Typical Multiple 3M™ Macurco™ GD-6 Combustible Gas Detector Installation

INSTALLATION NOTES

1.One sensor per 900 square feet (approximately).

2.If the gas used is natural gas (methane) or Hydrogen (H2) mount the 3M™ Macurco™ GD-6 Combustible Gas Detector high on a wall about one foot down from the ceiling. If the gas used is propane (LP), mount the 3M™ Macurco™ GD-6 Combustible Gas Detector on a wall or column one foot above the floor.

3.See applicable building code for fan size vs air changes per periods of time.

4.Make sure there are air inlets to provide adequate air flow throughout the building.

5.3M™ Macurco™ GD-6 Combustible Gas Detector fan relays are dry contact & can switch up to 240V.

6.Several fan relays (starters) may be used. Match the relays to the fan size.

Typical Connection to Alarm Control Panel

1.3M™ Macurco™ GD-6 Combustible Gas Detector can be used with 12VDC or 24VDC N.O. (fire) panels.

2.Alarm panel provides battery backed up power to 3M™ Macurco™ GD-6 Combustible Gas Detector.

3.3M™ Macurco™ GD-6 Combustible Gas Detector dry contact fan relay can use panel power or fan power. Check ratings on panel & fan.

4.Match fan relay contacts to fan size, and coil voltage to power source.

5.Alarm Control Panels are available with many features & can control other devices such as smoke detectors, fire detectors & burglar alarms.

8

9

Image 6
Contents Macurco Combustible Gas Detector, Controller and Transducer Table of Contents General Safety Information USE Instructions and LimitationsInstallation and Operating Instructions FeaturesSpecifications General InformationInstallation LELTypical Connection to Alarm Control Panel Default Fan Relay Delay setting is 3 minutes Power UpDefault Configuration Factory Settings Default Alarm Relay Configuration is Normally OpenSelecting Alarm Relay Setting ArS Selecting Default Configuration dEFSelecting Power Up Test Option PUt Selecting Alarm Relay Configuration ArcMaintenance Manual Operation Test Contents of the FCKOperation Test Combustible Gas TestGas Testing Testing the Fan Relay Testing the Alarm RelayTesting the 4-20mA current loop Zero the Sensor Field Calibration ProcedureQuick Gas Test CalibrationUnited States, contact 3M Fixed GAS Detection Products Limited WarrantyFor More Information For other 3M productsPage 3M Occupational Health Environmental Safety Division Match Colors Assumes full responsibility for its correctness