Bryan Boilers RV Series Length, Overall Gas Supply Return, Min. Tube Clearance for Height, Nozzle

Page 4

Bryan RV Series Steam & Hot Water Boilers

STEAM HEATING/PROCESSING BOILER DIMENSIONS in inches (cm)

 

A

B

C

D

E

F

 

G

H

I

J

K

L

Boiler

Length

Flue

Flue

Overall

Gas

Supply

Return

Width

Min. Tube

Clearance for

Height

Floor to

Nozzle

Model

of

Location

Size

Length

Train

Conn.

Outside

Removal

Servicing

Over

Flow

Number

Jacket

 

 

 

Connection

15 psi

150 psi

 

Jacket

Clearance

Burner

Jacket

Nozzle

RV350-S

98

16

16

130½

6

4

2

55

32

48

100¼

104¾

(248.92)

(40.64)

(40.64)

(331.47)

(6.35)

(15.24)

(10.16)

(5.08)

(139.70)

(81.28)

(121.92)

(254.64)

(266.1)

 

RV400-S

111

18¾

16

143½

8

6

2

55

32

48

100¼

104¾

(281.94)

(47.63)

(40.64)

(364.49)

(6.35)

(20.32)

(15.24)

(5.08)

(139.70)

(81.28)

(121.92)

(254.64)

(266.1)

 

RV450-S

120½

18¾

16

153¼

8

6

2

55

32

48

100¼

104¾

(306.07)

(47.63)

(40.64)

(389.26)

(6.35)

(20.32)

(15.24)

(5.08)

(139.70)

(81.28)

(121.92)

(254.64)

(266.1)

 

RV500-S

130¼

18¾

16

163

8

6

2

55

32

48

100¼

104¾

(330.84)

(47.63)

(40.64)

(414.02)

(6.35)

(20.32)

(15.24)

(5.08)

(139.70)

(81.28)

(121.92)

(254.64)

(266.1)

 

RV550-S

143¼

18¾

16

175¾

10

6

2

55

32

48

100¼

104¾

(363.83)

(47.63)

(40.64)

(446.41)

(6.35)

(25.40)

(15.24)

(5.08)

(139.70)

(81.28)

(121.92)

(254.64)

(266.1)

 

RV600-S

152¾

18¾

16

185¼

10

6

2

55

32

48

100¼

104¾

(387.99)

(47.63)

(40.64)

(470.54)

(6.35)

(25.40)

(15.24)

(5.08)

(139.70)

(81.28)

(121.92)

(254.64)

(266.1)

 

RV700-S

175¼

20¾

20

214½

10

6

2

55

32

48

100¼

104¾

(445.14)

(52.71)

(50.80)

(544.83)

(6.35)

(25.40)

(15.24)

(5.08)

(139.70)

(81.28)

(121.92)

(254.64)

(266.1)

 

RV800-S

197¾

20¾

20

237¼

10

6

2

55

32

48

100¼

104¾

(502.29)

(52.71)

(50.80)

(602.62)

(6.35)

(25.40)

(15.24)

(5.08)

(139.70)

(81.28)

(121.92)

(254.64)

(266.1)

 

HOT WATER HEATING BOILER DIMENSIONS in inches (cm)

 

 

A

B

C

D

E

F

G

H

I

J

K

L

 

Boiler

Length

Flue

Flue

Overall

Gas

Supply

Return

Width

Min. Tube

Clearance for

Height

Floor to

 

Model

of

Train

Outside

Removal

Servicing

Over

Flow

 

Location

Size

Length

Nozzle

Nozzle

 

Number

Jacket

Connection

Jacket

Clearance

Burner

Jacket

Nozzle

 

RV350-W

98

16

16

130½

4

4

50

32

48

87½

90

 

(248.92)

(40.64)

(40.64)

(331.47)

(6.35)

(10.16)

(10.16)

(127.00)

(81.28)

(121.92)

(222.25)

(228.60)

 

 

 

RV400-W

111

18¾

16

143½

6

6

50

32

48

87½

90

 

(281.94)

(47.63)

(40.64)

(364.49)

(6.35)

(15.24)

(15.24)

(127.00)

(81.28)

(121.92)

(222.25)

(228.60)

 

 

 

RV450-W

120½

18¾

16

153¾

6

6

50

32

48

87½

90

 

(306.07)

(47.63)

(40.64)

(389.25)

(6.35)

(15.24)

(15.24)

(127.00)

(81.28)

(121.92)

(222.25)

(228.60)

 

 

 

RV500-W

130¼

18¾

16

163

6

6

50

32

48

87½

90

 

(330.84)

(47.63)

(40.64)

(414.02)

(6.35)

(15.24)

(15.24)

(127.00)

(81.28)

(121.92)

(222.25)

(228.60)

 

 

 

RV550-W

143½

18¾

16

175¾

6

6

50

32

48

87½

90

 

(364.49)

(47.63)

(40.64)

(446.41)

(6.35)

(15.24)

(15.24)

(127.00)

(81.28)

(121.92)

(222.25)

(228.60)

 

 

 

RV600-W

152¾

18¾

16

185¼

6

6

50

32

48

87½

90

 

(387.99)

(47.63)

(40.64)

(470.54)

(6.35)

(15.24)

(15.24)

(127.00)

(81.28)

(121.92)

(222.25)

(228.60)

 

 

 

RV700-W

175¾

20¾

20

214½

6

6

50

32

48

87½

90

 

(446.41)

(52.71)

(50.80)

(554.83)

(6.35)

(15.24)

(15.24)

(127.00)

(81.28)

(121.92)

(222.25)

(228.60)

 

 

 

RV800-W

197¾

20¾

20

237¼

6

6

50

32

48

87½

90

 

(502.29)

(52.71)

(50.80)

(602.62)

(6.35)

(15.24)

(15.24)

(127.00)

(81.28)

(121.92)

(222.25)

(228.60)

 

 

Specifications subject to change without notice. Consult factory to consult on other boiler options.

Bryan Steam LLC Leaders Since 1916

783 N. Chili Ave., Peru, Indiana 46970 U.S.A.

Phone:765-473-6651 • Internet:www.bryanboilers.com

Fax: 765-473-3074E-mail:bryanboilers@iquest.net

Form No. 5310

©2007 Bryan Steam LLC

Printed in USA

 

 

57-8739

Image 4
Contents Bryan Boilers Bryan RV Series Boiler Specifications Hot water boiler Water BoilerSteam Boiler Straight gas fired unitLength Overall Gas Supply ReturnMin. Tube Clearance for Height Nozzle