2 Maintenance schedule
Maintenance procedures
Boiler must be serviced and maintained
Outdoor Knight XL User’s Information Manual
Read the list of potential materials listed in Table 1A on page 4 of this manual.
Check pressure/temperature gauge
WARNING
The boiler must be inspected and started annually at the beginning of the heating season by a qualified service technician. In addition, the maintenance and care of the boiler designated on page 5 of this manual and explained on pages 6 through 8 must be performed to assure maximum boiler efficiency and reliability. Failure to service and maintain the boiler and system could result in equipment failure, causing possible
1.Make sure the pressure reading on the boiler pressure/ temperature gauge does not exceed 24 psi (165.5 kPa). Higher pressure may indicate a problem with the expansion tank.
2.Contact a qualified service technician if problem persists.
Check all piping for leaks
NOTICE
severe personal injury, death, or substantial property damage.
The following information provides detailed instructions for completing the maintenance items listed in the maintenance schedule on page 5. In addition to this maintenance,
WARNING
Eliminate all system or boiler leaks. Continual fresh makeup water will reduce boiler life. Minerals can build up in sections, reducing heat transfer, overheating heat exchanger, and causing heat exchanger failure. Leaking water may also cause severe property damage.
the boiler must be serviced and started up at the beginning of each heating season by a qualified service technician.
1. | Inspect all water and gas piping and verify to be leak |
| free. |
2. | Look for signs of leaking lines and correct any problems |
Check boiler area
found. |
WARNING
To prevent potential of severe personal injury, death, or substantial property damage, eliminate all materials discussed below from the boiler vicinity and the vicinity of the boiler combustion air inlet. If contaminants are found:
Remove products immediately from the area. If they have been there for an extended period, call a qualified service technician to inspect the boiler for possible damage from acid corrosion.
3. Contact a qualified service technician if problem |
persists. |
Check relief valve
1.Inspect the boiler relief valve and the relief valve discharge pipe for signs of weeping or leakage.
2.If the relief valve often weeps, the expansion tank may not be working properly. Immediately contact your qualified service technician to inspect the boiler and system.
If products cannot be removed, immediately call a qualified service technician to
1.Combustible/flammable materials
2.Air contaminants
6
Check condensate drain system
1.Inspect the condensate drain line, condensate PVC fittings and condensate trap.
Fill condensate trap with water
1.Remove the PVC cap retaining screw from the PVC cap (FIG.
2.Remove the 2" PVC cap with the switch located at the top of the trap (FIG.
3.Fill with fresh water until the water begins to pour out of the drain.
4.Replace the cap. Press the cap onto the trap until the cap makes contact with the drain.
5.Replace the retaining screw.