INSTALLER/CONFIGURATION MENU
Press the Menu button for at least 5 seconds. The display will show item #1 in the table below. Press Menu to advance to the
next menu item. Press or to change a menu item.
INSTALLER/CONFIGURATION MENU
MENU |
|
| PRESS | DISPLAYED | Press | or | to |
|
REF. | HP | SS | BUTTON | (FACTORY DEFAULT) | select from listed options | COMMENTS | ||
|
|
|
|
|
|
|
| |
1 | 1 |
| MENU | On (Cool O) | Heat b On |
| Reversing Valve Output (Heat Pump switch S8 | |
|
|
|
|
|
|
|
| must be in the Heat Pump HP position) |
2 | 2 | 1 | MENU | P (2) |
| P 3, P 0 |
| Selectable Programs Per Week |
|
|
|
|
|
|
|
| (For programmable thermostat only) |
|
|
|
|
|
|
| ||
3 | 3 | 2 | MENU | Cool Saving CS (OFF) | Cool Saving CS On | Select Cool Savings on or off | ||
|
|
|
|
|
|
|
| |
|
|
|
| CS (3) | 6, 5, 4, 2, 1 |
| Selects Cool Savings value 1 (low) to 6 (high) | |
4 | 4 | 3 | MENU | E (On) |
| E OFF |
| Selects Energy Management Recovery (EMR) |
|
|
|
|
|
|
|
| on or off |
|
|
|
|
|
|
|
|
|
5 |
| 4 | MENU | CR Heat |
| FA, SL |
| Adjustable Anticipation (Heat) (only when |
|
|
|
| (ME) |
|
|
| heat pump switch is at the SS position) |
|
|
|
|
|
|
|
|
|
6 |
| 5 | MENU | CR Cool |
| SL |
| Adjustable Anticipation (Cool) (only when |
|
|
|
| (FA) |
|
|
| heat pump switch is at the SS position) |
|
|
|
|
|
|
|
|
|
7 | 5 |
| MENU | CR Heat Pump |
| SL |
| Adjustable Anticipation (Heat Pump) (only |
|
|
|
| (FA) |
|
|
| when heat pump switch is at the HP position) |
|
|
|
|
|
|
|
|
|
8 | 6 | 6 | MENU | CL (OFF) |
| CL On |
| Compressor Lockout Time |
|
|
|
|
|
|
|
| |
9 | 7 | 7 | MENU | Auto Heat | Heat Cool Off, |
| System Mode Configuration | |
|
|
|
| Cool Off | Heat Off with Fan icon, | with Automatic Changeover | ||
|
|
|
|
| Heat Off without Fan |
| ||
|
|
|
|
| icon, Cool Off, |
|
| |
|
|
|
|
|
| Auto Off |
|
|
|
|
|
|
|
|
| ||
|
|
|
| Cool Off Heat | Heat Off with Fan icon, | System Mode Configuration | ||
|
|
|
|
| Heat Off without |
| without Automatic Changeover | |
|
|
|
|
| Fan icon, Cool Off |
| ||
10 | 8 | 8 | MENU | L (On) |
| L OFF |
| Selects Display Light on or off |
|
|
|
|
|
|
| ||
11 | 9 | 9 | MENU | 0 HI | 1 HI, 2 HI, 3HI, 4 HI, | Adjustable Ambient Temperature Display | ||
|
|
|
|
| 1 LO, 2 LO, 3 LO, 4 LO |
| ||
|
|
|
|
|
|
|
|
|
12 | 10 | 10 | MENU | F |
| C |
| Selects Fahrenheit/Celcius Temperature Display |
|
|
|
|
|
|
| ||
13 | 11 | 11 | MENU | Change Filter (OFF) | Change Filter On | Selects Filter | ||
|
|
|
|
|
|
| ||
|
|
|
| Change Filter 200 h | 25 h to 1975 h in | When on, selects time in 25 hour increments | ||
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
14 | 12 | 12 | RUN |
|
|
|
| Returns to Normal Operation |
|
|
|
|
|
|
|
|
|
1)Select Reversing Valve Output (Heat Pump switch S8 must be set at HP) – The O/B option is factory set at "O" position. This will accommodate the majority of heat pump applications, which require the changeover relay to be energized in COOL. If the thermostat you are replac- ing or the heat pump being installed with this thermostat requires a "B" terminal, to energize the changeover relay in HEAT, the O/B option should be set at "B" position.
2)Program Options: This control can be configured for 5/2 day or 5/1/1 day programming or
pressing the or keys. A selection of 0 Days for
3)Select Cool Savings™: With Cool Savings™ enabled, the thermostat will make small adjustments to the setpoint temperature during periods of high demand to reduce AC
system running time and save energy. When the cooling system has been running for more than 20 minutes, humidity in the home will be lower and a higher setpoint temperature will feel comfortable. After 20 minutes of run time, the thermostat will start increasing the setpoint temperature in steps of less than one degree as the system continues to run. These adjustments will eventu- ally cause the system to satisfy the thermostat to turn the system off and reduce the energy consumption. When the Cool Savings™ feature is active and making adjust- ments, the display will show “Save” next to the setpoint temperature. The amount of the adjustments to the setpoint temperature is dependent on the Cool Savings™ value that is set, 1 being the least adjustment and 6 being the most adjustment. With this feature set to OFF, no change will occur when the AC system is continuously running during the periods of high demand. Periods of high demand will normally occur during the late afternoon and early evening on the hottest days of the summer.