HVAC SETBACK SYSTEMS

Occupancy Detection

Setback Operation

Door Switch Only Operation

Occupancy Detection

Install jumper JP3.

The T170 can be used with the PECO S200 series occupancy detection equipment. The occupancy and door switch inputs are designed to con- nect to the SB200 slave sensor and SE200 door switch. The Occupancy sensor switch is open when there is occupancy and closed when unoccupied. The Door Switch is open when the door is open and closed when the door is closed. This system requires both an Occupancy Sen- sor and a Door Switch. Operation is as follows:

FROM OCCUPIED MODE:

1.A door close signal initiates an occupancy status detection.

2.If occupancy is detected the T170 will maintain normal HVAC control. It then waits for a door open signal before determining occupancy again.

3.If no occupancy signal is detected within 2 minutes the T170 changes to unoccupied mode and controls at setback values.

FROM UNOCCUPIED MODE:

1.The T170 continually monitors the room.

2.Any occupancy detection, including door open, will set the operation to occupied mode.

In either mode, if the door is left open for more that 2 minutes the T170 will disable the HVAC system. A one-time ten minute override can be initiated by pressing any thermostat key pad.

In an Occupied State the thermostat operates normally and looks for a door close. In the Unoccupied State the thermostat sets heating and cooling set points to setback values, as determined by factory or user settings. In this mode the fan is automatically set to cycle with demand. The T170 will continue to monitor the occupancy sensor and will go to occupied state anytime occupancy is detected.

Setback Operation

Remove jumper JP3.

This is a low level switch input that is normally open. When closed the T170 Heating and Cooling setback limits are used as temperature control points. Fan operation in setback is cycled with demand. Pressing any button will override setback for 1 hour. Setback will override any user setting except if the control is turned to OFF. Units with a controlled off factory setting will override the OFF setting.

Intelligent occupancy sensors like the SD200-001 and SD200-002 can be used with this input to set the HVAC system to control at setback limits.

Door Switch Only Operation

Install jumper JP3.

A stand alone door switch can be connected to the T170 to disable the HVAC system if the door is left open for more that 2 minutes. A one-time ten minute override can be initiated by pressing any thermostat key pad.

CONDENSATE OVERFLOW INTERRUPT

The remote probe input can be used with a condensate overflow switch (CO), either in conjunction with a remote probe (normally closed CO switch) or with local sensing (normally open CO switch). When con- densate switch activates, the T170 will display the service wrench and disable all outputs.

Local Sensor Installation

Remote Probe

 

White/Yellow

 

 

Normally

 

 

 

 

 

Open

Circuit Common

 

Condensate

White/Violet

 

 

 

Switch

 

 

 

Remote Probe Installation

Remote Probe

 

White/Yellow

Normally

Circuit Common

Closed

Condensate

White/Violet

Switch

FAN OPERATION

Your thermostat can be configured for up to two fan speeds. Fan staging follows the Heat and Cool Staging Separation. Heat and Cool staging can be user selected to different values.

The FAN button is used to select FAN AUTO or ON. In the Auto position the fan cycles on with demand for heating or cooling. If ON is selected the fan will run continuously.

FAN AUTO:

Fan cycles on with demand

FAN ON:

 

 

 

FAN 2 ON

 

 

 

 

 

 

(FAN 1 OFF)

 

 

 

Fan runs continuously

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FAN 1 ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IF

2F

3F

4F

SETPOINT

Temperature Demand

 

 

 

 

 

 

 

 

 

 

 

CONTROLLED OFF

FACTORY CONFIGURATION

A factory configuration may be provided to ensure minimum heat and cool requirements. With this configuration the heat and cool outputs are automatically cycled on at the heat and cool setback limits. Your thermo- stat may not have this feature.

© COPYRIGHT 2008 PECO, INC. ALL RIGHTS RESERVED.

P/N 69289 3220-2083 REV 0 PAGE 2

Image 2
Contents Typical Operation InstallationMounting the Thermostat Condensate Overflow Interrupt Controlled OFF Factory ConfigurationHvac Setback Systems FAN OperationJP4 Jumper Selection Wiring DiagramOutput Configuration JP3 Jumper SelectionOutput Configuration Menu Service MenuService Menu Functions

TC170 specifications

Pecoware TC170 is an innovative touch computer designed for various industrial applications, offering robust features and cutting-edge technology to meet the demands of modern businesses. With a focus on durability, performance, and user-friendly interfaces, the TC170 stands out in the market as a reliable solution for various operational needs.

One of the main features of the Pecoware TC170 is its impressive touchscreen display. The device comes equipped with a 17-inch high-resolution display that provides excellent visibility, even in challenging lighting conditions. This makes it ideal for environments such as factories and warehouses where bright lights or glare might interfere with visibility. The touchscreen is designed for ease of use, supporting multi-touch functionality for a more intuitive user experience.

The TC170 is built on a powerful processor platform, ensuring fast response times and efficient multitasking. It typically features an Intel Celeron or Core i-series processor, allowing it to handle various applications seamlessly. This performance is further complemented by ample RAM options, which enable the device to run multiple applications without compromising speed or efficiency.

In terms of connectivity, the Pecoware TC170 excels with multiple ports, including USB, Ethernet, and serial connections, allowing easy integration with various peripherals and automation systems. This versatility makes it suitable for different sectors, including manufacturing, logistics, and retail.

Durability is another defining characteristic of the TC170. It is designed to withstand the rigors of industrial environments, featuring a rugged chassis and IP-rated protection against dust and water. This resilience ensures that the device can operate reliably in harsh conditions, minimizing downtime and maintenance costs.

Additionally, the TC170 supports various operating systems, including Windows and Linux, providing flexibility for businesses to choose the software that best meets their operational needs. This adaptability is crucial in a rapidly evolving technological landscape, allowing organizations to stay competitive.

With its blend of technology, durability, and functionality, the Pecoware TC170 is an ideal solution for businesses looking to enhance productivity and streamline operations. Its user-friendly design, coupled with robust performance features, positions it as a frontrunner in the touch computer market. Whether for data entry, inventory management, or real-time processing, the TC170 is designed to meet the diverse needs of modern enterprises, making it a valuable investment for the future.