Lifebreath MAXTOP, 200MAX, 95MAX, 155MAX, 200ERV, 300DCS Inspect Exterior Hoods at least once a month

Page 27

Maintenance Routine for HRV (for ERV, see following page)

1.Inspect Exterior Hoods at least once a month.

Make sure exhaust and fresh air supply hoods are not blocked or restricted by leaves, grass, or snow. In winter, it is especially important to make sure snow is not blocking the hoods or that frost has not built up on the wire mesh (bird screen).

6. Clean Duct Work if Required

The duct work running to and from the HRV may accumulate dirt. Wipe and vacuum the duct once every year. You may wish to contact a Heating/Ventilation company to do this.

WARNING: Blockage of hoods may cause an imbalance.

7. General Maintenance - Twice a Year

Wipe down the inside of the cabinet with a damp cloth to remove dirt, bugs and debris that may be present.

2. Clean Air Filters (clean twice a year)

The standard filters equipped with your HRV are removable and washable.

a)simply open access door and slide core out

b)remove filter clips

c)once clips are removed filters can be taken off the core to be rinsed with water or a combination of mild soap and water. Do not clean in the dishwasher

d)to re-assemble, place clean filter(s) (wet or dry) back into their positions against the core and return clips to their original position

e)slide core back into its’ original position

3.Clean Core Twice a Year a) open access door.

b) carefully grip ends of core and pull evenly outward. Core may be snug, but will slide out of the channel

c) once removed from the cabinet remove filters

d) wash core in warm soapy water (do not use dishwasher) e) install the clean filters

f) install clean core

Note: Core installation label on the outer end of the core.

To install the clean core:

a)first mount the bottom flange of the core guide into the bottom H channel approximately 1/4” (6mm)

b)mount the left or right side flange of the core guide approximately 1/4” (6mm) followed by the other side

c)mount the top flange of the core guide into the top H channel approximately 1/4” (6mm).

d)with all four corners in place and the core straight and even, push hard in the centre of the core until the core stops on the back of the cabinet.

NOTE: Core will appear to stick out from cabinet approximately 1/8” (3mm). This is designed this way so that the access door will fit tight against the core.

4.Motors - Maintenance Free

5.Drain (condensate) Line - Clean once a year

Inspect drain line, drain spout and “P” trap for blockage, mould or kinks. Flush with warm soapy water and replace if worn, bent or unable to clean.

8. Cleaning the Fans

Fans may accumulate dirt causing an imbalance and/or excessive vibration of the HRV. A reduction in the air flow may also occur. In new construction this may result within the first year due to heavy dust and may occur periodically after that over time depending on the outdoor conditions.

unplug the HRV and open the service door

remove the core

remove ducting (metal and/or flexible insulated type) from the red and/or blue ports which are connected immediately inline with the fan assembly

use a small brush, such as an old toothbrush or pipe cleaner, and insert first

(a)through the large opening of the fan assembly and then

(b)through the smaller opening in the end of the fan assembly.

scrub individual fan blades until clean. Avoid moving or damaging balancing flat weight, clip is usually found on one or more of the fan blades

vacuum and wipe

reassemble making sure ducting is reattached firmly and insulation and moisture barrier are sealed and taped

Before attempting this task, thought should be given to having a qualified service technician complete the service work.

27

Image 27
Contents Contains 95MAX200ERVD Table of Contents ERV Questions & Answers Page Engineering Data Model 95MAXModel 155MAX Dimensions 155MAX inches mmModel 200MAX Dimensions 200MAX inches mmModel Maxtop Dimensions Maxtop inches mmModel 195DCS Dimensions 195DCSThermally CONDUCTIVE, Patented Aluminum Core Model 300DCSModel 200ERV Dimensions 200ERV inches mmModel 200ERVD Dimensions 200ERVDFunction & Control To select mode of operation for ControlAir NEW! AIR Sentry AIR Quality Sensor Optional Remote ControlsUsing the Dehumidistat MAX Port Specifications Location InstallationInstalling AIR Ducts Dampers and Grilles Supply AIR DuctingInstallation Diagrams Simplified Installation Supply/Return Method Fully Dedicated System Pitot Tube AIR Flow Balancing Balancing Collar Instructions Inspect Exterior Hoods at least once a month Maintenance Routine for ERV for HRV, see previous Occupant Symptom Cause SolutionTechnical Bulletin Residential Wiring Diagram McCormick Blvd. London, Ontario N5W 4C
Related manuals
Manual 10 pages 11.12 Kb Manual 32 pages 15.63 Kb Manual 12 pages 19.73 Kb

MAXTOP, 195DCS, 200ERVD, 200ERV, 300DCS specifications

Lifebreath is well-known for its innovative heat recovery ventilators that enhance indoor air quality while conserving energy. Among their acclaimed models, the Lifebreath 150SP, 200MAX, 150MAX, and 200STD stand out for both their functionality and design, delivering optimal performance for various residential and commercial applications.

The Lifebreath 150SP is designed for spaces requiring effective air exchange while maintaining energy efficiency. This model boasts a compact design, making it ideal for smaller homes or apartments. One of its main features includes a top-mounted control panel with a user-friendly interface, allowing for easy adjustment of settings. Equipped with a high-efficiency heat exchanger, the 150SP effectively transfers heat from the outgoing stale air to the incoming fresh air, minimizing energy loss. Additionally, the unit operates quietly, ensuring that comfort is not compromised.

On to the 200MAX, this model is engineered for larger spaces. With increased airflow capacity, it ensures consistent air quality in bigger areas while optimizing energy consumption. The 200MAX features advanced filtering systems that capture dust, pollen, and other allergens, promoting a healthier indoor environment. Its built-in defrosting system operates automatically, enhancing efficiency during colder months. The 200MAX also supports optional accessories, such as a programmable timer and an energy recovery ventilator, allowing users to customize performance to meet specific needs.

The Lifebreath 150MAX pairs the efficiency of the 150SP with added versatility. This model is suitable for mid-sized spaces and comes equipped with a dual motor system. This unique feature provides users with the flexibility to adjust airflow independently, accommodating varying room conditions. The 150MAX excels in both heating and cooling modes, ensuring comfort year-round.

Finally, the Lifebreath 200STD offers a straightforward approach to ventilation without compromising on performance. Designed for standard residential applications, the 200STD is easy to install and maintain, featuring a washable pre-filter. This model is energy efficient and operates quietly while delivering excellent air exchange rates, making it perfect for families seeking reliable indoor air management.

In conclusion, the Lifebreath range—150SP, 200MAX, 150MAX, and 200STD—showcases superior design and cutting-edge technology. With their focus on energy efficiency, user comfort, and adaptable features, Lifebreath models uphold a promise of high indoor air quality and sustainable living. These systems not only contribute to a healthier environment but also reduce energy costs, making them an ideal investment for any modern building.