CFM Corporation WMC36 WMC42 manual Planning Information, Mounting the Fireplace, Ten Foot Rule

Page 6

WMC Series Woodburning Fireplace

Planning Information

Preplanning an installation is very important to ensure safety and to save time and money. An installer must predetermine where a fireplace will be set and how the chimney system will be run.

Mounting the Fireplace

A fireplace may be mounted on the following surfaces:

1.A flat combustible surface.

2.A raised wooden platform.

3.A concrete block or other solid object placed be- neath each of the four (4) corners of the fireplace.

The fireplace must be spaced 1/2" (13 mm) from a combustible back wall and 1/2" (13 mm) from a com- bustible side wall or support. Refer to Page 14, Figure 18.

Planning the Chimney Run

Determine how the chimney will be run, length of run and chimney components required to complete the job. (Fig. 4) Never install a chimney below minimum heights.

L

 

T

 

 

MODEL SK

TOTAL

INSTALLED

 

 

 

 

 

TRIPLE

2 WALL

LENGTH

LENGTH

 

 

 

 

WALL

CHIMNEY

(LT)

(L1)

 

 

 

 

 

 

 

 

 

 

 

 

L

 

1

81

SK81

�����"

�����"

 

 

 

 

818

SK818

�����"

�����"

 

 

 

L

 

1

83

SK83

�����"

�����"

 

 

 

84

SK84

"

�����

"

 

 

 

 

 

�����

 

 

 

 

 

 

 

 

 

FP288A

Fig. 5 Installed lengths of chimney sections.

In planning a chimney system, it is important to know:

1.The height of a chimney is measured from the hearth to the exit point on the termination.

2.A chimney cannot be offset more than 30° from a vertical plane.

3.A chimney may run straight up or it may be neces- sary to offset it to avoid obstructions.

4.The maximum length of an angled run (total chim- ney system) is 20' (6 m).

5.No more than 2 offsets (4 total 30˚ elbows in U.S./ or 2 total 45˚ elbows in Canada) per fireplace may be used.

6.A guy wire stabilizer (not provided) is required for chimneys extending more than 6' (1.8 m) above a roof line.

The Ten Foot Rule

Major U.S. building codes specify a minimum chimney height above the roof top. The “Ten Foot Rule” is a fire safety rule and not a draft rule. It is recommended that you always meet or exceed the “Ten Foot Rule,” espe- cially when installing a termination on a high pitch roof. (Fig. 6)

The key points of the "Ten Foot Rule" are:

1.If the horizontal distance from the chimney to the peak of the roof is 10' (3 m) or less, the top of the chimney must be at least 2' (609 mm) above the peak of the roof, but never less than 3' (914 mm) in height above the highest point where it passes through the roof.

2.If a horizontal distance from the chimney to the peak of the roof is more than 10' (3 m), a chimney height reference point is established that is on the surface of the roof a distance of 10' (3 m) from the chimney in a horizontal plane. The top of the chimney must be at least 2' (609 mm) above the reference point, but never less than 3' (914 mm) in height above the highest point where it passes through the roof.

0 To 10'

 

2' Min. 3'

0 To 10'

Min.

 

 

2' Min. 3'

 

Min.

Reference

 

Point

 

 

AC246

Fig. 6 Ten Foot Rule illustration.

6

20000583

Image 6
Contents WMC Series Safety Information Table of ContentsWMC36 Series Woodburning Fireplace Circulating Model Chase Installation Front Width Back Width DepthChimney Requirements Offset Installations Planning the Chimney Run Planning InformationMounting the Fireplace Ten Foot RuleChimney Supports InstallationChase Installation Insulating Fireplace Enclosure For Cold ClimatesInstallation Instructions Install Electrical ConnectionInstall Variable Speed Control FramingChimney Set-up Straight-Up Chimney InstallationOffset Installation Ceiling Chimney Hole Possible ObstructionsAngle of Chimney at Ceiling Positioning, Safety Strips Securing The FireplaceFraming the Ceiling Hole Size of ChimneyInstalling the Firestop Spacer Ceiling Hole Installing Outside Air KitInstalling the Chimney System Proper Firestop Spacer InstallationAdditional Ceilings Continue Installing Pipe to Complete RunCanadian Requirements for Insulation Shield Penetrating the RoofInstalling Chimney In a Chase Install Remainder of Chimney SectionsInstalling Top Housing Or Termination FinishingSide Wall Protection From top of grille opening for circu- lating modelsTop View Hearth Installation Minimum Wall ClearancesCommon Materials and Factors EH2416 458Installing Line for Gas Logs Fireplace Top ViewWMC36/42 Woodburning Fireplace Item/Model NumberAccessories Accessory Description Model NumberChimney Components Component DescriptionModel Number Component Description Model Number CanadaWMC Series Woodburning Fireplace Firegrate, Glass Doors, Outside Air System Fan MotorLiners Refractory or Metal CFM Corporation