White Rodgers T7351F, T7350 manual IPRO Applications, Remote Sensing, Unit Vent, Commercial Codes

Page 15

iPROApplications

Remote Sensing

Can be configured using Honeywell’s line of 10K ohm and 20K ohm commercial sensors, supporting the following applications that residential thermostats don’t:

Temperature Averaging Networks

Because commercial thermostats can be configured to a 20K ohm network, temperature average networks of anywhere from 1 to 9+ sensors can be deployed.

Combinations of 10K ohm and 20K ohm sensors are use to create the averaging network. The most popular sensors are the TR21 and TR21-A (averaging) 10K sensor and the TR21 and TR21-A 20K sensor.

SubbaSe

TR21

TR21-A

TR21

THE TR21-A IS A 10K OHM SENSOR

Room Temperature Control

Performed via a sensing network using the following sensors:

Wall Sensors: TR21-A (10K) for averaging only, TR21 (20K), C7189U1005 (10K)

Flush Mount Sensors: C7772A1012 (20K)

Button Sensors: C7041P (20K)

Duct Return Temperature Control Performed using the following 20K sensors:

C7041B/C7041C/C7770A/C7041J

Unit Vent

Can be programmed to control ASHRAE Cycle 1 unit vent applications.

Unit vent outside-air damper can be programmed through the Economizer feature. When the unit vent is on and occupied, the thermostat will enable the economizer relay to keep the outside air damper at the maximum percentage opening. Only maximum percentage opening is available; the thermostat will not modulate the damper. When the unit vent is unoccupied, the thermostat will close the damper.

Range Stop feature can be configured to program a low limit setpoint to prevent equipment damage from freezing.

Commercial Codes

Comply with commercial building codes and meet the most rigorous standard, California’s Title 24.

No hold button is available, so the thermostat remains in permanent schedule.

Override button allows the tenant to override an unoccupied mode for up to 4 hours and can be configured for an exact override setpoint. Depending on the partial lockout level deployed, a user may override to an exact setpoint or be given a setpoint range to choose from.

Pre-Occupancy Purge and Economizer functions allow the building owner to meet all HVAC ventilation codes for commercial buildings.

Lighting Load Reduction (TOD)

Commercial buildings are frequently automated to turn off lighting loads. Lighting loads can use even more energy than HVAC systems in commercial buildings, and 79% of commercial buildings have off-hours lighting load reduction control. By using the time-of-day relay (TOD) in conjunction with a lighting control system, users can automate their lighting loads. (Not available on MultiPRO)

15

Image 15
Contents Application Selection and Cross-Reference Guide Innovative Leader WebStat Controller Web Accessible ThermostatsFeatures WebStat Features and Benefits SummaryCompatible With These Honeywell Systems Replacements SensorT7350H Communicating ThermostatDescription Application Outdoor Air and Discharge Air Temperature LockoutT7350M Modulating and Staged ThermostatT7350A, B, D Standalone Staged ThermostatConventional/Heat Pump T7351F2010 T7351FT7350/T7351F Applications Modulating Control Discharge Air Control Office Building ZonesHeat Pumps Equipment ProtectionCommercial VisionPRO Programmable Touchscreen ThermostatTB8220U1003 CommercialPRO ThermostatCommercialPRO MultiPRO Multispeed and Multipurpose ThermostatMultiPRO Program Details Private Label ProgramSchools Individual Zone Control Restaurant/Food Service ControlAfter-Hours Control in Office Buildings Condominiums/HotelsCommercial Codes IPRO ApplicationsRemote Sensing Unit VentHumidity Sensors AccessoriesRemote Room Temperature and Discharge Air Sensors Infrared Thermostat Interface Module IR/TIMCompatible Sensors Commercial Modulating Zoning Thermostat ZonePROHydronic Control Modulating Heating ZonePRO ApplicationsModel Schedule Options User Application Interface Honeywell Thermostat Cross-Reference ChartPower Method Line Volt SuitePRO Digital Fan CoilElectromechanical Fan Coil Other ThermostatsPage Learn More