B. Blowers
The design life of the blowers used in all Kooltronic Air Conditioners is substantially in excess of 20,000 hours. All Kooltronic condenser and evaporator blowers are equipped with
CAUTION
Before opening the air conditioner, disconnect all power.
If field replacement of a blower motor is necessary, most blower assemblies, including the mounting plate, are readily removable. Each of the blower mounting plates is held to the air conditioner cabinet structure by screws and nuts. For installation of the replacement blower, electrical connections may be broken at the terminal block, or power leads may be cut and appropriately spliced together.
C. Compressor
All Kooltronic compressors are approved by UL and CSA, and require no maintenance. They are hermetically sealed and charged at the factory, and equipped with
If the compressor fails, it is strongly recommended that the air conditioner be returned to Kooltronic for service.
D. Refrigerant Loss
Kooltronic Air Conditioners are subjected to a series of tests to detect refrigerant leaks, during and after manufacture. It is possible that shipping or other damage, or microscopic leaks over a long period, may result in the need for replenishment of refrigerant charge. When it has been verified by a Certified
EPA Technician that a refrigerant shortage does exist, the leak must be repaired. Then the unit may be evacuated and recharged in the field by a Certified EPA Technician only.
CAUTION
Refer to the data on the unit name plate which specifies the type of
refrigerant and the amount of charge in ounces.
E. Relocation
If your Kooltronic Air Conditioner has to be moved to another location by truck, the following precautions should be taken:
■
■
Conform to the applicable provisions of PROCEDURE FOR PROPER PACKING AND SHIPMENT OF KOOLTRONIC AIR CONDITIONERS in this manual under Section III. "PRODUCT HANDLING."