Crown Boiler TWZ100, TWZ200, TWZ090, TWZ125, TWZ065, TWZ175, TWZ150, TWZ120, TWZ075 2423, Boiler Model

Page 24

TABLE 3a: BECKETT BURNER CONFIGURATION AND SETUP DATA

BOILER MODEL

TWZ065

TWZ075

TWZ100

TWZ090

TWZ125

TWZ150

TWZ120

TWZ175

TWZ200

KSZ065

KSZ075

KSZ100

KSZ090

KSZ125

KSZ150

KSZ120

KSZ175

KSZ200

 

BURNER MODEL

AFG

AFG

AFG

AFG

AFG

AFG

AFG

AFG

AFG

AIR TUBE COMBO.

70MMAQ

70MMAQ

70MMAQ

70MMAQ

70MDAQ

70MDAQ

70MLAQ

70MLAQ

70MLAQ

HEAD TYPE

L1

L1

L1

L1

V1

V1

V1

V1

V1

STATIC PLATE

3 3/8

3 3/8

3 3/8

3 3/8

2 3/4

2 3/4

NONE

NONE

NONE

LOW FIRING RATE

BECKETT

BECKETT

NONE

NONE

NONE

NONE

NONE

NONE

NONE

BAFFLE

#3708

#3708

 

 

 

 

 

 

 

INSERTION LENGTH

2 1/4

2 1/4

2 1/4

2 1/4

2 1/4

2 1/4

2 1/4

2 1/4

2 1/4

PITCH ANGLE

2

2

2

2

2

2

2

2

2

STANDARD

HAGO

HAGO

HAGO

DEL.

HAGO

HAGO

HAGO

HAGO

HAGO

NOZZLE

0.55/60B

0.65/60B

0.85/60B

0.75/60B

1.00/60B

1.25/60B

0.90/60B

1.35/45B

1.50/45B

ALTERNATE

DEL.

DEL.

DEL.

HAGO

DEL.

DEL.

DEL.

DEL.

DEL.

NOZZLE

0.55/60W

0.65/60W

0.85/60W

0.75/60B

1.00/60B

1.25/60B

0.90/60B

1.35/45B

1.50/45B

PUMP PRESS (psi)

140

140

140

140

140

140

175

175

175

HEAD SETTING

NA

NA

NA

NA

0

0

0

3

4

STARTING:

 

 

 

 

 

 

 

 

 

SHUTTER SETTING

1

10

5

7

10

10

8

6

8

BAND SETTING

1

2

2

0

0.5

6

1

6

4

DRAFT OVER FIRE

-0.02

-0.02

-0.02

-0.02

-0.02

-0.02

-0.02

-0.02

-0.02

(in w.c.)

 

 

 

 

 

 

 

 

 

MAX. SMOKE

#1

#1

#1

#1

#1

#1

#1

#1

#1

(bacharach scale)

 

 

 

 

 

 

 

 

 

FLUE CO2 (%)

 

 

 

 

 

 

 

 

 

MIN.

11.0

11.0

11.0

11.0

11.0

11.0

11.0

11.0

11.0

MAX

12.5

12.5

12.5

12.5

12.5

12.5

12.5

12.5

12.5

PREPURGE

 

 

15 SECONDS

 

 

 

None

 

IGNITION MODE

 

 

 

INTERUPTED

 

 

 

TABLE 3b: CARLIN BURNER CONFIGURATION AND SETUP DATA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TWZ065

TWZ075

TWZ100

TWZ090

TWZ125

TWZ150

TWZ120

TWZ175

TWZ200

 

 

 

 

 

 

 

 

 

 

BURNER MODEL

EZ-1HP

EZ-1HP

EZ-1HP

EZ-1HP

EZ-1HP

EZ-1HP

EZ-1HP

EZ-2HP

 

STANDARD

DEL.

HAGO

HAGO

DEL.

DEL.

HAGO

HAGO

DEL.

 

NOZZLE

0.55/70B

0.60/60ES

0.85/60B

0.75/60A

1.00/60A

1.25/60B

1.00/60B

1.50/60A

 

PUMP PRESS (psi)

150

150

150

150

150

150

150

150

 

HEAD BAR

0.50

0.60-0.65

0.85-1.00

0.75

0.85-1.00

1.10-1.25

0.85-1.00

1.50

 

STARTING

 

 

 

 

 

 

 

 

 

BAND SETTING

0.55

0.60

0.75

0.75

1.00-1.10

1.25-1.35

0.90

1.75

 

DRAFT OVER FIRE

-0.02

-0.02

-0.02

-0.02

-0.02

-0.02

-0.02

-0.02

 

(in w.c.)

 

 

 

 

 

 

 

 

 

 

MAX. SMOKE

#1

#1

#1

#1

#1

#1

#1

#1

 

(bacharach scale)

 

 

 

 

 

 

 

 

 

 

FLUE CO2 (%)

 

 

 

 

 

 

 

 

 

MIN.

11.0

11.0

11.0

11.0

11.0

11.0

11.0

11.0

 

 

 

 

 

 

 

 

 

 

 

MAX

12.5

12.5

12.5

12.5

12.5

12.5

12.5

12.5

 

PREPURGE

 

 

 

 

NONE

 

 

 

 

IGNITION MODE

 

 

 

INTERRUPTED

 

 

 

2423

Image 24
Contents TWZ Series Table of Contents II SpecificationsProduct Description III Before Installing General SpecificationsIV Locating the Boiler Frontview Side View Air for Combustion and Ventilation For Buildings of Other than Unusually Tight ConstructionBoiler Installed in Confined Space ALL AIR from Inside For Buildings of Unusually Tight ConstructionALL AIR from Outdoors Ventilated Crawl Space and Attic ALL AIR from OUTDOORS, Using VI Venting 109Minimum Recommended Breeching Chimneysize 1110VII System Piping StandardPiping1312 Piping for Special Situations 1413Isolation of Boiler from System Viii Tankless Heater Piping 1615IX Fuel Line Piping 17161817 ONE-PIPE Lift System1918 TWO-PIPE Gravity Feed SystemWiring Single Zone WiringWiring Variations 2019Wiring DIAGRAM, Single Heating Zone only XI Start-up and Checkout 22212223 2423 Boiler ModelXII Service and Maintenance 25242625 Avoid Breathing Fiber Particulates and Dust 27262827 KEY # Description QTY. or Quantity PER Boiler or Crown P.NPage 3029 Quantity PER Boiler or Crown P.N3130 PN980270 Rev609/10

TWZ150, TWZ125, TWZ065, TWZ075, TWZ100 specifications

Crown Boiler, known for its solid and reliable heating solutions, has designed the TWZ series to provide effective heating for both residential and commercial applications. The models in this series—TWZ090, TWZ120, TWZ175, TWZ200, and TWZ100—offer varying capacities and features tailored to meet diverse heating needs.

One of the key features of the TWZ series is its efficiency. These boilers are designed with a cast-iron heat exchanger that maximizes thermal efficiency, allowing for optimal heat transfer. This not only helps in reducing energy consumption but also ensures that the home remains warm and comfortable during the colder months. With an annual fuel utilization efficiency (AFUE) rating that can reach up to 85%, users can expect lower energy bills as well.

Each model in the TWZ series is equipped with a durable and robust construction. The cast iron sections provide increased resistance to wear and tear, making the TWZ series a long-lasting solution for heating needs. This is particularly beneficial for users looking for reliability over time, as the longevity of these boilers reduces the need for frequent replacements.

In terms of technology, the TWZ series features advanced controls that enhance functionality and ease of use. These boilers are compatible with various heating control systems, allowing users to fine-tune their heating setup according to their specific requirements. The inclusion of a flame safeguard system further ensures safety during operation, reducing the risk of malfunctions and improving overall reliability.

The TWZ series is designed for easy installation and maintenance. With options for direct venting or conventional chimney venting, homeowners and installers can choose the most suitable configuration for their properties. Additionally, the maintenance access points on these boilers make routine service checks simple and efficient, ensuring that the boilers remain in optimal condition.

Another important characteristic of the Crown Boiler TWZ series is its quiet operation. Advanced engineering minimizes noise production, making these boilers ideal for residential settings where peace and comfort are valuable.

In conclusion, the Crown Boiler TWZ090, TWZ120, TWZ175, TWZ200, and TWZ100 models offer a compelling combination of efficiency, durability, advanced technology, and user-friendly features. Whether for residential or light commercial use, they represent an excellent choice for anyone seeking reliable heating solutions.