Nortec Industries NHTC Series installation manual Humidifier Variable Addresses Unit #4

Page 18

Table 7. Humidifier Variable Addresses

Unit #4

Unit #4

BACnet

Lonworks

 

N2

 

Variable Name

Type

Instance

SNVT

SNVT #

Element

Type

 

Instance

nvoHourOpt_4

AV

46

time_hour

124

67

AI

 

46

nvoCapLimit_4

AV

47

lev_percent

81

68

AI

 

47

nvoRHDem1_4

AV

48

lev_percent

81

69

AI

 

48

nvoSet1_4

AV

49

lev_percent

81

70

AI

 

49

nvoRHDem1_4

AV

50

lev_percent

81

71

AI

 

50

nvoSet2_4

AV

51

lev_percent

81

72

AI

 

51

nvoSysDemand_4

AV

52

lev_percent

81

73

AI

 

52

nviCapLimit_4

AV

53

lev_percent

81

74

AO

 

53

nviSet1_4

AV

54

lev_percent

81

75

AO

 

54

nviSet2_4

AV

55

lev_percent

81

76

AO

 

55

nviRHDem1_4

AV

56

lev_percent

81

77

AO

 

56

nviRHDem2_4

AV

57

lev_percent

81

78

AO

 

57

nviDisable_4

AV

58

switch

95

86

AO

 

58

Expansion_4

AV

59

N/A

N/A

N/A

AO

 

59

Expansion_4

AV

60

N/A

N/A

N/A

AO

 

60

 

 

 

 

 

 

 

 

 

nvoFault_4

BV

46

switch

95

79

Binary In

 

46

nvoHWSensor_4

BV

47

switch

95

80

Binary In

 

47

nvoNetSensor_4

BV

48

switch

95

81

Binary In

 

48

nvoDisable_4

BV

49

switch

95

82

Binary In

 

49

nvoSecurity_4

BV

50

switch

95

83

Binary In

 

50

nvoService_4

BV

51

switch

95

84

Binary In

 

51

nvoStatus_4

BV

52

switch

95

85

Binary In

 

52

Expansion_2

BV

53

N/A

N/A

N/A

Binary Out

 

53

nviNetSensor_4

BV

54

switch

95

87

Binary Out

 

54

nvoConnection_4

BV

55

switch

95

88

Binary Out

 

55

Expansion_4

BV

56

N/A

N/A

N/A

Binary Out

 

56

Expansion_4

BV

57

N/A

N/A

N/A

Binary Out

 

57

Expansion_4

BV

58

N/A

N/A

N/A

Binary Out

 

58

Expansion_4

BV

59

N/A

N/A

N/A

Binary Out

 

59

Expansion_4

BV

60

N/A

N/A

N/A

Binary Out

 

60

10-10

Page 11 2008-02-18

Image 18
Contents Nhtc Nortec Links 2 Options Manual No. H-502Proprietary Notice Liability Notice 2008-02-18Table of Contents List of Figures This page Intentionally Left Blank Introduction 10-00Overview Protocol OptionsInstallation 10-10Networking Wiring Recommended Wire Types and LengthsGateway Configuration Network IntegrationBaud Rates Variable Definition Unit must be configured for Networked demand Variable Definitions10-10 Humidifier Variable Addresses Unit #1 Snvt Snvt #Humidifier Variable Addresses Unit #2 Humidifier Variable Addresses Unit #3 Humidifier Variable Addresses Unit #4 Humidifier Variable Addresses Unit #5 Humidifier Variable Addresses Unit #6 Humidifier Variable Addresses Unit #7 Humidifier Variable Addresses Unit #8 Nhtc 10-10 This page Intentionally Left Blank START-UP 10-20Nortec Links 2 START-UP Checklist START-UP ProcedureTroubleshooting 10-30Troubleshooting Indicator LightsOnLine Diagnostic LED Locations OnLine Diagnostic LED Description LED Name Color FunctionLinks 2 Module Diagnostic LEDs Troubleshooting Communication Problems ProblemSpare Parts 10-40Replacement Parts BACnet or N2 Module Ethernet Switch Technical 10-50Net + To Units 2 toNet + Shield-+ Net Net This page Intentionally Left Blank Warranty Authorized Agent