GE Monogram 3900 Series, 5800 Series, 2900 Series manual General Installation Suggestions

Page 57

General Installation Suggestions

Many times poor or non-existent caulking around the exterior of the wall case results in air infiltration causing the unit to run excessively. One way to check for air infiltration is to look under and around the unit to the outdoors. If you can see light, there is air infiltration. The first floor of a building is where this problem most frequently occurs since caulking the bottom of the wall case may require lying outside in the dirt while working. This has been the cause of many complaints about the “short cycling” of the Freeze Sentinel.

Curtains, furniture or other obstructions interfering with the discharge air circulation will make the unit cycle turn off too soon since the cooled (or heated) discharge air is pulled back into the unit. This results in a room that is not adequately heated or cooled.

Blocking the discharge air on the left side during heating operation can result in the air getting hot enough to distort the plastic room front. If you have a property where this may occur we recommend a “tent card” advising room occupants not to put anything on the unit.

Electrical Wiring Installation

Do not allow the installer to drill a hole in the wall case to run the electrical wiring. If this is done, the wiring will have to be run between the chassis and the edge of the wall case so it can be connected to the unit wiring on the room side of the wall case. When the chassis is removed for servicing or cleaning, the insulation on the wires can be cut and can create a safety hazard.

If the electrical connection on a 230-volt or 208-volt installation is to be made by the line cord plugged into a wall-mounted receptacle, the receptacle should be located in the wall under the case or close to the side of the wall case. This installation makes a much neater appearance than a line cord running a foot or more across the floor. The electrician may want to place the receptacle as far from the unit as possible to save a few feet of wiring without considering how the installation may appear.

Central Desk Control and Remote

Thermostat Wiring

Do not allow the installer to drill a hole in the wall case to run Central Desk Control wiring or remote thermostat wiring to the unit terminals. CDC and remote thermostat wiring is classified as low-voltage wiring and does not have to be run in conduit unless required by local code. CDC and remote thermostat wiring should be run in the walls and exit the wall under the wall case about 2" from the right-hand side. The base pan is designed with a clearance for the line cord and the low-voltage wiring can be run to the chassis in this area also. Wire molding can be used to hold the wiring close to the bottom of the wall case. If a sub-base is used, the wiring can be run through the sub-base, entering the rear and exiting through one of the front panels. When the room cabinet is in place the CDC or remote thermostat wiring is usually not

ge.com

visible to someone standing or sitting in the room. Do not run the low-voltage wiring in conduits with line-voltage wiring or near uninsulated line-voltage wiring since induced current can interrupt the low-voltage controls.

Consult the electrical inspector early in the project, especially if the power to the air conditioner is to be 265 volts, to understand what is required to comply with local electrical codes.

Wall Case/Exterior Grille

When making an installation where the exterior grille is flush with the exterior wall, or part of a custom window/louver section, make sure the installer caulks the wall case to the exterior wall, especially the bottom of the case. Many times the air conditioners are run during construction and the building is not closed. This can result in excessive humidity from the warm humid air entering the building, or from the “drying out” of the building materials. Many problems have been caused by condensate water or rainwater running back into the building where proper caulking has not been done.

Capacity Considerations

A unit that has a greater cooling capacity than required will cool the room quickly but will usually not run long enough under normal operation to adequately dehumidify the room. Most musty odors in rooms are due to excess humidity. Using a smaller capacity unit or using Dry Air 25 units will provide better dehumidification. The largest factor in causing mold and mildew in the room is excess moisture, and a smaller unit running longer or a Dry Air 25 model can remove more moisture. Mold behind wall coverings that do not allow water vapor to pass through — vinyl wallpaper or oil-base paints, for example — is not a problem of excessive moisture in the room, but rather is caused by moisture trapped in the walls.

Using a resistance heater larger than required — using a 5 kW heater when a 3.45 kW heater would suffice for example

may not cost any more in electrical consumption since the larger heater will operate for less time. The “Demand Charge” portion of the utility bill — which is based on the highest electrical load for a period of time — may be a significant portion of the utility bill. Some customers have reported the “Demand Charge” actually being more than the usage charge. In a 100-room property it would be possible for the demand of the 5.0 kW heater versus a 3.45 kW heater to be 155 kW more than the demand charge if the lower wattage heaters were used. Working with the utility companies to understand their method of billing and taking advantage of any rebates they may offer can reduce the utility bill.

Exterior Grilles

When replacing an older unit the existing outdoor grille may need to be changed or modified. Outdoor airflow patterns have changed and this may dictate the need for outdoor grille replacement or modification.

57

Image 57
Contents GE Zoneline packaged terminal air conditioners 2900, 3900 and 5800 Series Control Panel Quick ReferenceZoneline Chassis Nomenclature Power Connection Kits230/208-Volt Line Cord Connection Units Volt Sub-Base and Direct Connected UnitsDeluxe Dry Air 25 Models Newest Innovation from GECooling With Resistance Heat Table of Contents Introduction Zoneline System Optional Accessories of the Zoneline SystemChassis Room Cabinet Wall CaseZoneline Features 29003900 5800 Features and Benefits Fan-Cycle Switch SmartFan Fan-Only Setting HIGH/LOWCompressor Restart Delay Electronic Temperature LimitingUp-Front Air Filters Easy Clean Air Discharge AreaConcealed Manual Vent Control Corrosion Protection OptionalCooling Temperature Limits Auxiliary Control SwitchesHeating Temperature Limits 3900 SeriesSeries Occupancy Sensor ModeUp resistance heat only Up Occupancy Sensor ConnectedCentral Desk Control CDC Terminal Location and Typical WiringImportant CDC Comments all series applicable Maximum Allowable LengthRemote Thermostat Control Field Wiring TerminalResistance Heat Models RAK806 Universal Control Cover LabelFeature Heat Pump Electric Heat Heat Pump ModelsRAK148D1 RAK148P1 Type Function Zoneline SeriesThermostat Model Low-Voltage ConductorsBalance Point Heat Pumps and Energy SavingsZoneline Heat Pump Heat Source Logic Heat Pump Operation Zoneline 3900 and 5800 SeriesHeat pump condensate Heat pump defrost Zoneline 3900 and 5800 SeriesAir Distribution Application CommentsWall Case with Chassis Installed DimensionsRAB71A Wall Case RAB77 Wall CaseWall Case RAK204U No receptacle, no wiring, will accept anySub-Base Choice of wall cases is available for the ZonelineWall Case Installation Data GeneralSub-bases for the 265 volt units Window, Curtain and Panel Wall Construction Architectural Window Louver InstallationMasonry Wall Construction Brick, Frame, Stucco Shingle ConstructionInstallation of Wall Case in Wall Opening Preparation of the Wall Case for All Types of ConstructionCase Angles Framing for Wall Case Fastening Wall CaseBrick Veneer and Frame Construction Wall Section Detailed Side View Frame and Brick Veneer Installation Cord set connectedRoom Wall Case Installation Cord SET Connected Sealant ALL Four 4 Flanges Ge.com TOP View RAB71/77 Wall Case RAK204 Series SUB-BASE Installation and Electrical DataCondensate Disposal Systems External Drain. See page 36 for internal drain Wall Case with RAD10 Drain KITInternal Drain. See page 35 for external drain New Ducted Installations Ducted InstallationsReplacements of Existing Ducted Units Ducted Application ConsiderationsDucted Application AZ2800/3800 Series RAK Ducted Detailed Side Views AZ2800/3800 SeriesExterior Grilles Outdoor GrilleRAG63 Bittersweet Chocolate Exterior Architectural Treatments Special Outdoor Grilles 230/208-Volt Line-Cord Connected Units Or 277-Volt Unit Installation Permanently Connected Units230/208-Volt Permanently Connected Units 230/208 Volt Sub-Base and Direct Connected UnitsElectrical Wiring Information 2900/3900/5800 Series Replacement of Existing ChassisEssential Elements Ordering Overview Maximum Connected Load 230/208-Volt Line Cord Connected UnitsVolt Units Cooling Performance Data Heat Pump Performance DataTotal Capacity Btuh Btuh at 80º F D.B. 67º F W.B Model Latent System CapacityNormal Yearly Operating Data Formula for Calculating Operating Costs Using Above DataSchematic Diagram Wiring Diagrams Typical 2900 Series, 208/230-Volt Wiring DiagramSeries, 208/230-Volt Wiring Diagrams Series, 208/230-Volt Schematic Diagrams Schematic Diagram of AZ39H AC motor modelSchematic diagram of AZ39H DC motor model Typical 5800 Series Wiring Diagram Typical 5800 Series Schematic DiagramEach shall consist of the following sections and components Suggested Bid Form SpecificationsAlternate specification for molded wall case 265V 30 Amp Receptacles/Sub-BasesGe.com Preliminary SpecificationsKit Number Description Complete Accessory ListGeneral Installation Suggestions Ducted Installation Comments Zoneline warrantyReplacement Installations New InstallationsExterior Grille Color Samples Alphabetical IndexCategory Warm Gray Beige Maple Bittersweet ChocolateGE Consumer & Industrial Century of quality and innovation

3900 Series, 2900 Series, 5800 Series specifications

The GE Monogram series is renowned for its commitment to excellence in kitchen appliances, offering high-end features, superior technology, and outstanding performance. Among the extensive lineup, the 3900 Series, 2900 Series, and 5800 Series stand out for their innovative designs and multifunctionality.

The GE Monogram 3900 Series is a flagship line that combines luxury with practicality. It features stainless steel construction for durability and elegance, along with a commercial-grade appearance that enhances any kitchen setting. One of its key characteristics is the advanced convection cooking technology, which ensures even heat distribution for perfectly cooked dishes. This series often includes options like dual-fuel ranges that provide the precision of a gas cooktop and the reliable performance of an electric oven. Smart technology integration allows users to control their appliances remotely, making meal preparation more convenient.

The 2900 Series presents a compelling option for those seeking high performance in a more compact form factor. This series is characterized by its sleek design and versatile capabilities, making it ideal for urban homes or smaller kitchens. The ovens typically feature multiple cooking modes, including a self-cleaning function and steam cooking options, which preserve nutrients in food while ensuring moist results. Energy efficiency is a priority in this series, with many units designed to reduce consumption without sacrificing power or performance.

On the other hand, the GE Monogram 5800 Series is designed for those who desire the pinnacle of culinary technology. With features like a dual-fuel convection oven and integrated temperature probes, home chefs can achieve restaurant-quality results. The 5800 Series boasts a variety of customizable settings that enable precision cooking, while the built-in smart technologies provide remote monitoring and alerts. The design integrates seamlessly with contemporary kitchens, featuring intuitive touch controls and high-quality finishes that reflect sophistication.

Each of these series embodies GE’s commitment to crafting appliances that inspire both culinary creativity and efficient cooking. With the Monogram brand, customers enjoy a blend of elegance, performance, and smart technology that makes preparing meals an effortless and enjoyable experience. Whether you choose the 3900, 2900, or 5800 Series, you’re investing in an appliance that brings professional-grade quality to your home kitchen.