TROUBLESHOOTING
Continued
WARNING: If you smell gas
•Shut off gas supply.
•Do not try to light any appliance.
•Do not touch any electrical switch; do not use any phone in your building.
•Immediately call your gas supplier from a neighbor’s phone. Fol- low the gas supplier’s instructions.
•If you cannot reach your gas supplier, call the fire department.
OBSERVED PROBLEM | POSSIBLE CAUSE | REMEDY | |||
|
|
|
|
|
|
Fireplace produces a clicking/ | 1. | Metal expanding while heat- | 1. | This is common with most fireplac- | |
ticking noise just after burner |
| ing or contracting while |
| es. If noise is excessive, contact | |
is lit or shut off |
| cooling |
| qualified service person | |
|
|
|
|
|
|
Slight smoke or odor during | 1. | Residues from manufacturing | 1. | Problem will stop after a few hours | |
initial operation |
| processes and logs curing |
| of operation |
|
Gas odor even when control | 1. | Gas leak. See Warning | 1. | Locate and correct all leaks (see | |
knob is in OFF position |
| statement at top of |
| Checking Gas Connections, page | |
| 2. | page | 2. | 23) |
|
| Control valve defective | Replace control valve | |||
|
|
|
|
|
|
Gas odor during combustion | 1. | Foreign matter between | 1. | Take apart gas tubing and remove | |
| 2. | control valve and burner | 2. | foreign matter | |
| Gas leak. See Warning | Locate and correct all leaks (see | |||
|
| statement at top of |
| Checking Gas Connections, | |
|
| page |
| page 23) | |
|
|
|
|
|
|
Glass soots | 1. | Debris around burner air | 1. | Inspect the opening at the base of | |
|
| mixer |
| the burner to see that it is NOT | |
| 2. | Improper vent configuration. | 2. | packed with any type of material | |
| Check vent configuration speci- | ||||
|
|
|
| fication (see Venting Installation | |
|
|
|
| Instructions, page 9) |
|
Dark residue on logs or inside | 1. | Air holes at burner inlet | 1. | Clean out air holes at burner inlets. | |
of fireplace | 2. | blocked | 2. | Periodically repeat as needed | |
| Burner flame holes blocked | Remove blockage | |||
| 3. | Improper venting or exces- | 3. | Have the vent system inspected, | |
|
| sive blockage |
| including the termination cap. | |
|
|
|
| Remove any restrictions or ob- | |
| 4. |
|
| struction | |
| Excessive amounts of em- 4. Clear excess embers until a mini- | ||||
|
| bers and pan material |
| mum gap of 1/2" remains under the | |
|
|
|
| grate |
www.desatech.com | 33 |