11. Installing The Appliance
The appliance is only suitable for fitting to a sealed system.
11.1 FLUE OPTIONS.
The standard flue length is from 127mm to 350mm measured from the appliance casing to the outer wall.
Extension flue kits, a vertical
Horizontal balanced flue:
a)From 127mm to 2500mm straight flue.
b)From 127mm to 1750mm when a 90¡ flue bend is required.
c)From 127mm to 1000mm when two 90¡ flue bends are required.
A 90¡ flue bend is equivalent to 750mm of straight flue. A 45¡ flue bend is equivalent to half a 90¡ bend.
Refer to Figs. 21 and 22 to determine whether extension kits, 90¡ flue bend, 45¡ flue bend, or adapters are required.
The maximum number of 90¡ flue bends allowed is two.
Flue components
1.Turret clamping ring.
2.Flue turret assembly
3.Flue terminal assembly
4.Extension air duct
5.Extension flue duct
6.
7.
8.Vertical flue adapter
The flue must be installed as specified in BS 5440 Part 1.
NOTE: READ THIS SECTION FULLY BEFORE COMMENCING INSTALLATION
11.2 GENERAL FITTING.
Check that the appliance carton contains:- Appliance, Installers Instruction Pack, Appliance Wall Plate, Users Information Pack, Installer Hardware Pack and an appliance template.
Check that the position chosen for the appliance is in accordance with the instructions given in Sections 4 and 5.
Hold the template to the wall. Check that the template is horizontal. See Fig. 10.
Mark the position of the fixing holes and the position of the flue hole centre line onto the wall. See Fig. 10.
Fig. 10. Appliance mounting plate and flue position.
Mounting wall |
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
| Rear flue hole |
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
| 110mm dia. |
|
|
|
|
|
|
|
|
|
|
|
| (150mm dia. for |
|
|
|
|
|
|
|
|
|
| |||
| 166mm |
|
|
|
|
|
|
| ||||
|
|
|
|
|
| internal fixing) | ||||||
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
| 60mm |
|
|
| |||||
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
Rear flue hole 110mm dia.
Side wall (150mm dia. for internal fixing)
Fixing holes Mounting (alternatives) plate
Appliance casing
740mm |
| Rear flue position |
400mm
Mounting wall
Mounting plate
222mm
Appliance casing
Side flue position
Fig. 11. Marking out the side flue position.
Side Flue Ð Extend the flue hole centre line from Fig. 11 along the appropriate wall. Check that it remains horizontal and mark a horizontal line. Measure 222mm from the junction of the walls and mark a vertical line which will then give the position of the
Mounting wall
Side flue hole 110mm dia. (150mm dia. for internal fixing)
222mm |
|
|
| |
|
| |||
Side |
|
|
|
|
wall |
|
| 166mm | |
|
|
| ||
|
|
|
|
flue hole.
Drill the two fixing holes 60mm deep for No. 12 size plugs. Cut the flue duct hole at 110mm diameter (150mm dia. for internal fitting). Ensure that the hole is horizontal through the wall. Fit the wall mounting bracket.
Drill the two fixing holes 60mm deep for No. 12 size plugs. For the boiler retaining screws.
Fix the wall plate and check that it is horizontal before tightening the 2 screws.
Hang the appliance on the wall plate and screw the appliance to the wall using the screws provided.
11