GE Monogram 5800 Series Preparation of the Wall Case for All Types of Construction, Case Angles

Page 25

Preparation of the Wall Case for All Types of Construction

Do not remove the stiffener from inside the wall case or the weather closure panel from the outside face of the wall case until the outdoor grille and chassis are ready to be installed.

Installation of Wall Case in Wall Opening

1.Position the wall case into the wall. The room side edge of the RAB71 or RAB77 wall case should be at least flush with the finished wall for line cord installations and permanent connection installations when no sub-base is used, and should project into the room at least 2-3/8" when a sub- base is used. If the minimum exterior dimensions are not met, refer to page 27 and 28. The outside edge of the wall case should extend at least 1/4" beyond the outside wall. This is necessary for proper caulking, to prevent sealing the drain holes in the rear flange of the wall case, and to facilitate the installation of an accessory drain, if used.

The wall case should be level from side to side and from level to 1/4 bubble tilt to the outdoors. The condensate disposal system in the unit is designed to dissipate the condensate water generated during cooling operation in accordance with ARI standards and actually uses this water for maximum unit efficiency. A level unit will also ensure proper performance of the Internal Condensate Removal (ICR) system optional on heat pump units.

2.The wall case should be secured to the wall at both sides. Use a minimum of two screws or other fastening device on each side. See Figure 2 page 26. Mark the wall case on each side 2" from the bottom and 2" from the top at a point where basic wall structure is located. Drill wall case and use fasteners appropriate for wall construction. All holes for fasteners in the side of the wall case must be at least 2" up from the bottom of the wall case. Never locate screws or put other holes in the bottom of the wall case. The only exception is when an RAD10 drain kit is installed to connect to an internal drain system. See page 36 for RAD10 Drain Kit information.

If the wall opening is greater than the case dimensions, spacers must be used on the sides between the wall case and the wall support structure to prevent distorting the wall case.

3.Caulk or gasket the entire opening on the outside between the wall case and exterior wall surface (4 sides) to provide total water and air seal.

4.Caulk or gasket room-side opening between wall case and interior wall surface (4 sides). Opening beneath or around the wall case can allow outdoor air to leak into the room resulting in increased operating costs and improper room temperature control.

Care should be taken in location of electrical supply entry in relationship to wall sleeve to assure access to receptacle or junction box once unit is installed.

Refer to page 43 for maximum power cord length.

Permanent connected units close to finished floor must allow for conduit clearance.

ge.com

Case Angles

In some installations such as curtain walls, window walls, or where the structural material of the wall is insufficient to support or fasten wall case to, the use of case angles may be used. Case angles are pieces of steel or other material of similar structural strength that are formed to a 90° angle, with holes to fasten the case angle to the wall case and to the structural component of the wall surrounding the wall case.

The following describes the procedure when field fabricated and installed case angles are applied.

1.Position case angles around top and sides of wall case at the desired location. Position case angles vertically on each side of wall case to provide a level installation.

2.Mark wall case through holes in case angles. The lowest hole on the sides of the wall case must be a minimum of 2" above the bottom of the case.

3.For RAB71 wall case drill 5/32" diameter holes at locations marked on wall case in Step 2, and assemble angles to wall case using #10 x 1/2" self tapping screws. For RAB77 wall case follow the same procedure except use a #10 x 1/2" bolt, washer and nut to attach case angles to case. Install screws or bolts from outside wall case.

4.Do not drill any holes in bottom of wall case. Do not distort wall case.

5.Do not use case angles for a lintel.

25

Image 25
Contents GE Zoneline packaged terminal air conditioners 2900, 3900 and 5800 Series Control Panel Quick ReferenceZoneline Chassis Nomenclature Power Connection Kits230/208-Volt Line Cord Connection Units Volt Sub-Base and Direct Connected UnitsNewest Innovation from GE Deluxe Dry Air 25 ModelsCooling With Resistance Heat Table of Contents Introduction Zoneline System Optional Accessories of the Zoneline SystemChassis Room Cabinet Wall Case2900 Zoneline Features3900 5800 Features and Benefits Fan-Cycle Switch SmartFan Fan-Only Setting HIGH/LOWCompressor Restart Delay Electronic Temperature LimitingUp-Front Air Filters Easy Clean Air Discharge AreaConcealed Manual Vent Control Corrosion Protection OptionalCooling Temperature Limits Auxiliary Control SwitchesHeating Temperature Limits 3900 SeriesSeries Occupancy Sensor ModeUp resistance heat only Up Occupancy Sensor ConnectedCentral Desk Control CDC Terminal Location and Typical WiringImportant CDC Comments all series applicable Maximum Allowable LengthRemote Thermostat Control Field Wiring TerminalResistance Heat Models RAK806 Universal Control Cover LabelHeat Pump Models Feature Heat Pump Electric HeatRAK148D1 RAK148P1 Type Function Zoneline SeriesThermostat Model Low-Voltage ConductorsBalance Point Heat Pumps and Energy SavingsZoneline Heat Pump Heat Source Logic Heat Pump Operation Zoneline 3900 and 5800 SeriesHeat pump condensate Heat pump defrost Zoneline 3900 and 5800 SeriesAir Distribution Application CommentsWall Case with Chassis Installed DimensionsRAB71A Wall Case RAB77 Wall CaseWall Case RAK204U No receptacle, no wiring, will accept anySub-Base Choice of wall cases is available for the ZonelineGeneral Wall Case Installation DataSub-bases for the 265 volt units Window, Curtain and Panel Wall Construction Architectural Window Louver InstallationMasonry Wall Construction Brick, Frame, Stucco Shingle ConstructionPreparation of the Wall Case for All Types of Construction Installation of Wall Case in Wall OpeningCase Angles Fastening Wall Case Framing for Wall CaseBrick Veneer and Frame Construction Wall Section Detailed Side View Frame and Brick Veneer Installation Cord set connectedRoom Wall Case Installation Cord SET Connected Sealant ALL Four 4 Flanges Ge.com TOP View RAB71/77 Wall Case RAK204 Series SUB-BASE Installation and Electrical DataCondensate Disposal Systems External Drain. See page 36 for internal drain Wall Case with RAD10 Drain KITInternal Drain. See page 35 for external drain New Ducted Installations Ducted InstallationsReplacements of Existing Ducted Units Ducted Application ConsiderationsDucted Application AZ2800/3800 Series RAK Ducted Detailed Side Views AZ2800/3800 SeriesOutdoor Grille Exterior GrillesRAG63 Bittersweet Chocolate Exterior Architectural Treatments Special Outdoor Grilles 230/208-Volt Line-Cord Connected Units Or 277-Volt Unit Installation Permanently Connected Units230/208-Volt Permanently Connected Units 230/208 Volt Sub-Base and Direct Connected UnitsReplacement of Existing Chassis Electrical Wiring Information 2900/3900/5800 SeriesEssential Elements Ordering Overview 230/208-Volt Line Cord Connected Units Maximum Connected LoadVolt Units Heat Pump Performance Data Cooling Performance DataTotal Capacity Btuh Btuh at 80º F D.B. 67º F W.B Model Latent System CapacityNormal Yearly Operating Data Formula for Calculating Operating Costs Using Above DataSchematic Diagram Wiring Diagrams Typical 2900 Series, 208/230-Volt Wiring DiagramSeries, 208/230-Volt Wiring Diagrams Schematic Diagram of AZ39H AC motor model Series, 208/230-Volt Schematic DiagramsSchematic diagram of AZ39H DC motor model Typical 5800 Series Wiring Diagram Typical 5800 Series Schematic DiagramEach shall consist of the following sections and components Suggested Bid Form SpecificationsAlternate specification for molded wall case 265V 30 Amp Receptacles/Sub-BasesGe.com Preliminary SpecificationsKit Number Description Complete Accessory ListGeneral Installation Suggestions Ducted Installation Comments Zoneline warrantyReplacement Installations New InstallationsExterior Grille Color Samples Alphabetical IndexCategory Warm Gray Beige Maple Bittersweet ChocolateGE Consumer & Industrial Century of quality and innovation

3900 Series, 2900 Series, 5800 Series specifications

The GE Monogram series is renowned for its commitment to excellence in kitchen appliances, offering high-end features, superior technology, and outstanding performance. Among the extensive lineup, the 3900 Series, 2900 Series, and 5800 Series stand out for their innovative designs and multifunctionality.

The GE Monogram 3900 Series is a flagship line that combines luxury with practicality. It features stainless steel construction for durability and elegance, along with a commercial-grade appearance that enhances any kitchen setting. One of its key characteristics is the advanced convection cooking technology, which ensures even heat distribution for perfectly cooked dishes. This series often includes options like dual-fuel ranges that provide the precision of a gas cooktop and the reliable performance of an electric oven. Smart technology integration allows users to control their appliances remotely, making meal preparation more convenient.

The 2900 Series presents a compelling option for those seeking high performance in a more compact form factor. This series is characterized by its sleek design and versatile capabilities, making it ideal for urban homes or smaller kitchens. The ovens typically feature multiple cooking modes, including a self-cleaning function and steam cooking options, which preserve nutrients in food while ensuring moist results. Energy efficiency is a priority in this series, with many units designed to reduce consumption without sacrificing power or performance.

On the other hand, the GE Monogram 5800 Series is designed for those who desire the pinnacle of culinary technology. With features like a dual-fuel convection oven and integrated temperature probes, home chefs can achieve restaurant-quality results. The 5800 Series boasts a variety of customizable settings that enable precision cooking, while the built-in smart technologies provide remote monitoring and alerts. The design integrates seamlessly with contemporary kitchens, featuring intuitive touch controls and high-quality finishes that reflect sophistication.

Each of these series embodies GE’s commitment to crafting appliances that inspire both culinary creativity and efficient cooking. With the Monogram brand, customers enjoy a blend of elegance, performance, and smart technology that makes preparing meals an effortless and enjoyable experience. Whether you choose the 3900, 2900, or 5800 Series, you’re investing in an appliance that brings professional-grade quality to your home kitchen.