Lochinvar 45,000 - 260,000 BTU/HR service manual Check Expansion Tank, Check Relief Valve

Page 45

Installation & Service Manual

7Maintenance (continued)

Check Expansion Tank

1.Expansion tanks provide space for water to move in and out as the heating system water expands due to temperature increase or contracts as the water cools. Tanks may be open, closed, diaphragm or bladder type. See Section 4 - Water Connections for suggested best location of expansion tanks and air eliminators.

Check Relief Valve

1.Inspect the relief valve and lift the lever to verify flow. Before operating any relief valve, ensure that it is piped with its discharge in a safe area to avoid severe scald potential. Read Section 4 - Water Connections before proceeding further.

WARNING

Safety relief valves should be re-inspected

AT LEAST ONCE EVERY THREE

 

YEARS, by a licensed plumbing contractor

 

or authorized inspection agency, to ensure

 

that the product has not been affected by

 

corrosive water conditions and to ensure

 

that the valve and discharge line have not

 

been altered or tampered with illegally.

 

Certain naturally occurring

conditions

 

may corrode the valve or its components

 

over time, rendering the valve inoperative.

 

Such conditions are not detectable unless

 

the valve and its components are

 

physically removed and inspected. This

 

inspection must only be conducted by a

 

plumbing contractor or

authorized

 

inspection agency – not by the owner.

 

Failure to re-inspect the boiler relief valve

 

as directed could result in unsafe pressure

 

buildup, which can result in severe

 

personal injury, death, or substantial

 

property damage.

 

WARNING Following installation, the valve lever must be operated AT LEAST ONCE A YEAR to

ensure that waterways are clear. Certain naturally occurring mineral deposits may adhere to the valve, rendering it inoperative. When manually operating the lever, water will discharge and precautions must be taken to avoid contact with hot water and to avoid water damage. Before operating lever, check to see that a discharge line is connected to this valve directing the flow of hot water from the valve to a proper place of disposal. Otherwise severe personal injury may result. If no water flows, valve is inoperative. Shut down the appliance until a new relief valve has been installed.

2.After following the above warning directions, if the relief valve weeps or will not seat properly, replace the relief valve. Ensure that the reason for relief valve weeping is the valve and not over-pressurization of the system due to expansion tank waterlogging or undersizing.

45

Image 45
Contents Models 45,000 260,000 Btu/hr Contents Please read before proceeding WarrantyCodes Ratings Solution Boiler =B=R RatingTemperature and pressure gauge Solution How it worksSolution How it works Solution How it works Location of unit Determine boiler location3Combustion Air Direct from Outside 6Combustion Air from Outside Single Opening Minimum Recommended Combustion AIR Supply to Equipment Room Venting Conventional Negative Draft Venting SystemVent Pipe Sizes Venting Less from Ridge From Parapet Wall Vertical Vent Termination ClearancesSidewall Venting Negative Draft Masonry Chimney InstallationVent Materials Fan Assisted Venting7Vent Damper and Vent Damper Terminal Block Automatic Vent DamperGas connections Gas Supply Gas Pressure TestGas Connection Gas Piping Install Piping to Control2Wrench Gas Manifold Pressure Adjustment Procedure4Gas Supply Pressure Checking Gas Supply PressureCombination Gas Valves Venting of Combination Gas ValvesTwo Stage Burner Control System Water Flow Switch if equipped Water connectionsRelief Valve Low Water Cutoff if equipped Typical Heating Boiler InstallationsMinimum Required Flow For Heating Boiler General Plumbing RulesPiping of the Boiler System System Temperature Rise ChartHeat Exchanger Pressure Drop Chart Water ConnectionsCirculator Pump Requirements Circulator Pump Specifications Primary/Secondary Boiler PipingCirculator Pump Operation Low Temperature Bypass Requirements Full Flow ApplicationBoiler Flow Rates Make UP Water Primary / Secondary PipingMake UP Water 6Multiple Boilers Zoned with Circulators From System Full System Flow8Single Boiler Full System Flow with Low Temperature Bypass Boiler Operating Temperature Control Terminal Strip WiringElectrical connections Auxiliary Device Connection to Terminal StripAMP Draw Data Temperature AdjustmentMaximum Set Point Determination Maximum SET Point DeterminationOutdoor Air Temperature Sensor Wiring of Remote SensorsInstallation of Remote Sensors Additional Temperature Controls Outdoor Air Reset Option7Blocked Vent Switch Location Blocked Vent and Flame Roll-Out / Flame Interlock SwitchStart-up Pre-start ChecklistInitial Start-up Lighting Instructions for Spark Ignition Pilot ModelsSafety Shutoff Test for Spark Ignition Pilot System Operating InstructionsTo Turn Off Gas to Appliance Freeze Protection Intermittent Pilot Spark Ignition SystemWater Treatment Ignition and Control TimingsService technician Maintenance Maintenance and annual startupOwner maintenance See the User’s Information Manual for instructionsMaintenance Check Relief Valve Check Expansion TankCheck Control Settings Check All WiringHeat Exchanger / Burner Access Perform Start-up and ChecksBreathing Fresh air Inspection and CleaningInspection of Heat Exchanger Waterways Review with ownerGas Train and Controls Water Circulating PumpTroubleshooting Guide M9 Solution Boilers TroubleshootingSchematic Diagram M9 Unit DiagramsWiring Diagram M9 Unit 45,000 260,000 Btu/hr Models 45,000 260,000 Btu/hr ModelsPage Revision a ECO #C03746 initial release SBR-I-S Rev a

45,000 - 260,000 BTU/HR specifications

Lochinvar, a leader in high-efficiency heating solutions, presents the Lochinvar line of boilers, specifically the Lochinvar 45,000 - 260,000 BTU/HR models. These boilers are designed to meet a wide range of heating demands, making them ideal for residential and commercial applications alike.

One of the key features of the Lochinvar boilers is their impressive efficiency rating. Utilizing advanced condensing technology, these units can achieve efficiencies of up to 96% AFUE (Annual Fuel Utilization Efficiency). This high efficiency not only reduces fuel consumption but also lowers utility bills, making it a cost-effective solution for heating needs.

The Lochinvar boilers are equipped with a powerful heat exchanger constructed from durable stainless steel. This design not only maximizes heat transfer but also enhances the longevity of the unit. By preventing corrosion and minimizing maintenance requirements, the stainless steel heat exchanger ensures that the boiler operates at peak performance for years.

Another significant aspect of the Lochinvar boilers is their modulating burner system. This technology allows the boiler to adjust its output based on demand, ensuring that it only uses the energy necessary to maintain the desired temperature. This feature not only improves efficiency but also contributes to a more comfortable indoor environment by minimizing temperature fluctuations.

The Lochinvar series also showcases a user-friendly control interface. The advanced LCD display allows for easy monitoring and adjustment of system settings. Connectivity options are often included, providing the ability to integrate with modern building management systems for enhanced control and diagnostics.

Safety features abound in the Lochinvar models, which include built-in safeguards such as temperature and pressure relief valves, flame detection systems, and modulation cut-off to protect against overheating and other hazardous conditions.

Moreover, these boilers are designed for easy installation and maintenance. Compact dimensions and lightweight design facilitate straightforward setup, even in tight spaces. Additionally, users can take advantage of the unit’s self-diagnostic capabilities to simplify troubleshooting and reduce downtime.

In conclusion, the Lochinvar 45,000 - 260,000 BTU/HR boilers represent a pinnacle of innovation in heating technology. With high efficiency, advanced control systems, durable components, and safety features, they stand out as reliable and effective solutions for a variety of heating applications, ensuring comfort and efficiency in any environment.