COMMON PROBLEMS | COMMON CAUSES | POSSIBLE CORRECTIONS | |
|
|
| |
Rapid cycling - burner turns | Thermostat installed where drafts or | Locate thermostat on inner wall away from | |
on and off frequently. | heat affect reading. | heat sources or cool drafts. | |
|
|
| |
| Heat anticipator in thermostat | Adjust heat anticipator to match current | |
| adjusted incorrectly. | draw. Refer to boiler wiring diagram. | |
|
|
| |
| Incorrect limit setting. | Have qualified service technician increase | |
|
| limit setting to decrease cycling. Normal | |
|
| operation is usually less than 5 psig. | |
|
|
| |
Need to frequently add | Leaks in boiler or piping. | Have qualified service technician repair leaks | |
makeup water. |
| at once to avoid constant use of makeup | |
|
| water. | |
|
|
| |
Popping or percolating noise | Mineral deposits in sections due to | Have qualified service technician | |
heard in boiler. | constant use of makeup water. or | boiler and repair leaks at once to avoid | |
| incorrect pH. | constant use of makeup water and check | |
|
| pH | |
|
|
| |
Metal flakes found in flueway. | Contaminated combustion air supply. | Remove sources of hydrocarbons in or | |
|
| near boiler area. (Bleaches, cleaners, | |
|
| chemicals, sprays, fabric softeners, paint | |
|
| remover, etc.) | |
|
|
| |
| Condensation of combustion gases. | Have qualified service technician check | |
|
| boiler operation. | |
|
|
| |
Isolated radiation does not | Air vents or traps inoperative. | Have qualified service technician repair, | |
heat. |
| clean or replace air vents or traps. | |
|
|
| |
Water disappearing from | Incorrect Hartford Loop piping. | Have qualified service technician pipe boiler | |
gauge glass and back into |
| exactly as shown in Boiler Manual. | |
system through return piping. |
|
| |
Have qualified service technician clean or | |||
| |||
|
| replace | |
|
|
| |
| Have qualified service technician clean or | ||
|
| replace vacuum breaker. | |
|
|
| |
Violent waterline fluctuations | Dirt, oil or other impurities in water. | Have qualified service technician skim | |
- surging. |
| boiler. | |
OR |
|
| |
Waterline too high. | Have qualified service technician adjust | ||
Water passing into steam | |||
| waterline to normal height. | ||
mains - priming. |
| ||
|
| ||
Incorrect piping. | Have qualified service technician pipe boiler | ||
| |||
|
| exactly as shown in Boiler Manual. | |
|
|
| |
| Sudden release of boiler steam | Have qualified service technician adjust | |
| pressure by action of zone valves. | valve operating time or install | |
|
| valves. | |
|
|
| |
Domestic water from tankless | Mineral deposits insulate internal | Have qualified service technician delime or | |
heater is hot then suddenly | waterways of heater. | replace coil. | |
turns cold. |
|
| |
Boiler | Have qualified service technician remove | ||
OR | |||
added to boiler water and is insulating | and clean coil AND drain and flush boiler to | ||
Domestic water from tankless | |||
outside of coil. | remove | ||
heater is always lukewarm. | |||
|
| ||
Incorrect mixing valve setting for | Have qualified service technican adjust | ||
| |||
| tankless heater. | mixing valve setting. | |
|
|
| |
| Domestic flow rate too high. | Have qualified service technician install flow | |
|
| check valve set to rating of tankless heater. | |
|
|
| |
| Incorrect setting on tankless heater | Have qualified service technician raise | |
| control. | tankless control setting. Adjust differential | |
|
| on tankless control to lower setting. | |
|
|
|
The problems and corrections above represent common situations that can occur. There may be others not listed above. It is important always to contact a qualified service techni- cian if you have any questions about the operation of your boiler or system.