Weil-McLain 550-141-830/1202 manual Fill the system

Page 10

Detailed Service Procedures

Fill the system:

1.Do not fill (except for leakage tests) until boiler is ready to be fired.

2.Fill to normal water line as indicated on jacket front panel.

3.Boiler water pH 7.0 to 8.5 is recommended.

Failure to maintain recom- mended pH can cause section failure and leaks.

Skim steam boiler:

Clean new steam boilers to remove any impurities. Failure to properly clean can result in violent water level fluctuations, water passing into steam mains, or high maintenence costs on strainers, traps or vents. Skim boiler only. Do not clean old piping or leaks can occur.

Do not use petroleum-based

compounds in boiler system. Damage to

system components can result, causing property damage.

1.Provide 1-1/2" skim piping from skim tapping (located on front of boiler) to floor drain. Add a tee in piping to observe skim water level. Raise waterline to midpoint of skim tapping.

2.Fire burner to maintain water temperature below steaming temperature during skimming process.

3.Feed in water to maintain water level. Cycle burner to prevent rise in steam pressure. Continue skimming until discharge is clear.

4.While boiler is warm, but not hot, drain boiler through drain valve.

5.Remove skim piping. Close drain valve. Fill with fresh water to normal waterline. Start burner and steam for 15 minutes to remove dissolved gases. Stop burner.

6.Check traps and air vents for proper opera- tion.

7.Process may need to be repeated after several weeks of operation.

To place in operation:

Follow information below to prevent severe personal injury, death or substantial prop- erty damage:

Do not use crankcase drainings or any oil containing gasoline. See burner manual for proper fuel oil.

Do not attempt to start burner when excess oil has accumulated in combustion chamber, when unit is full of vapor, or when combustion chamber is very hot.

Do not start burner unless collector hood, flue cap, jacket cap, breeching and burner mount- ing door are secured in place.

Never burn garbage or paper in the boiler.

Never leave combustible material around boiler.

1.Verify boiler is filled with water to normal waterline as indicated on jacket front panel.

2.Open burner door and verify rear target wall, floor and burner door insulations are in proper condition and position.

3.Verify burner mounting door is closed and

bolted tightly and burner plug is connected.

4.Refer to burner manual for burner start-up, adjustment and check-out procedures. Factory burner adjustment and settings may not be suitable for specific job conditions.

Make final burner adjustments using combustion test equipment to assure proper operation. Do not fire boiler without water. Sections will overheat, damaging boiler and resulting in substantial property damage.

5.Check boiler and system piping for leaks.

6.Inspect breeching and venting for proper operation.

10

Part No. 550-141-830/1202

Image 10
Contents Part No -141-830/1202 Read This Page First Hazard DefinitionsForYour Safety Tips for steam systemsRoutine Maintenance Schedule Start-up SGO with float-type low water cutoffSGO with probe-type low water cutoff Common Problems Common Causes Possible Corrections Annual Service Check List Detailed Service Procedures Cleaning boiler fluewaysFill the system Controls requiring annual service General description of control operationPart No -141-830/1202

550-141-830/1202 specifications

The Weil-McLain 550-141-830/1202 is a high-efficiency boiler designed for water heating and heating applications in residential and commercial environments. Known for its reliability and performance, this model incorporates advanced technologies that enhance energy efficiency and reduce operating costs.

One of the standout features of the Weil-McLain 550-141-830/1202 is its robust construction, utilizing durable materials to ensure longevity and resistance to wear and corrosion. This boiler is designed with a high output capacity, providing ample heat for various applications, making it suitable for larger homes or commercial establishments. The unit is also engineered to accommodate multiple zoning configurations, allowing for customizable heating solutions tailored to specific needs.

This model incorporates a state-of-the-art control system that optimizes performance by adjusting to the specific demands of the heating system. This smart technology enables precise temperature control and enhances energy savings. Additionally, the Weil-McLain 550-141-830/1202 is compatible with smart home systems, providing users with the ability to monitor and control heating functions remotely.

Efficiency is further enhanced by the incorporation of a modulating burner, which adjusts its output based on the heating needs of the space. This allows for significant reductions in fuel consumption while maintaining comfort. The unit is also designed to work with various fuel types, including natural gas and propane, offering flexibility to homeowners and businesses alike.

Another significant characteristic is its compact design, which allows for versatile installation options, even in tight spaces. The appliance is also equipped with advanced safety features, including low water cutoff, pressure relief valves, and venting options that ensure safe and efficient operation.

Maintenance is a key consideration with the Weil-McLain 550-141-830/1202. Its user-friendly design allows for easy access to components, facilitating routine inspections and servicing. This ease of maintenance contributes to its reliability and prolongs the lifespan of the boiler.

In summary, the Weil-McLain 550-141-830/1202 boiler is a sophisticated heating solution characterized by its efficiency, durability, and advanced technology. Ideal for both residential and commercial applications, it ensures optimal comfort while keeping energy costs manageable. With its robust features and ease of use, it remains a preferred choice among homeowners and professionals in the heating industry.