Nortec Industries NHTC Series installation manual Humidifier Variable Addresses Unit #3

Page 17

Table 6. Humidifier Variable Addresses

Unit #3

Unit #3

BACnet

Lonworks

 

N2

 

Variable Name

Type

Instance

SNVT

SNVT #

Element

Type

 

Instance

nvoHourOpt_3

AV

31

time_hour

124

45

AI

 

31

nvoCapLimit_3

AV

32

lev_percent

81

46

AI

 

32

nvoRHDem1_3

AV

33

lev_percent

81

47

AI

 

33

nvoSet1_3

AV

34

lev_percent

81

48

AI

 

34

nvoRHDem1_3

AV

35

lev_percent

81

49

AI

 

35

nvoSet2_3

AV

36

lev_percent

81

50

AI

 

36

nvoSysDemand_3

AV

37

lev_percent

81

51

AI

 

37

nviCapLimit_3

AV

38

lev_percent

81

52

AO

 

38

nviSet1_3

AV

39

lev_percent

81

53

AO

 

39

nviSet2_3

AV

40

lev_percent

81

54

AO

 

40

nviRHDem1_3

AV

41

lev_percent

81

55

AO

 

41

nviRHDem2_3

AV

42

lev_percent

81

56

AO

 

42

nviDisable_3

AV

43

switch

95

64

AO

 

43

Expansion_3

AV

44

N/A

N/A

N/A

AO

 

44

Expansion_3

AV

45

N/A

N/A

N/A

AO

 

45

 

 

 

 

 

 

 

 

 

nvoFault_3

BV

31

switch

95

57

Binary In

 

31

nvoHWSensor_3

BV

32

switch

95

58

Binary In

 

32

nvoNetSensor_3

BV

33

switch

95

59

Binary In

 

33

nvoDisable_3

BV

34

switch

95

60

Binary In

 

34

nvoSecurity_3

BV

35

switch

95

61

Binary In

 

35

nvoService_3

BV

36

switch

95

62

Binary In

 

36

nvoStatus_3

BV

37

switch

95

63

Binary In

 

37

Expansion_2

BV

38

N/A

N/A

N/A

Binary Out

 

38

nviNetSensor_3

BV

39

switch

95

65

Binary Out

 

39

nvoConnection_3

BV

40

switch

95

66

Binary Out

 

40

Expansion_3

BV

41

N/A

N/A

N/A

Binary Out

 

41

Expansion_3

BV

42

N/A

N/A

N/A

Binary Out

 

42

Expansion_3

BV

43

N/A

N/A

N/A

Binary Out

 

43

Expansion_3

BV

44

N/A

N/A

N/A

Binary Out

 

44

Expansion_3

BV

45

N/A

N/A

N/A

Binary Out

 

45

10-10

Page 10 2008-02-18

Image 17
Contents Manual No. H-502 Nhtc Nortec Links 2 Options2008-02-18 Proprietary Notice Liability NoticeTable of Contents List of Figures This page Intentionally Left Blank 10-00 IntroductionProtocol Options Overview10-10 InstallationNetworking Recommended Wire Types and Lengths WiringBaud Rates Gateway ConfigurationNetwork Integration Variable Definition Variable Definitions Unit must be configured for Networked demand10-10 Snvt Snvt # Humidifier Variable Addresses Unit #1Humidifier Variable Addresses Unit #2 Humidifier Variable Addresses Unit #3 Humidifier Variable Addresses Unit #4 Humidifier Variable Addresses Unit #5 Humidifier Variable Addresses Unit #6 Humidifier Variable Addresses Unit #7 Humidifier Variable Addresses Unit #8 Nhtc 10-10 This page Intentionally Left Blank 10-20 START-UPSTART-UP Procedure Nortec Links 2 START-UP Checklist10-30 TroubleshootingIndicator Lights TroubleshootingOnLine Diagnostic LED Locations LED Name Color Function OnLine Diagnostic LED DescriptionLinks 2 Module Diagnostic LEDs Problem Troubleshooting Communication Problems10-40 Spare PartsReplacement Parts BACnet or N2 Module Ethernet Switch 10-50 TechnicalTo Units 2 to Net +Net + Shield-+ Net Net This page Intentionally Left Blank Warranty Authorized Agent