Page 5

2 Maintenance schedule

Service technician

(see the following pages for instructions)

 

General:

 

 

 

 

• Address reported problems

 

• Inspect interior; clean and vacuum if

 

necessary;

 

 

 

• Clean condensate trap and fill with fresh

 

water

 

 

 

 

• Check

for leaks (water, gas, flue,

 

condensate)

 

 

UP-

• Verify flue and air passage ways in good

condition and sealed tight

 

START

• Check

system

water

pressure/system

piping/expansion tank

 

 

 

 

• Check control settings

 

ANNUAL

• Check

ignition

and

flame sense

electrodes (sand off any deposits; clean

and reposition)

 

 

• Check wiring and connections

 

• Perform start-up checkout and

 

performance verification per Section 10.

 

• Flame inspection (stable, uniform)

 

• Flame signal (at least 10 microamps at

 

high fire)

 

 

 

• Clean the heat exchanger if flue

 

temperature is more than 54°F (30°C)

 

above return water temperature.

If combustion or performance indicate need:

Clean heat exchanger

Remove and clean burner using compressed air only

Clean the blower wheel

Outdoor Knight XL User’s Information Manual

Owner maintenance

(see the Outdoor Knight XL User’s Information

Manual for instructions)

Daily

• Check boiler area

• Check pressure/temperature

 

 

gauge

 

 

 

• Check air and vent termination

Monthly

screens

 

 

• Check relief valve

 

• Check condensate drain system

 

 

 

• Test low water cutoff (if used)

Periodically

• Reset button (low water cutoff)

 

 

 

Every

• Check boiler piping (gas and

water) for leaks

6 months

• Operate relief valve

 

 

 

End

• Shut boiler down (unless boiler

of season

used for domestic hot water)

months

 

 

 

￿WARNING

Follow the maintenance procedures given throughout this manual. Failure to perform the service and maintenance or follow the directions in this manual could result in damage to the boiler or system, resulting in severe personal injury, death, or substantial property damage.

5

Image 5
Contents Outdoor Knight XL User’s Information Manual Models 400 Contents Please read before proceeding Boiler service and maintenanceAreas likely to have contaminants Prevent combustion air contaminationProducts to avoid Owner maintenance Maintenance schedule Service technicianFill condensate trap with water Maintenance scheduleCondensate disposal 1Condensate TrapCheck air vents Operating instructions For Your Safety Read Before OperatingUser InstallerSmart System control module Manual and auto reset high limit set points Temperature UnitsNight Setback Override Space heating SH1, SH2, SH3 and tank set pointsCall for Heat Information Dial Function Outdoor Knight XL User’s Information Manual