Samson 5476 manual Optimization

Page 46

Functions of the heating circuit

have been activated.

Refer to page 78 onwards for the wiring diagrams of the room panels.

Functions

WE

Configuration

Room sensor RF

OFF

FB13 = ON

Potentiometer input 1 to 2 kΩ

OFF

FB24 = OFF

5.7Optimization

This function requires the use of a room sensor. Depending on the building characteristics, the controller determines and adapts the required preheating time (maximum 6 hours) to ensure that the desired Room set point (rated room temperature) has been reached in the reference room when the time-of-use starts. During the preheating period, the controller heats with the max. flow temperature. This temperature is built up in steps of 10 °C. As soon as the Room set point has been reached, weather-compensated control is activated.

Depending on the room sensor, the controller switches off the heating system up to two hours before the time-of-use ends. The controller chooses the deactivation time such that the room temperature does not drop significantly below the desired value until the time-of-use ends. It two times-of-use are programmed for one day, the controller monitors the Reduced room set point in the time between these times-of-use. Outside the times-of-use, the controller monitors the Sus- tained temperature. Should the temperature fall below the Sustained temperature, the controller heats with the max. flow temperature until the measured room temperature exceeds the ad- justed value by 1 °C.

During the preheating period, DHW heating does not take place in systems with DHW circuits linked in the secondary side.

Note!

Direct sunshine can cause the room temperature to increase and thus result in the premature de- activation of the heating system.

Function

WE

Configuration

Optimization

OFF

FB0 = ON

 

 

 

Parameter

WE

Range of values

Room set point

20 °C

0 to 40 °C

Reduced room set point

17 °C

0 to 40 °C

Sustained temperature

15 °C

0 to 40 °C

46EB 5476 EN

Image 46
Contents Mounting and Operating Instructions EB 5476 EN Disclaimer of liability Contents Contents Contents Operating elements OperationOperating keys Operating switches Operating modes Display ClosedDisplaying data Setting the controller time Setting the times-of-use Heating circuitStart Entering public holidays Entering vacation periods Correcting temperature set points Start-up Setting the system code number Activating and deactivating functionsDisplay shows Current system code number Blink Changing parameters Enter key numberCalibrating sensors Resetting to default values Manual operation Systems DHWSystem Anl Default settings FB13 = OFF Without RF FB20 = on 26 EB 5476 EN FB15 = ON, select CF FB15 = ON, select Solar FB21 = OFF Solar collector 32 EB 5476 EN FB15 = ON, select CF 34 EB 5476 EN Default settings FB13 = OFF Without RF FB20 = on FB15 = on Systems 38 EB 5476 EN FB15 = on Functions of the heating circuit Weather-compensated controlGradient characteristic 2 4-point characteristic · 4-point characteristicFixed set point control Underfloor heatingSummer mode OT deactivation value in reduced operationDelayed outdoor temperature adaptation Remote operationOptimization Flash adaptation AdaptationPump management Potentiometer input· DHW heating in a storage tank system Functions of the DHW circuit DHW heating in the storage tank charging system · DHW heating in a storage tank charging system52 EB 5476 EN DHW heating with solar system Anl 2, 3, 4, 5 und DHW heating in instantaneous heating system AnlIntermediate heating operation Anl 2, 3 Circulation pump operation during storage tank chargingCirculation over the heat exchanger Parallel pump operation Anl 2, 3Reverse control Priority circuit Anl 4, 5, 6, 7, 8Set-back operation Forced charging of the DHW storage tank Anl 2, 3, 5, 7, 8 Thermal disinfection of the DHW storage tankFrost protection Return flow temperature limitationForced operation of the pumps FB21 = on Condensate accumulation control Three-step controlReleasing a control circuit over the binary input On/off controlProcessing of external demand in RK1 Limitation using pulse input Flow rate/capacity limitationLimitation using 0/4 to 20 mA signal Locking manual levelsSetting a customized key number Collective error alarm Operational faultsSensor failure Temperature monitoring Error status registerCommunication CommunicationController with RS-232-C port Controller with serial RS-485 interface · Pin assignment of RS-232 port left and RS-485 port rightDescription of communication parameters to be adjusted Meter bus interface Modem time-out t0Activating the meter bus Flow rate and/or capacity limitation via meter busInstallation Appendix Installation Memory modulePanel mounting Electrical connection TWF Systems Anl 1 to Systems Anl 5 to 80 EB 5476 EN Appendix Function block list Parallel pump Setting only possible after entering key number UP1 Circulation over BA8 12.2 Parameter list 88 EB 5476 EN Maximum flow temperature Can only be set after entering the key number Min. return flow temperature System Anl 9, underfloor heating circuit Min. flow temperature 20 to 130 C 20 C DHW heating DHW heating OFF 20 to 90 C 50 C 20 to 130 C 120 C ST.-NR Sensor resistance tables Technical data Customer data Model code WMZ 2 FB29 = on Parameter settings Appendix Public holidays and vacations SLP Key number 1732 Appendix Index PTC Thermal disinfection EB 5476 EN 0000 Page EB 5476 EN

5476 specifications

The Samson 5476 is a high-performance microphone designed for professional audio applications, offering exceptional quality and versatility for various recording environments. Known for its robust build and advanced features, the 5476 is a reliable choice for musicians, broadcasters, and sound engineers.

One of the standout characteristics of the Samson 5476 is its cardioid polar pattern, which effectively isolates the sound source while minimizing background noise. This feature is especially beneficial in live performance settings or during studio recordings where external noise can be a challenge. The microphone’s frequency response ranges from 20 Hz to 20 kHz, making it suitable for capturing a wide variety of sound sources, from deep bass notes to crisp high frequencies.

The 5476 incorporates a dynamic transducer that enhances its durability and reliability, ensuring it can withstand the rigors of frequent use. The built-in shock mount system further reduces handling noise and vibrations, allowing for clearer audio capture. Additionally, the microphone is equipped with a built-in pop filter, which mitigates plosive sounds that can occur during vocal recordings.

This microphone also features a low impedance output, ensuring compatibility with a wide range of mixing consoles and recording interfaces. Users can easily connect the 5476 to XLR inputs, making it straightforward to integrate into any professional audio setup. The microphone’s high output level ensures excellent signal integrity, providing clean and precise audio reproduction.

Another notable technology in the Samson 5476 is its advanced capsule design, which helps to enhance the microphone's sensitivity and transient response. This results in natural-sounding audio, whether it’s used for vocals, instruments, or ambient sounds. The microphone’s construction also includes a durable metal body that can withstand the wear and tear of live performances and frequent handling.

In summary, the Samson 5476 is a versatile and reliable microphone that combines advanced technology with practical features suited for both studio and live environments. Its cardioid pattern, dynamic transducer, low impedance output, and robust build make it a valuable tool for any audio professional looking to achieve high-quality recordings. Whether for vocals, instruments, or broadcasting, the Samson 5476 delivers consistent performance and exceptional sound quality, making it a top choice in its class.