VIII. Maintenance
Kooltronic
If filter service is neglected or delayed, the air conditioner will not perform at its design capacity. The first indication of excessively clogged air filters is usually a gradual increase of temperature within the equipment cabinet. If operation is continued under these conditions, the compressor will be shut off by the thermal overload device. The compressor will restart when its external temperature drops below the protector threshold setting and the compressor will continue to cycle on and off. Continued operation under these conditions will cause damage, shorten compressor life and void the warranty.
A. Filter Removal and Service
Kooltronic Air Conditioners feature an easily removable inlet filter to facilitate necessary cleaning.
CAUTION
Do not operate the air conditioner for extended periods of time with the filter removed, as the condenser coil may become clogged with dust or lint from the air entering the face. A unit with a clogged condenser coil will have the same reaction as one with a clogged filter.
A clean filter is the best protection.
1)Remove the two screws from the rear panel.
2)Remove the rear panel from the unit.
3)Remove the filter from the filter holder by moving it up and towards you.
4)After removal the filter should be flushed under warm water with the clean side up, driving contaminants out from the dirty side of the filter. If the accumulated dirt is oily, washing in a detergent bath is recommended, followed by a warm water rinse as above.
5)The filter may be sprayed with Kooltronic
6)Reinstall the filter.
7)Replace the rear panel and attach it to the unit with two screws.