Desa (V)T36ENA installation manual Connecting Fireplace to GAS Supply, Checking GAS Connections

Page 20

20

FIREPLACE INSTALLATION

Connecting Fireplace To Gas Supply

 

Checking Gas Connections

 

 

FIREPLACE INSTALLATION

Continued

CONNECTING FIREPLACE TO GAS SUPPLY

Installation Items Needed

5/16" hex socket wrench or nut-driver

sealant (resistant to propane/LP gas, not provided)

1.Open lower louver door panel by gently pulling forward.

2.Route flexible gas line (provided by installer) from equipment shutoff valve to fireplace. Route flexible gas supply line through one of the access holes on side of fireplace.

3.Attach flexible gas line from gas supply to control valve (see Figure 32).

4.Check all gas connections for leaks. See Checking Gas Connections.

 

Red Surface Indicates

Equipment

For Propane/LP Use Only

Flexible Gas Line

Shutoff Valve

Do NOT Kink

1/2" NPT Incoming

 

 

Gas Line

Inlet Pressure Tap

Outlet Pressure Tap

 

Note: Wire Connections Not Shown for Clarity

Figure 32 - Connecting Flexible Gas Line to Electronic Valve

CHECKING GAS CONNECTIONS

WARNING: Test all gas piping and connections, internal and external to unit, for leaks after installing or servicing. Correct all leaks at once.

WARNING: Never use an open flame to check for a leak. Apply a noncorrosive leak detection fluid to all joints. Bubbles forming show a leak. Correct all leaks at once.

5.Reconnect fireplace and equipment shutoff valve to gas sup- ply. Check reconnected fittings for leaks.

Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)

1.Close equipment shutoff valve (see Figure 33).

2.Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas fireplace or opening main gas valve located on or near gas meter for natural gas fire- place, or using compressed air.

3.Check all joints from propane/LP supply tank or gas meter to equipment shutoff valve (see Figure 34 for propane/LP or Figure 35 for natural gas). Apply noncorrosive leak detection fluid to all joints. Bubbles forming show a leak. Correct all leaks at once.

Equipment

Shutoff Open

Valve

Closed

Figure 33 - Equipment Shutoff Valve

Propane/LP

Equipment

Supply Tank

Shutoff

 

 

Valve

 

Gas Valve

Figure 34 - Checking Gas Joints for Propane/LP Gas Fireplace

Pressure Testing Gas Supply Piping System

Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)

1.Disconnect fireplace and its individual equipment shutoff valve from gas supply piping system. Pressures in excess of 1/2 psig (3.5 kPa) will damage fireplace gas regulator.

2.Cap off open end of gas pipe where equipment shutoff valve was connected.

3.Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas fireplace or opening main gas valve located on or near gas meter for natural gas fire- place, or using compressed air.

4.Check all joints of gas supply piping system. Apply noncorro- sive leak detection fluid to all joints. Bubbles forming show a leak. Correct all leaks at once.

Equipment

Shutoff

Valve

Gas

Meter

Gas Valve

Figure 35 - Checking Gas Joints for Natural Gas Fireplace

For..com

111251-01B

Image 20
Contents For Your Safety For Your Safety What to do if YOU Smell GASTable of Contents Safety InformationProduct Identification Local CodesLocation and Space Requirements Product FeaturesPRE-INSTALLATION Preparation Clearances Framing and FinishingLocation of Termination CAP Balcony with Perpendicular Side WallVenting Installation Instructions Installation PrecautionsInstallation Planning Horizontal Termination InstallationVent Pipe Connections Installing Horizontal Vent Cap Noncombustible Exterior Horizontal Termination Configurations Square TerminationCorner and Alternate Installation Horizontal System Installation Using TWO Elbows Venting with Two 90 ElbowsInstallation for Vertical Termination Flat Ceiling InstallationVertical Termination Configurations Venting with One 90 ElbowHigh Altitude Installation Vertical VentingFireplace Installation Parts Lists for Venting Kits and ComponentsInstalling Optional Blower Accessories Check GAS TypeModel BKT Installation Blower Model BKBlower Wiring Diagram Blower Model BKTInstalling GAS Piping to Fireplace Location Installation Items NeededConnecting Fireplace to GAS Supply Installation Items NeededPressure Testing Gas Supply Piping System Checking GAS ConnectionsPressure Testing Fireplace Gas Connections Cleaning Glass DoorREMOVING/REPLACING Glass Door Removing Louver PanelsInstalling LOGS, Lava Rock and Glowing Embers Installing Side Brick PanelsInstalling Log No Optional Remote Control Wiring DiagramWall Switch Installation For Your Safety Read Before Lighting Operating FireplaceLighting Instructions To Turn OFF GAS To ApplianceOperating Optional Blower Accessory Pilot AssemblyInspecting Burners Burner Flame PatternCleaning Maintenance Glass DoorPilot and Burners LogsTroubleshooting Needle, or similar object toGas leak. See Warning statement at TopVT36EPBA VT36EPRA VT36EPRBA Illustrated Parts BreakdownModels VT36EN, VT36ENB VT36ENRA, VT36ENRBA Parts List Parts Available not Shown109 2917 KEY Part Number Description QTY Replacement Parts Service HintsTechnical Service SpecificationsOwners Registration Form Postage Required Accessories Warranty Information