ming this sensor and return to step 1.b

j)You will hear “Enter number then press pound”

k)Enter the value then press #.

Use * to program a negative number (i.e. *20 = -20º)

Acceptable range is -999 to 999

l)You will hear the value you just entered (i.e. 50º)

m)Proceed to step 4.a

4. Programming the callout delay time

a)You will hear "Callout time delay is x minutes press 1 to change” (default 0 minutes)

b)Press 1 to make a change

Press 2 to skip and return to step 1.b

c)You will hear “Enter number then press pound

d)Enter the time delay in minutes (i.e. 15 for 15 minutes or 0 minutes for an immediate callout)

Acceptable range is 0 to 900 minutes

e)You will hear the value you just entered

f)Proceed to step 1.b

Repeat the steps 1 to 4 for each additional sensor.

Programming Temperature Corrections

The Four Zone Temperature Monitor allows the user to correct for small tem- perature measurement errors due to sensor cable extension length for each sensor. A calibrated standard must be used to obtain the actual temperature.

a) From the Main Menu, press 2 to Set Limits

b) You will hear “Enter Sensor Number"

c) Enter #

d) You will hear "Enter Sensor Number to Adjust"

Alarm Conditions

When an alarm condition occurs, the alarm relay and buzzer are activated and the Four Zone Temperature Monitor waits 2 minutes before making callouts.

The time remaining before alarm callouts commence is displayed. During this time, onsite personnel can cancel the emergency by pressing the black alarm acknowledge button on the face of the Four Zone Temperature Monitor.

 

1: 51 >

CALL-

 

 

 

 

2: 28

OUTS

 

 

3:

IN

 

 

4:

01:58

 

 

 

 

 

 

 

 

 

Alarm Callouts

When the Four Zone Temperature Monitor is making callouts, the status is displayed in the right side of the screen.

While the Four Zone Temperature Monitor is making telephone calls, the display is not updated with new temperature readings.

e)

Enter the number of the sensor you want to correct (1-8)

 

►To return to the Set Limits Menu press 0

f)

You will hear "Enter Sensor Number x Actual Temperature, then press

 

pound"

g)

Enter the actual temperature measured using the standard, then press #.

 

► The maximum the temperature measurement can be corrected is +-25º

 

from the currently displayed temperature.

 

(i.e. If the temperature currently being displayed is 100º, the max correc-

 

tion is 125º and the min correction is 75º. An “invalid" message is played

 

for larger corrections.)

h)

You will hear the corrected temperature and the corrected temperature will

 

be displayed on the display.

The temperature

sensor has

become

disconnected

 

1: 501 >

ALERT

 

 

 

 

2: OPEN

CALL1

 

 

3:

RING

 

 

4:

CHECK

 

 

 

 

 

 

 

 

 

An alert callout is being made

Contact 1 is currently being called

The line is ringing

8

17

Image 8
Contents Four Zone Temperature Monitor and Alarm User’s GuideWARRANTY/DISCLAIMER General Description Model DetailsAccessing advanced network setup Optional 20 / 30 Hour Extended BatteriesStandard 4 hour / 20 / 30 Hour Batteries Verifying Network Connectivity DCP unitsTroubleshooting Installing the Four Zone Temperature Monitor and AlarmVerifying telephone communication Surge suppresser must be used for the phone lineFrequently Asked Questions Accessing the Four Zone Temperature Monitor over the phoneWhen is a sensor/input in alarm condition? Main Menu Option FunctionProgramming the Sensor ID message Programming the Lower and Upper Temperature LimitsSensor Reading After Callouts 0158 501Programming the Alarm Input 200 510 370 1845Start Up Sensor ReadingAccessing the Program Menu Confirming Alarm Conditions RemotelyTure Confirming Alarm Conditions Locally Programming the Autodialer FunctionsChanging the Callout Delay Time Clearing High and Low Temperature Readings LocallyClearing High and Low Temperature Readings Remotely Checking Sensor Inputs LocallyProgramming the Full Access PIN Number Set Temperature Readout Units C or FProgram Power Outage Delay Time PIN number must be 4 digits and must not include a # sign