2 Maintenance schedule
Service technician
(see the following pages for instructions)
| General: |
|
|
| |
| • Address reported problems | ||||
| • Inspect interior; clean and vacuum if | ||||
| necessary; |
|
| ||
| • Clean condensate trap and fill with fresh | ||||
| water |
|
|
| |
| • Check | for leaks (water, gas, flue, | |||
| condensate) |
|
| ||
UP- | • Verify flue and air passage ways in good | ||||
condition and sealed tight | |||||
| |||||
START | • Check | system | water | pressure/system | |
piping/expansion tank |
| ||||
|
| ||||
| • Check control settings |
| |||
ANNUAL | • Check | ignition | and | flame sense | |
electrodes (sand off any deposits; clean | |||||
and reposition) |
|
| |||
• Check wiring and connections | |||||
| • Perform | ||||
| performance verification per Section 10. | ||||
| • Flame inspection (stable, uniform) | ||||
| • Flame signal (at least 10 microamps at | ||||
| high fire) |
|
| ||
| • Clean the heat exchanger if flue | ||||
| temperature is more than 54°F (30°C) | ||||
| above return water temperature. |
If combustion or performance indicate need:
•Clean heat exchanger
•Remove and clean burner using compressed air only
•Clean the blower wheel
Outdoor Knight XL User’s Information Manual
Owner maintenance
(see the Outdoor Knight XL User’s Information
Manual for instructions)
Daily | • Check boiler area | |
• Check pressure/temperature | ||
| ||
| gauge | |
|
| |
| • Check air and vent termination | |
Monthly | screens | |
| ||
| • Check relief valve | |
| • Check condensate drain system | |
|
| |
| • Test low water cutoff (if used) | |
Periodically | • Reset button (low water cutoff) | |
| ||
|
| |
Every | • Check boiler piping (gas and | |
water) for leaks | ||
6 months | • Operate relief valve | |
| ||
|
| |
End | • Shut boiler down (unless boiler | |
of season | ||
used for domestic hot water) | ||
months | ||
| ||
|
|