3.3.4 Configure Relays, Horn & Strobe Submenu

There is a list of parameters for each relay in the system. The left and right cursor keys can be used to move from one relay, horn or strobe to another. Doing so always goes to the first (summary) display. The up and down keys will scroll through the parameters for the particular relay, horn or strobe.

3.3.4.1 Relay Summary

R e l a y

1 N o r m . O f f

D e l a y

O n , M i n . O n

Figure 3-29 Relay Summary

This display example shows that Relay 1 is configured to operate Normally Off, with a turn on delay and a minimum on time.

Notice that the relay number, 1 in this example, is underlined. This indicates that the digit keys can be used to jump to a particular relay, horn or strobe. The relays are numbers 1, 2 and 3; the horn is number 4 and the strobe is 5.

3.3.4.2 Relay Mode

R e l a y 1 N o r m . O f f

M o d e : 2

Figure 3-30 Relay Mode

This display example shows that relay 1 is configured to operate in the Normally Off mode. The relay modes are:

– 1 ALARM

2 Normally Off (default)

3 Normally On

Relay mode 1 is a special case. This mode is only available on relay 1 and dedicates the relay to function as an alarm signal to a subsequent alarm or monitoring panel. This mode forces the relay to normally off mode with no turn on delay or minimum on time. See section 3.1.4 for more detail regarding alarms

Fail Safe operation can be implemented by configuring a relay to operate Normally On, and wiring the circuit using the NC (normally closed) contact. In this way, if the control panel looses power the relay will turn on the controlled device if it still has power.

3.3.4.3 Relay Turn On Delay

R e l a y 1 D e l a y

O n

( m m : s s ) 0 1 : 0 0

 

Figure 3-31 Turn On Delay

The default turn on delay is one minute and the maximum allowed value is fifteen minutes. The value is entered in two groups, 2 digits for the minutes and then 2 digits for the seconds. A leading zero must be entered for each group if applicable.

3.3.4.4 Relay Minimum On Time

R e l a y 1 ( m m : s s )

M i n . O n 0 1 : 0 0

Figure 3-32 Minimum on time

The default minimum on time is one minute and the maximum allowed value is fifteen minutes.

Revision 0.07

26

Image 26
Contents DVP-120 Installation & Operating Instructions List of Figures Normal System Display List of Tables Compatible Macurco Transducers FeaturesGeneral Information System Wiring Diagram DVP-120 Internal View Return Instructions Specifications1Warranty General Wiring Information Mounting the DVP-120Main power Connection Remote Sensor ConnectionSensor Connectors Channel and Pin Assignments Relay Connector Relay ConnectionHorn & Strobe signals and Connector Assignments Horn & Strobe ConnectionInterfacing Macurco Sensors P 1 2 R m u p Initial Operating ModeDVP 1 2 0 V e r 1 Status Light DisplayUser Interface Keypad layoutO w S e n s o r Alarm Status DisplayMO N 1 0 2 3 R 1 C O S E N S O R 0Trouble Status Display R 5 M I N U T E SWA R N I N G F O R 1 R 1 5 M I N U T E S Zone Signal DisplayR 8 H O U R S Ventilation controlSetting the System Configuration V e C o n f i g . ? 0 = N O , 1 = Y E SM e 0 1 5 Y T u e s d a y Configure System SubmenuM e 2 2 5 Y T u e s d a y M e 1 6 5 Y T u e s d a yO a d D e Fault C o n f i g u r a t i o n M e 2 2 5 Y 2 T u e s d a yS s w o r d O n g P a s s w o r dN s o N s o r Alarm 0 p p mConfigure Sensors Submenu N s P eN s o r 0 R n i n g 5 0 p p m N s o r N g e 0 p p mL a y 1 N o r m . O f f D e Configure Relays, Horn & Strobe SubmenuL a y O r m . O f f M i n . O n L a y 1 D e l a y S s 0 1 0R n R m . O f f D e Configure Horn SubmenuR n R m . O f f L a R n L a y S sR o b e R m . O f f D e Configure Strobe SubmenuR o b e 5 N o r m . O f f L a y O n R o b e S sO u p N s o r T y p e Configure Zones SubmenuN e 1 C o n t r o l s R 2 R 3 H 4 S R o u p 1 T i m e d O p T i m e 1 8 0 R o u p D a y s I m e d W e e k d a y sR o u p M e d A r t T i m e R o u p 1 N O N s o r s 0 2 , 0 4 , 1O u p D e 2 V o t i n g R o u p S i n g P mR o u p L l i n g P m O u p U mAlarm S i g n a l s R n 2 I n t e r m i t Alarm S i g n a l s Z z , H o r n , S t r o b eAlarm S i g n a l s Z z 2 I n t e r m i t Configure Signals SubmenuR n G S i g n a l s Z z M S i g n a l sB e 1 C o n t i n R n S i g n a l s Z zO u b l e B u z z G n a l s T r i p l e R o b eO u b l e S i g n a l s Z z O u b l e S i g n a l s R n63 Strobe Trouble Signal O u b S i g n a l s R o b eInput Channel Trouble Timed ventilation problemSystem Status Light Flashing Internal Controller Board TroubleLCD Display unreadable No PowerAfter a power failure Keypad does not respond LCD shows Keys Locked

DVP-120 specifications

The Macurco DVP-120 is an advanced gas detection sensor that is designed for various commercial and industrial applications. It provides real-time monitoring of hazardous gases, ensuring safety in environments where gas leaks can pose significant risks. The device is built with high-precision technology, allowing for accurate detection of gases such as carbon monoxide, methane, propane, and others.

One of the standout features of the DVP-120 is its dual-channel sensing capabilities. This allows the unit to simultaneously monitor two different gas types, which significantly enhances its versatility in diverse settings. Users can customize the device to target specific gases relevant to their operations, making it a highly adaptable tool for a variety of workplaces.

The DVP-120 utilizes state-of-the-art electrochemical sensors that deliver reliable and fast response times, allowing businesses to act quickly in the event of a gas leak. These sensors are known for their long lifespan and low maintenance requirements, thus reducing the total cost of ownership over time. Additionally, the sensor head is designed for easy replacement, further simplifying maintenance for users.

Another notable characteristic of the DVP-120 is its user-friendly interface. The device features an intuitive LCD display that provides clear readings, making it easy for operators to monitor gas levels at a glance. The display also includes alarm indicators, ensuring that users are alerted promptly in an emergency situation. The alarms can be configured with different sound levels and visual alerts to suit the needs of the environment.

Moreover, the Macurco DVP-120 is equipped with advanced connectivity options, including wired and wireless communication capabilities. This allows the device to be integrated into existing monitoring systems or networks, ensuring seamless operation alongside other safety equipment.

In terms of durability, the DVP-120 is built to withstand harsh environmental conditions. Its rugged housing is resistant to dust and moisture, making it suitable for use in industrial settings where exposure to various elements is a concern.

Overall, the Macurco DVP-120 is a comprehensive solution for gas detection and monitoring. With its combination of advanced sensing technology, user-friendly design, and robust construction, it stands out as an essential tool for ensuring the safety and efficiency of operations across various industries.