limited Warranty PO Box 8680 Madison, WI Phone 608-222-5301 Fax

Rx Free-Standing Dehumidification specifications

Therma-Stor Products Group has emerged as a leader in providing innovative solutions for moisture control, and one of their standout offerings is the Rx Free-Standing Dehumidification unit. This product is engineered to meet the needs of various environments, including residential and commercial spaces that require efficient humidity management.

A primary feature of the Rx Free-Standing Dehumidifier is its impressive moisture removal capacity. With an ability to extract up to 70 pints of moisture per day, it is well-suited for areas prone to high humidity levels, such as basements, laundry rooms, and bathrooms. This high capacity ensures that spaces remain dry, preventing the growth of mold and mildew, which can cause health issues and property damage.

Incorporating advanced technologies, the Rx model is equipped with a state-of-the-art digital humidistat. This feature allows users to set their desired humidity levels, ensuring the unit operates only when necessary. The digital display offers real-time humidity readings, making it easy to monitor environmental conditions and adjust settings accordingly. Additionally, the automatic restart function is a valuable benefit during power interruptions. The unit can resume operation under the previous settings, protecting your space from potential moisture buildup after outages.

The Rx Free-Standing Dehumidifier also emphasizes user-friendliness. It features a continuous drainage option, which eliminates the need for frequent manual emptying of the water tank. This continuous drainage can be connected to a standard hose, making it ideal for long-term, unattended use. The unit is designed for portability, with robust casters that allow for easy movement between rooms, accommodating the dynamic needs of homeowners and businesses alike.

Furthermore, the quiet operation of the Rx model ensures that it can perform effectively without disrupting daily activities. Its energy-efficient design means lower energy costs while still delivering optimal performance. The unit is also built with durable materials that ensure longevity, making it a reliable investment for long-term humidity control.

In summary, Therma-Stor's Rx Free-Standing Dehumidification unit combines high performance with user-friendly features, advanced technology, and energy efficiency. This makes it an excellent choice for anyone seeking to maintain a healthy and comfortable living or working environment.