AHE Series 4 Direct Vent Wall-Mounted Boilers — User’s Information Manual

User maintenance procedures continued

Monthly .....................

Main burner flames

1.See Figure 4. Remove burner input plenum cover plate “A”.

2.Visually inspect burner flames:

Proper main burner flame (see Figure 5):

a.Yellow-orange streaks may appear (caused by dust).

Improper main burner flame:

a.Overfired — Large flames.

b.Underfired — Small flames.

c.Lack of primary air — Yellow tipping on flames (sooting will occur).

Figure 4

Periodically ..........

Test low water cutoff

Test the low water cutoff periodically during the heating season, following the low water cutoff manufacturer’s instructions.

Clean vent termination and air intake screens

1.Remove all lint and debris from both the boiler air intake screen and the flue discharge screen.

2.The boiler control module will sense blockage of the air intake or flue and lockout if the blockage is excessive. It will signal by flashing the appropriate indicator lights on the control board.

3.If removing the debris does not allow the boiler to operate correctly afterwards, contact your qualified service technician to inspect the boiler and vent/ air systems.

89301

Figure 5 Main burner flame, typical

Transparent blue flame

Inner flame

26024

Part number 550-141-893/0800

7

 

Image 7
Contents AHE SERIES User’s Information ManualDirect Vent Wall-Mounted Boilers Stop!! - Read before proceeding - Important safety information ContentsPlease read this page first Hazard definitionsBoiler water When servicing boilerStop!! - Read before proceeding Boiler operationService technician Boiler maintenanceBoiler service and maintenance Maintenance scheduleComponent information User maintenance proceduresBoiler must be serviced and maintained DailyCheck venting system User maintenance procedures continuedMonthly Check boiler pipingTest low water cutoff Clean vent termination and air intake screensPeriodically Main burner flamesOperate relief valve Shut down procedureEvery 6 months End of seasonOPERATING INSTRUCTIONS FOR YOUR SAFETY READ BEFORE OPERATINGOperating instructions Robertshaw 7200 gas valveHoneywell VR8205 and White-Rodgers 36E gas valves Operating instructions - Robertshaw 7200 gas valvePossible Corrections Common problems and solutionsSymptom Common CausesLimited Warranty for cast iron sections Weil-McLain Limited Warranty forCOMMERCIAL WARRANTY-Limited 10-Year Limited Warranty for Cast Iron Boilers