Nortec NH Series installation manual Software Initial SELF-TEST, Self-Test Messages, Self-Help

Page 40

E.SOFTWARE INITIAL SELF-TEST

 

Table 2. Self-Test Messages

 

 

Graphic Display

Explanation/Comments (What You Read)

 

 

NHTC START-UP:

The unit is beginning its bootup routine, along with powering up the EEPROM on the

INIT CYLINDER

SMART Cylinder

 

 

NHTC START-UP:

The unit reads the type of cylinder to provide maximum control of operation. If it

READING CYLINDER DATA

unable to do so it will skip the rest of the self-test and fault out.

 

 

SELF TEST CYLINDER

Unit energizes the fill valve for 1 second.

Inlet Valve

 

ESC

 

 

 

SELF TEST CYLINDER

Unit energizes the drain valve for 2 seconds.

Drain Valve

 

ESC

 

 

 

SELF TEST CYLINDER

Unit closes the contactor for 2 seconds.

Heat Cont.

 

ESC

 

 

 

SELF TEST CYLINDER

Unit activates the pump (if present) for 2 seconds.

Pump

 

ESC

 

 

 

SELF TEST CYLINDER

Unit activates the bleed valve (if present) for 2 seconds.

Bleed Valve

 

ESC

 

 

 

SELF TEST REMOTE

Unit activates the steam relay for remote fault indication package and green light.

Steam Relay

 

ESC

 

 

 

SELF TEST REMOTE

Unit activates the service relay for remote fault indication package and yellow light.

Service Relay

 

ESC

 

 

 

SELF TEST REMOTE

Unit activates the error relay for remote fault indication package and red light.

Error Relay

 

ESC

 

 

 

SELF TEST REMOTE

Unit activates the unit on relay.

Oper. Relay

 

ESC

 

 

 

F.SOFTWARE FLOW CHART WITH DEFINITIONS

(1)The flow chart in Figure 7 depicts the software logic and definitions.

G.SELF-HELP

(1)The microcomputer applies corrective actions whenever its self-diagnostics identifies a problem that it is able to correct by itself. If the corrective action is not successful then it displays a system message. If the corrective action requires a service person, then the microcomputer’s only resort is to stop the unit and display a system message. The unit never stops unless it has to.

(2)After three days of no call from either the on/off controls or the modulating controls, when active, the three-day drain active feature is automatically activated long enough to drain all water from the steam cylinder. This NORTEC feature will prolong the life of the cylinder. (User selectable, default is ON.)

10-20

Page 33 2008-08-28

Image 40
Contents SeriesTM 2522381-C2008-08-28 Revision Number Date Date Put ManualTable of Contents Warranty List of Figures List of Tables 2008-08-28 Introduction Nhtc PRE-INSTALLATION PackagingHumidifier Box Preinstallation Equipment Verification Typical Nhtc Installation Sheet 1 Typical Nhtc Installation Sheet 2 This page Intentionally Left Blank Installation Humidifier Installation LocationMounting with Keyholes Mounting with Wall BracketDrain Line Drain Water from Humidifier can be Very HOT Water Supply LineSteam Runs and Condensate Returns Clearances and Operating Conditions Drain Water and Supply Connection 30+ Copper Tube Inch MED-L Tubing 1.125 inch OD 10-10 10-10 Nominal Tube Standard 90degree Standard 45 degree Diameter Side Outlet TeeSteam Outlet Steam InletPrimary Voltage Supply Wiring Primary Voltage Supply Wiring to Humidifier Control WiringDemand Signal Controls Installation ElectricalOn/Off Control Guidelines and Low Voltage Terminal Strip Nortec Control Guidelines and Wiring Optional Optional Outdoor Temperature Reset Function Setpoint Versus Outdoor TemperatureNortec Online Installation Humidity Transducer Signal InstallationNetworking Nhtc Nortec Humidity Transducer Guidelines and Wiring Optional Networking NHTCs Optional Nortec OnLine Installation Guidelines Optional Operation Nhtc Nhtc ComponentsHumidifier START-UP Basic Steam Production MethodNHTC/NHPC Components Item Number Component Name DescriptionIf loose or frayed Humidifier Start-Up Basic Steam Production Method Software Flow Chart with Definitions Software Initial SELF-TESTSelf-Test Messages SELF-HELPSoftware Flow Chart Sheet 1 Software Flow Chart Sheet 2 Software Flow Chart Sheet 3 Software Flow Chart Sheet 4 Software Flow Chart Sheet 5 Software Flow Chart Sheet 6 Software Flow Chart Sheet 7 Signal Light Status System Messages and LightsDouble Unit Operation Yellow Green RedStatus Messages with LED State Nhtc Display Message LED state System ActionSymptom Diagnosed Probable Cause Corrective Action Steam Distributor Operation Steam DistributionSAM-e Operation Blower Pack Operation and Adjustments Digital Control Operation Controls and Remote Communication OptionalDigital Transducer Operation Nortec Links 2 Operation Nortec Online OperationThis page Intentionally Left Blank Maintenance Procedures NH Electrode Steam Humidifiers When to Replace the Steam CylinderExtended SHUT-DOWN Components of the Steam Cylinder Cylinder ComponentsHOW to Remove the Steam Cylinder Cylinder Removal ProcedureMandatory Cleaning of the Drain Valve Drain Valve MaintenanceHOW to Install the Replacement Cylinder Cylinder Replacement ProcedureTroubleshooting Preparation Troubleshooting NH Electrode Steam HumidifiersStarting Point Troubleshooting Symptoms System What to Check WhyTroubleshooting Distributors Ensuring a Demand SignalProcedure Check Why and HowBlower Packs Troubleshooting Digital ON/OFF Humidistat Sensor CalibrationNH System Messages REDProbable Cause Corrective Action E17 Req off current Contactor is open? W27 Safety loop instability Verify that the RH setpoint is less than the RH high limit Term Definitions 10V Digital Humidistat Sensor CalibrationTerm Definition Technical Controller and Sensor Specifications Wiring and TerminalsHumidifier Control Information NH Wiring NHTC/NHPC Double Unit Wiring DiagramNHTC/NHPC Wiring Diagram PRE-NORTEC Links START-UP Checklist PRE-NORTEC Online Start UP Checklist WiringCheck Lists Humidifier Mandatory PRE-START UP Checklist WiringPower Water QualityHumidifier Mandatory START-UP Checklist and Quick Reference START-UP ProcedurePreliminary RemarksWhen to Replace the Cylinder Periodic Maintenance Checklist and Quick Reference page 1Cylinder Replacement Procedure Periodic Maintenance Checklist and Quick Reference page 2 Extended ShutdownSpare Parts and Exploded Views ASD, BSD, CSD DistributorNH Series Humidifier Spare Parts NHTC/NHPC Plumbing Compartment Exploded View and Spare PartsNHTC/NHPC Plumbing Part List Model10-50Page 79 NHTC/NHPC Plumbing Part List Fillcup Extension KIT NHTC/NHPC10-50 10-50Page 81 NHTC/NHPC Electrical Parts List Three Phase This page Intentionally Left Blank Warranty Cylinder Replacement Date MM/DD/YYYY Walter Meier Climate USA Inc

NH Series specifications

The Nortec NH Series stands as a remarkable line of heating and cooling equipment designed specifically for commercial and industrial applications. Renowned for its efficiency, reliability, and innovation, the NH Series is engineered to meet the demanding needs of various environments, including hospitals, educational institutions, and office buildings.

One of the standout features of the Nortec NH Series is its modular design. This flexibility allows for easy integration into existing systems, making it an ideal choice for both new installations and upgrades. The modular setup not only enhances space efficiency but also allows users to scale the system according to their specific requirements. This adaptability is essential for facilities looking to optimize their HVAC systems without extensive renovations.

The NH Series incorporates advanced technologies that set it apart in the market. It employs high-efficiency heat exchangers made from durable materials that provide exceptional thermal performance. These heat exchangers facilitate rapid heat transfer while maintaining energy efficiency, lowering operational costs. Additionally, the unit features variable-speed fans that adjust airflow according to real-time demands, contributing to quieter operation and further energy savings.

Another noteworthy characteristic of the NH Series is its intelligent control system. The integrated controls offer user-friendly interfaces and compatibility with building management systems. This enables operators to monitor and adjust settings remotely, enhancing operational efficiency and ensuring optimal indoor climate conditions.

Furthermore, the Nortec NH Series is designed with sustainability in mind. It complies with stringent environmental regulations and utilizes eco-friendly refrigerants, reducing the overall carbon footprint of the facility. This commitment to sustainability resonates with businesses looking to enhance their green credentials while maintaining a comfortable environment.

In summary, the Nortec NH Series exemplifies innovation in HVAC technology, combining modular design, high-efficiency heat exchangers, variable-speed fans, intelligent controls, and sustainable practices. These features make it a top choice for professionals seeking reliable and efficient heating and cooling solutions for a variety of commercial applications. With the Nortec NH Series, users can achieve significant energy savings, enhanced comfort, and a positive impact on the environment.